No Display message
Description
10
DC bus unbalance
The difference between the positive and negative DC buses exceeds
30 V
11
Mains site wiring fault
Wrong input phase rotation
12
Soft start fault
Rectifier can’t start because the DC bus voltage is too low
13
Input neutral line missing
UPS switched to battery mode
14
Battery reverse
Battery polarity incorrect
15
No battery
Battery is disconnected
16
Positive battery charger fault
Charger shutdown
17
Negative battery charger fault
Charger shutdown
18
Battery under voltage
Charger is deactivated
19
Battery over voltage
Charger is deactivated
20
Battery under voltage pre-warning
The UPS is in battery mode and the battery voltage is low.
Note:
Runtime is limited.
21
Mains freq. abnormal
Rectifier shutdown
22
Mains volt. abnormal
Rectifier shutdown
23
Inverter fault
The inverter has shutdown because its output voltage is out of range
(rated v12.5% and
–25%), and the UPS has transferred to
bypass. Power off the UPS to clear this fault.
24
Inverter IGBT bridge direct conduct
protection
Inverter shutdown
25
Inverter thyristor short fault
There is a short circuit inverter SCR
26
Inverter thyristor broken fault
There is an open circuit inverter SCR
27
Bypass thyristor short fault
There is a short circuit bypass SCR
28
Bypass thyristor broken fault
There is an open circuit bypass SCR
29
CAN comm. fault
CAN communication fault
30
Parallel system load sharing fault
Load sharing unbalance has exceeded 30%
31
Bypass site wiring fault
Wrong bypass phase rotation
32
System not synchronized to bypass
System cannot synchronize to bypass. Mode may not be available
33
Bypass unable to trace
34
Bypass not available
The frequency or voltage is out of range for bypass
35
IGBT over current
36
Fuse blown
One or more inverter fuses has blown
37
Parallel cable connection error
A parallel cable is not correctly connected in a parallel system
38
Parallel relay fault
Occurs when a parallel circuit relay cannot be turned on correctly. The
UPS shuts down. Power off the UPS to clear this fault
39
LBS not sync.
Two paralleled system are not synchronised
40
Initialisation fault
41
Inverter on invalid
The inverter on button has been activated
42
Overload
The load exceeds the UPS capacity
43
Parallel overload
44
DC component over limitation
The DC component exceeds the specified value