Dale Power Solutions Ltd
User Manual
28
…………………………………………………………………………………………………………
Appendix 3 Specifications
Electrical
Model
E206(E)
E2010(E)
Capacity (Int. battery or 20 cell external battery)
6 kVA, 4.8 kW, 0.8 pf
10 kVA, 8 kW, 0.8 pf
Capacity (16 or 18 cell external battery)
6 kVA, 4.2 kW, 0.7 pf
10 kVA, 7 kW, 0.7 pf
Input
Power factor
≥0.99
Rated voltage (nominal)
220 Va.c. or 230 Va.c.
Rated frequency
50 Hz or 60 Hz
Voltage range
145 to 280 Va.c.
Maximum input voltage
320 Va.c., 1 h
Frequency range
40 to 70 Hz
Bypass voltage range
max: +5%, +10% or +15%, d5%
min: -20%, -30% or -45%, default -45%
Bypass frequency range
±1%, ±2%, ±4%, ±5%, ±10%
THDI
5% (100% linear load, input THDV
≤1%)
5% (100% non-linear load, input THDV
≤1%)
Battery
Number of 12 V batteries
16, 18 or 20 batteries in series, centre tapped
Battery type
VRLA
Charge model
Boost charge or float charge auto switch
Charge time
Boost charge up to 20 h (max)
Charge current (A)
6 kVA: 1 A (S) / 6 A (H)
10 kVA: 1 A (S) / 6 A (H)
Output
Output type
Single phase (L, N and E)
Output precision
1.0%
Voltage distortion (THD)
<2% with 100% linear load
<3.5% with 100% non-linear load
Rated voltage
220 Va.c. / 230 Va.c.
Frequency precision
±0.1%
Frequency
50 Hz / 60 Hz
Frequency tracking speed
1 Hz/s