Important Safety Information

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

The following checks shall be applied to installations 

using fl ammable refrigerants:

•  The charge size is in accordance with the room 

size within which the refrigerant containing 

parts are installed. 

•  The ventilation machinery and outlets are 

operating adequately and are not obstructed.

•  If an indirect refrigerating circuit is being used, 

the secondary circuit shall be checked for the 

presence of refrigerant.

•  Marking to the equipment continues to be visible 

and legible. Markings and signs that become 

illegible must be corrected.

•  Refrigeration pipe or components are installed in 

a position where they are unlikely to be exposed 

to any substance which may corrode refrigerant 

containing components, unless the components 

are constructed of materials which are inherently 

resistant to being corroded or are suitable 

protected against being corroded.

9.  Checks to electrical devices: 

Repair and 

maintenance to electrical components shall 

include initial safety checks and component 

inspection procedures. If a fault exists that 

could compromise safety, then no electrical 

supply shall be connected to the circuit until it 

is satisfactorily dealt with. If the fault cannot 

be corrected immediately but it is necessary to 

continue operation, an adequate temporary 

solution shall be used. This shall be reported to 

the owner of the equipment so all parties are 

advised.

Initial safety checks shall include:

•  That capacitors are discharged. This shall be 

done in a safe manner to avoid possibility of 

sparking.

•  That no live electrical components and wiring 

are exposed while charging, recovering or 

purging the system.

•  That there is continuity of earth bonding.

Repairs to sealed components

1.  During repairs to sealed components, all 

electrical supplies shall be disconnected from 

the equipment being worked upon prior to any 

removal of sealed covers, etc. If it is absolutely 

necessary to have an electrical supply to 

equipment during servicing then a permanently 

operating form of leak detection shall be located 

at the most critical point to warn of a potentially 

hazardous situation.

2.  To ensure that by working on electrical 

components the casing is not altered in such 

a way that the level of protection is affected, 

particular attention shall be paid to the 

following:

•  Damage to cables, excessive number of 

connections, terminals not made to original 

specifi cation, damage to seals, incorrect fi tting 

of glands, etc.

•  Ensure the apparatus is mounted securely.

•  Ensure that seals or sealing materials have 

not degraded such that they no longer serve 

the purpose of preventing the ingress of 

fl ammable atmospheres. Replacement parts 

shall be in accordance with the manufacturer’s 

specifi cations.

Note: The use of silicon sealant may inhibit the 

effectiveness of some types of leak detection 

equipment. Intrinsically safe components do not 

have to be isolated prior to working on them.

Repair to intrinsically safe components

Do not apply any permanent inductive or 

capacitance loads to the circuit without ensuring 

that this will not exceed the permissible voltage 

and current permitted for the equipment in use. 

Intrinsically safe components are the only types that 

can be worked on while live in the presence of a 

fl ammable atmosphere. The test apparatus shall 

be at the correct rating. Replace components only 

with parts specifi ed by the manufacturer. Other 

parts may result in the ignition of refrigerant in the 

atmosphere from a leak.

4

Содержание DAC0100B5WDB

Страница 1: ...OHIO USA 45840 OWNER S MANUAL MANUEL DU PROPRI TAIRE MANUAL DEL PROPIETARIO www Danby com AIR CONDITIONER Owner s Manual 1 16 CLIMATISEUR Manual du propri taire 17 32 AIRE ACONDICIONADO Manual del pro...

Страница 2: ...ide the original purchase receipt to validate your warranty and receive service Model Number _________________________________________________ Serial Number ___________________________________________...

Страница 3: ...of the appliance just above the power cord contains electrical and other technical data This appliance is not intended for use by persons including children whose physical sensory or mental capabilit...

Страница 4: ...nt detector prior to and during work to ensure the technician is aware of potentially ammable atmospheres Ensure that the leak detection equipment being used is suitable for use with ammable refrigera...

Страница 5: ...recovering or purging the system That there is continuity of earth bonding Repairs to sealed components 1 During repairs to sealed components all electrical supplies shall be disconnected from the equ...

Страница 6: ...d Extreme care shall be taken not to over ll the refrigeration system Prior to recharging the system it shall be pressure tested with OFN The system shall be leak tested on completion of charging but...

Страница 7: ...hat there are labels on the equipment stating the equipment contains ammable refrigerant Recovery When removing refrigerant from a system either for servicing or decommissioning it is recommended good...

Страница 8: ...e ef cient functioning Do not install the appliance where leakage of combustible gas is suspected This appliance is designed to evaporate condensation under normal conditions Under extremely hot or hu...

