background image

DataTime

®

 Series 50 

 

ELECTRICAL 

13” LED Time & Temp Displays 

 

INSTALLATION 

3-3

3.2 Power 

Connection 

 
 

Reference Drawings:

 

Schematic, 13 LOC T&T ..........................

Drawing A-80682

 

 

Note

: When power is run to the display, a disconnect switch or plug must be provided within 

sight of the display.  
 
Refer to 

Figures 6

 and 

7

. Power is supplied to the display through the terminal block labeled 

TB41. The service required for a single face display is 120 VAC. Service for a 2V display is 
120/240 VAC 

single phase

. The display amperage is stated on the display specification label. 

Follow the instructions below to connect power to the display. 
 

1.

  Run power through conduit into the display through one of the knockouts provided 

and route over to the termination panel.  

2.

  Connect the white neutral wire(s) to “120VAC-N” on TB41. 

3.

  Connect the black 120 VAC wire to “120VAC-L” on TB41. 

 
 

3.3 Grounding 

 

All power service must be supplied with an earth-ground wire. Use the following instructions to 
properly ground the display: 
 

1.

  Attach the ground wire to the earth ground lug in the termination panel marked with 

“Earth Ground” (

Figure 6

). 

2.

  Attach the ground wire to a copper earth ground rod installed according to the 

National Electrical Code. Do not ground to any steel columns supporting the display. 

 
 

3.4 Handset 

Connection 

 

The handset enclosure consists of a small weatherproof box which houses the handset and a 
junction box (refer to 

Figure 8

). A 25-foot signal cable is provided to connect the handset 

enclosure to the display. The end terminated with spade lugs goes to the handset j-box. Install the 
handset as follows: 
 

1.

  Mount the handset enclosure at the base of the display in a position where it will be 

possible to see the display when using the handset. The handset has a six-foot cable 
that plugs into the j-box. 

2.

  Run the signal cable through 1/2” conduit from the handset enclosure into the 

display, and route to the display controller enclosure. Knockouts are provided in both 
the handset enclosure and the display. 

3.

  Remove the cover from the handset j-box and route the cable into the j-box. Connect 

the three wires terminated with spade lugs to the terminal block mounted on the j-box 
cover. Connect CLR (SIG) to WHT, BLK, and RED respectively, already connected 
to the terminal block. Cut the shield back and leave it unterminated. Replace the 
cover and plug in the handset. 

4.

  Remove the cover from the controller enclosure and connect the control cable to TB3 

on the controller. Connect CLR to position 1, RED to position 6, and BLK to 
position 5. Connect the shield drain wire to position 5 as well. 

Содержание DATATIME 50 Series

Страница 1: ...been taken in the preparation of this manual the publisher assumes no responsibility for errors or omissions No part of this book covered by the copyrights hereon may be reproduced or copied in any f...

Страница 2: ......

Страница 3: ...ster Slave Connection 3 7 4 OPERATION 4 1 4 1 Using the Handset to Program the Controller 4 1 4 2 Setting the Time 4 1 4 3 Setting the Functions 4 2 4 4 The 14 Display Functions 4 2 4 4 1 Function 1 D...

Страница 4: ...erature 5 5 5 3 3 Dimming 5 6 5 4 Repair 5 6 5 4 1 Fuse Replacement 5 6 5 4 2 Exchanging a Controller 5 7 5 4 3 Exchanging a Driver 5 7 5 5 Structural Inspection 5 7 5 6 Daktronics Exchange Replacemen...

Страница 5: ...isconnect power when servicing the displays 6 Do not modify the displays or attach any panels or coverings to the displays without the written consent of Daktronics Inc The box below is an illustratio...

Страница 6: ......

Страница 7: ......

Страница 8: ......

Страница 9: ...and total wind loading of the display and advertising panels that make up the entire display Column selection is critical and should be done only by a qualified individual Only pipe and square or rect...

Страница 10: ......

Страница 11: ......

Страница 12: ......

Страница 13: ...y Access Access the inside of the display through the hinged face panel to perform electrical installation The face panel is held closed with 1 4 turn fasteners along the bottom Release the fasteners...

Страница 14: ...e directly to the display controller Both the power termination panel and the controller enclosure can be accessed by removing the 1 4 turn retaining screws in the cover refer to Figure 7 Note The 1 4...

Страница 15: ...ectrical Code Do not ground to any steel columns supporting the display 3 4 Handset Connection The handset enclosure consists of a small weatherproof box which houses the handset and a junction box re...

Страница 16: ...l temperature fluctuations Usually a separation of at least 20 30 feet horizontally is required to achieve this Locations where air movement is restricted are also unsatisfactory A first choice sensor...

