TECHNICAL PARAMETERS
Model
E-HP 9
E-HP 12
E-HP 15
E-HP 18
E-HP 24
E-HP 30
Supply voltage, 50 Hz [V]
3 ~ 400
Max. fan power [W]
140
253
Fan current [A]
0,61
1,1
Electric heater power [kW]
9
13,0
12
15
18
26,0
24
30
Electric heater current [A]
17,3
21,7
34,6
43,3
Total unit power [kW]
9,14
12,14
15,14
18,25
24,25
30,25
Total unit current [A]
13,6
17,9
22,3
27,1
35,7
44,4
Air capacity [m
3
/h]
2300
4000
RPM [min
-1
]
1420
1480
Casing material
Painted steel
Noise level, 5 m, [dB(A)]
55
61
Ingress protection rate
IP 21
Weight [kg]
32
48
Transported air must not contain any flammable or explosive mixtures, evaporation of chemicals,
coarse dust, soot and oil particles, sticky substances, fibrous materials, pathogens or any other
harmful substances.
DESIGN AND OPERATING LOGIC
The unit is designed for indoor air heating by means of the electric heater and uniform air flow
distribution with the fan and louvre shutters.
The special unit design enables quick air heating in large premises due to high-efficient electric
heater and a powerful fan. The electric connections and control connections are performed in a
terminal box at the side unit panel.
UNIT MOUNTING AND SET-UP
THE UNIT INSTALLATION IS ALLOWED BY QUALIFIED PROFESSIONALS AFTER
CAREFUL STUDY OF THE USER’S MANUAL.
While mounting the unit provide the minimum required access to the unit for maintenance and
repair.
The unit is designed for wall mounting or mounting to any other vertical surface or ceiling mounting
with fixing bracket.
While mounting the unit provide free air flow to the unit intake opening. The minimum distance from
the wall or the ceiling to the unit is 300 mm.