3.5.
Connection to a Programmable Logic Controller (PLC)
For instructions about the electrical connection of the PLC, please refer to the
original equipment instruction manual.
Prior to connecting the
DAT 420
to a PLC please follow these instructions:
▪
Use an external stabilized power supply for the detector (+24 Vdc).
▪
Ensure that the polarity of the detector output signal matches the polarity of the PLC input.
▪
Please read the instructions below regarding the loop resistance.
Loop resistance
The supply voltage applied to the detector has direct influence on the MAXIMUM loop resistance.
This resistance includes the cable resistance and the shunt resistor of the PLC.
Example
-
The minimum operating voltage of the
DAT 420
is 10 Vdc.
-
Consider a supply voltage of 24 Vdc, the allowable voltage drop due to the loop resistance is
14 Vdc.
-
The MAXIMUM loop resistance will be:
00
7
0.02
14
I
10
-
24
R
Loop
Loop
=
=
=
ohms
-
With
20
I
Loop
=
mA
-
For a 1 to 5 Vdc input scale, the shunt resistor to put across the PLC input will be:
250
0.02
5
I
5
R
Loop
Shunt
=
=
=
ohms
-
Therefore, the maximum allowable resistance for the cable will be:
450
250
700
R
Cable
=
−
=
ohms