Страница 17: ...the sign rather than concrete or some other material Display mounted sensors are generally discouraged because of the potential of the display to self heat and gain heat from the sun causing erroneou...

Страница 18: ...ough 1 2 conduit to the display To reduce the conduit entrances route this cable into the display through the same conduit used by the handset controller signal cable refer to Figure 4 2 Route the cab...

Страница 19: ...pple or other appropriate method When back to back the displays can have a maximum separation of 24 due to the harness length The interconnect harness consists of eight 8 digit cables Each digit cable...

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ...ton steps the display controller through its different modes Pressing SET once will put the controller in the Function Set mode This mode is used to set all Function values for the display Pressing th...

Страница 24: ...n number is being displayed press the SET button once to return to the operating mode If one of the function values is being displayed press the SET button twice to return to the operating mode The di...

Страница 25: ...this function value to 1 for Manual Bright Set the value to 2 for Manual Dim Default 0 4 4 4 Function 4 Font Select One of two fonts can be selected using this function The two fonts rounded and bloc...

Страница 26: ...nheit Celsius F C 3 Fahrenheit Celsius F degree 4 4 7 Functions 7 10 Shut Down Feature The controller can be programmed to go into a shut down mode that blanks the display at a programmed time and sta...

Страница 27: ...lt 1 4 5 Operation Summary FUNCTION DESCRIPTION RANGE 1 Display Frame Duration 2 9 Seconds 2 Display Sequences T Time F Fahrenheit C Celsius P1 Price 1 P2 Price 2 Selections 0 20 0 F C 11 P1 C 1 T F 1...

Страница 28: ...it 2 digit 3 digit 4 decimal point and then wrap around to digit 1 again 5 Step through each digit position with the FUNCTION button and set the digit to the desired value with the VALUE button 6 When...

Страница 29: ...FF again If S2 is turned ON while S1 is ON the display pixels will cycle through a pattern of digits The display controller can get its time base from one of two sources A 50 or 60 hertz power line fr...

Страница 30: ......

Страница 31: ...steps are outlined as well Figures 6 and 11 show the component layout and locations in a display All of these components are located in the master face Figure 11 Block Diagram Component Layout 5 1 Th...

Страница 32: ...digits are connected directly into these jacks on the driver Figure 12 Dot Matrix Digit Segmentation 5 2 The Display Controller The Series 50 display controller is locked inside the display cabinet ne...

Страница 33: ...C 1 Photocell 2 Power 10 VAC 2 GND 3 Reset 3 5 Volts 4 Reset Ground 4 GND 5 Temp In TB1 6 GND Pin Function 1 Data Out 1 TB3 2 Data Out 1 Pin Function 3 Data Out 2 1 RX Handset 4 Data Out 2 2 TX 5 Swit...

Страница 34: ...OFF DS6 Not used OFF DS7 Source of Clock Time Base ON Internal Real Time Clock OFF Power Line Frequency 50 or 60 Hertz DS8 System Clock Turns ON and OFF at one second intervals RST Monitor Reset ON Mo...

Страница 35: ...by connecting the 9 pin to another digit If the problem occurs on this digit it indicates that the driver has failed If a pixel is stuck ON it usually can be fixed by replacing the driver Section 5 4...

Страница 36: ...equire one of the following Replacing a digit Replacing a blown fuse Exchanging a faulty controller or driver IMPORTANT NOTES FOR SERVICE DONE INSIDE THE DISPLAY This service should only be done by qu...

Страница 37: ...for corrosion especially at footing bolts and support or guy cables Fasteners should be checked and tightened or replaced as required 5 6 Daktronics Exchange Repair Return Programs To serve customers...

Страница 38: ...n the defective equipment within 30 days from the invoice date Daktronics also offers a Repair and Return program for items not subject to exchange Where to Send To return parts for service contact yo...

Страница 39: ......

Страница 40: ......

Страница 41: ...C 60 Hz outlet Also note that signal to the display and from a temperature sensor must be routed to the controller enclosure A 2 Installation Signal Connection The display is installed as stated in Se...

Страница 42: ...in the fourth right digit position of the display for prices appears as a 9 on the LCD When the cursor is in the fourth digit position in the Price Set Mode it will be on the e on the LCD when this ch...

Страница 43: ...following additions PART DESCRIPTION DAKTRONICS PART Indoor Console 0A 1114 20 Wall Transformer 0A 1065 0022 Console Cable W 1265 Figure 13 Installation Electrical layout Indoor Controller DataTime S...

Страница 44: ......

Страница 45: ...APPENDIX B FULL VIEW OPTION Refer to Figure 14 for the wiring diagram of the full view option Figure 14 Wiring Diagram Full View 2V DataTime Series 50 FULL VIEW OPTION 13 LED Time Temp Displays B 1...

Отзывы: