6.7.2
Behavior in the event of an error (with standard setting)
The behavior of the servo amplifier always depends on the current setting of a number of
different parameters (e.g., ACTFAULT, VBUSMIN, VELO, STOPMODE, etc.; see online
help). The diagram shows the startup procedure and the procedure that the internal con-
trol system follows in the event of one or more electrical supply phases failing, assuming
that the standard parameter settings apply.
(F16/F19 = error messages Mains BTB /input phase, F05 = error message Undervoltage)
Even if there is no intervention from an external control system (in the example, the
ENABLE signal remains active), the motor is immediately braked using the emergency
stop ramp if an input phase error is detected and assuming that no changes have been
made to the factory setting (ACTFAULT=1).
SERVOSTAR
®
300 Product Manual
27
Danaher Motion
10/2007
Technical description