Страница 9: ...left and right on the frames This refers to the left and right sides of the appliance when facing the front of the appliance 8 REQUIRED TOOLS Screwdrivers Phillips and at head Power Drill 3 2mm 1 8in...

Страница 10: ...frame using two 13 mm 1 2 inch screws 9 Check the Tilt Angle The air conditioner should be tilted downward towards the outside approximately 3 to 4 This tilt will encourage any condensed water to dra...

Страница 11: ...crease buttons for 3 seconds to change between C and F 4 Power Button Used to turn the appliance on or off OPERATING INSTRUCTIONS 10 A Energy saver mode indicator B Wireless connection indicator C Coo...

Страница 12: ...y saver function 7 LED Button Press to turn the LED back light on or off Press 7 times to activate the wireless connection Follow the directions on the wireless connection app for more information 8 T...

Страница 13: ...sted and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against interference in a resident...

Страница 14: ...Visit https www danby com support apps to download the application and learn about its operation 13 SHORTCUT FUNCTION The shortcut function is only available on the remote control It can be used to se...

Страница 15: ...all for service L0 Displayed when the room temperature is lower than 0 C 32 F HI Displayed when the room temperature is higher than 37 C 99 F AS Room temperature sensor error ES Evaporator temperature...

Страница 16: ...he appliance Water dripping inside Appliance is not properly angled to allow water to drain to the outside Water dripping outside On very hot or humid days dripping water from the back of the applianc...

Страница 17: ...ce depot Any appliance requiring service outside the limited boundaries of In Home Service will be the consumer s responsibility to transport at their own expense to the original point of purchase or...

Страница 18: ...e re u d achat original pour valider votre garantie et recevoir le service Num ro de mod le _____________________________________________ Num ro de serie ______________________________________________...

Страница 19: ...plosion Fluide frigorig ne in ammable utilis Ne pas endommager le circuit de r frig rant Assurez vous que les r parations sont effectu es par du personnel autoris par l usine a n de minimiser les domm...

Страница 20: ...ue le technicien est conscient des atmosph res potentiellement in ammables Assurez vous que l quipement de d tection des fuites utilis convient aux uides frigorig nes in ammables c est dire qu il ne p...

Страница 21: ...mise la terre R paration de composants scell s 1 Lors de la r paration de composants scell s toutes les alimentations lectriques doivent tre d branch es de l quipement utilis avant toute d pose de co...

Страница 22: ...r me doit tre pris pour ne pas trop remplir le syst me de r frig ration Avant de recharger le syst me il doit tre test sous pression avec OFN Le syst me doit tre soumis un test d tanch it la n du char...

Страница 23: ...sur l quipement indiquant que celui ci contient du r frig rant in ammable R cup ration Lorsque vous retirez du uide frigorig ne d un syst me que ce soit pour un entretien ou une mise hors service il e...

Страница 24: ...ctionnement ef cace Ne pas installer l appareil en cas de suspicion de fuite de gaz combustible Cet appareil est con u pour vaporer la condensation dans des conditions normales Dans des conditions ext...

Страница 25: ...nt tiquet s gauche et droite sur les cadres Il s agit des c t s gauche et droit de l appareil face l avant de l appareil 24 OUTILS REQUIS Tournevis Phillips et t te plate Perceuse lectrique 3 2 mm 1 8...

Страница 26: ...urit sur le cadre de la fen tre ext rieure l aide de deux vis de 13 mm 1 2 pouce 25 V ri ez l angle d inclinaison Le climatiseur doit tre inclin vers le bas vers l ext rieur environ 3 4 Cette inclinai...

Страница 27: ...pour passer de C F 4 Bouton d alimentation Utilis pour allumer ou teindre l appareil A Indicateur de mode d conomie d nergie B Indicateur de connexion sans l C Indicateur de mode froid D Indicateur de...

Страница 28: ...d nergie 7 Bouton DEL Appuyez pour allumer ou teindre le r tro clairage Appuyez 7 fois sur la touche pour activer la connexion sans l Suivez les instructions sur l application de connexion sans l pou...

Страница 29: ...de classe B conform ment la partie 15 des r gles de la FCC Ces limites sont con ues pour fournir une protection raisonnable contre les interf rences dans une installation r sidentielle Cet quipement...

Страница 30: ...l Rendez vous sur https www danby com support apps pour t l charger l application et d couvrir son fonctionnement FONCTION DE RACCOURCI La fonction de raccourci est uniquement disponible sur la t l c...

Страница 31: ...ambiante est inf rieure 0 C 32 F HI S af che lorsque la temp rature ambiante est sup rieure 37 C 99 F AS Erreur du capteur de temp rature ambiante ES Erreur du capteur de temp rature de l vaporateur N...

Страница 32: ...u s coule l int rieur L appareil n est pas correctement inclin pour permettre l eau de s couler vers l ext rieur Eau d gouttant l ext rieur Sur des jours tr s chauds ou humides l eau qui goutte l arri...

Страница 33: ...premiers douze 12 mois toutes les pi ces fonctionnelles de ce produit qui s av rent d fectueuses seront r par es ou remplac es selon le choix du garant sans frais l acheteur initial Danby se r serve l...

Страница 34: ...ci n para obtener un servicio bajo garant a Debe proporcionar el recibo de compra original para validar su garant a y recibir servicio N mero de modelo _____________________________________________ N...

Страница 35: ...STRUCCIONES DE SEGURIDAD REQUERIMIENTOS DE SEGURIDAD PELIGRO Riesgo de incendio o explosi n Refrigerante in amable utilizado No da e el circuito de refrigerante Aseg rese de que el servicio sea realiz...

Страница 36: ...nte el trabajo para garantizar que el t cnico tenga conocimiento de las atm sferas potencialmente in amables Aseg rese de que el equipo de detecci n de fugas que se est utilizando sea adecuado para el...

Страница 37: ...ientras se est cargando recuperando o purgando el sistema Que hay continuidad de la uni n de la tierra Reparaciones a componentes sellados 1 Durante las reparaciones de componentes sellados todos los...

Страница 38: ...ener mucho cuidado de no sobrecargar el sistema de refrigeraci n Antes de recargar el sistema se someter a prueba de presi n con OFN El sistema debe ser probado contra fugas al nalizar la carga pero a...

Страница 39: ...o que indiquen que el equipo contiene refrigerante in amable Recuperaci n Cuando se retira refrigerante de un sistema ya sea para servicio o cierre se recomienda que todos los refrigerantes se elimine...

Страница 40: ...a garantizar un funcionamiento e caz No instale el aparato donde se sospeche una fuga de gas combustible Este aparato est dise ado para evaporar la condensaci n en condiciones normales En condiciones...

Страница 41: ...derecha en los marcos Esto se re ere a los lados izquierdo y derecho del aparato cuando est frente a la parte frontal del aparato 40 HERRAMIENTAS REQUERIDAS Destornilladores Phillips y cabeza plana T...

Страница 42: ...ornillos de 13 mm 1 2 pulgada 41 Compruebe el ngulo de inclinaci n El acondicionador de aire debe inclinarse hacia abajo hacia el exterior aproximadamente de 3 a 4 Esta inclinaci n estimular el drenaj...

Страница 43: ...nte 3 segundos para cambiar entre C y F 4 Bot n de encendido Se utiliza para encender o apagar el aparato A Indicador de modo de ahorro de energ a B Indicador de conexi n inal mbrica C Indicador de mo...

Страница 44: ...ci n de ahorro de energ a 7 Bot n LED Presione para encender o apagar la luz de fondo del LED Presiona 7 veces para activar la conexi n inal mbrica Siga las instrucciones de la aplicaci n de conexi n...

Страница 45: ...y cumple con los l mites para un dispositivo digital de Clase B de acuerdo con la Parte 15 de las Reglas de la FCC Estos l mites est n dise ados para proporcionar una protecci n razonable contra inte...

Страница 46: ...aplicaci n y obtener informaci n sobre su funcionamiento FUNCI N DE ACCESO DIRECTO La funci n de acceso directo solo est disponible en el control remoto Se puede utilizar para establecer un ajuste fa...

Страница 47: ...Si el error persiste llame al servicio t cnico L0 Se muestra cuando la temperatura ambiente es inferior a 0 C 32 F HI Se muestra cuando la temperatura ambiente es superior a 37 C 99 F AS Error del se...

Страница 48: ...arato El agua que gotea en el interior El aparato no est correctamente inclinado para permitir que el agua se drene hacia el exterior El agua que gotea fuera En d as muy calurosos o h medos el agua go...

Страница 49: ...rea limitada de Servicio en Domicilio el cliente ser responsable por transportar dicho artefacto hasta el Taller de Servicio Autorizado mas cercano Si el electrodom stico est instalado en un lugar que...

Страница 50: ...___________________ __________________________________________________________________________________________ _________________________________________________________________________________________...

Страница 51: ...___________________ __________________________________________________________________________________________ _________________________________________________________________________________________...

Страница 52: ...MODEL MOD LE MODELO Printed in China Imprim en Chine Impreso en China Danby Products Limited Guelph ON Canada N1H 6Z9 Danby Products Inc Findlay Ohio USA 45840 DAC0100B5WDB DAC120B5WDB 6...

Отзывы: