background image

DAKEN Users Manual –  PAGE 9

 Figure 4 – Warning plate symbol

  6.   The 

energiser earth electrode

 shall penetrate the ground to a depth of at least 1 m.

  7.   

Connecting leads

 that are run inside buildings shall be effectively insulated from the earthed structural 

parts of the building. This may be achieved by using insulated high voltage cable.

  8.   

Connecting leads

 that are run underground shall be run in a conduit of insulating material or else 

insulated high voltage cable shall be used. Care shall be taken to avoid damage to the 

connecting leads

 

due to the effects of animal hooves or tractor wheels sinking into the ground.

  9. 

 Connecting leads

 shall not be installed in the same conduit as the mains supply wiring, communicating 

cables or data cables.

10.   

Connecting leads

 and 

electric fence

 wires shall not cross above overhead power or communication 

lines.

11.   Crossings with overhead power lines shall be avoided wherever possible. If such a crossing cannot be 

avoided, it shall be made underneath the power line and as nearly as possible at right angles to it.

12.   If 

connecting  leads

  and 

electric  fence

  wires  are  installed  near  an  overhead  power  line,  the 

clearances shall be not less than those shown in table 3.

13.   If 

connecting leads

 and 

electric fence

 wires are installed near an overhead power line, their height 

above the ground shall not exceed 2 m. This height applies either side of the orthogonal projection of the 

outermost conductors of the power line on the ground surface, for a distance of 

* 2 m for power lines operating at a nominal voltage not exceeding 1,000 V
* 15 m for power lines operating at a nominal voltage exceeding 1,000 V.

3

 

Power line voltage V 

Clearance in metres

4
8

 

<=1000

>=1000 <=33 000

>33 000

Table 3 - Minimum Clearances from Power Lines

Содержание Techfence MT5

Страница 1: ...information FREECALL 1800 636 451 email daken nsw clarkequipment com au www daken com au INSTALLATION AND OPERATIONS MANUAL For Techfence Energiser Models Mains Powered MT5 MT15 35 60 and 100 Battery...

Страница 2: ...hout supervision Young children should be supervised to ensure that they do not play with the appliance SCOPE This manual is the users instruction manual for Daken Techfence energisers Models BT12 BT2...

Страница 3: ...lar Powered Energisers 5 Earthing 5 Solar Energiser Kit Installation 6 Checking your Solar Energiser is Operating Correctly 6 Estimated State of charge of a 12V car battery 6 TROUBLE SHOOTING 7 Testin...

Страница 4: ...wer the BT12 20 50 and 80 will run from a battery that is charged from a solar panel The BT12 requires a 10W panel and at least a 7Ah battery preferably 15Ah The BT20 requires a 20W panel and at least...

Страница 5: ...WERED ENERGISERS Model BT12 Solar BT20 BT50 BT80 Energiser 8 5kV peak no load output voltage Pulse period 1 3 seconds normal 1 7 seconds low battery Stored Energy 1 Joule 2J 5J 8J Power 12V or 24V abs...

Страница 6: ...featuring digital display a reading of Lo b this means low battery voltage Early models will switch themselves off to conserve the battery on re applying the correct voltage the energiser will start...

Страница 7: ...system For detailed information on earthing see the Daken Electric Fencing Manual IMPORTANT NOTE Always ensure adequate ventilation is given to the enclosure if it houses a battery Lead Acid batterie...

Страница 8: ...r e t e m t l o v e h t h t i W r o t a l u g e r e h t m o r f s e r i w l e n a p e h t t c e n n o c s i D l e n a p r a l o s e h t k c e h c o T 1 range check that the panel is delivering approx...

Страница 9: ...s or 3kV Should this point be reached you will need to trouble shoot your fence to determine the presence of short circuits or high load from weed growth See Fault nding the fence on page 7 for assist...

Страница 10: ...persons shall be avoided 3 An electric fence shall not be supplied from two different energisers or from independent fence circuits of the same energiser For any two different electric fences each su...

Страница 11: ...fence wires shall not cross above overhead power or communication lines 11 Crossings with overhead power lines shall be avoided wherever possible If such a crossing cannot be avoided it shall be made...

Страница 12: ...t connected to the electric animal fence circuit provides isolation between the fence circuit and the supply mains equivalent to that provided by the energiser PROHIBITED MOUNTING Electric fence condu...

Отзывы: