Page 6 of 48
SK2019 EU FDHD-V/P-AC-001
General Specifications
A.2.1.
2-pipe Systems
Product range:
FDHD High Static Hydronic Ducted Fan Coil
FDHD-V~ Hydronic Ducted 2-pipe Unit with AC motor
FDHD-[Size]-V~
18R
24B
30R
36B
48
60B
75
100
Unit
Configuration
Configuration
2-pipe
Number Of Fan Blowers
Signal
Twin
Power Supply (V/Ph/Hz)
230 / 1 / 50
220 / 1 / 60
Operation Control
~S: Complete function onboard PCB with integrated group control functionality.
~T: Terminal strip only.
Per
fo
rma
n
ce
D
ata
Ai
r
Air Flow
H
m
3
/hr
1020
1500
1900
2150
2880
3180
3500
4361
M
920
1360
1700
1950
2680
2880
3100
4050
L
770
1200
1450
1700
2270
2400
2600
3688
Available pressure
H
Pa
60
60
60
60
58
60
62
72
M
50
50
50
50
50
50
50
50
L
35
35
35
35
35
35
35
42
C
o
o
ling
Cooling Capacity
e
H
kW
4.26
6.86
8.15
11.24
13.4
17.18
18.19
22.34
M
3.99
6.38
7.53
10.4
12.7
15.98
16.6
21.2
L
3.48
5.8
6.68
9.43
11.2
13.74
14.52
19.73
Sensible Cooling
Capacity
e
H
3.37
5.19
6.25
8.32
9.8
12.7
13.8
16.99
M
3.11
4.8
5.73
7.69
9.26
11.7
12.5
16.06
L
2.7
4.35
5.05
6.87
8.12
10.1
10.8
14.83
Latent Cooling
Capacity
H
0.89
1.67
1.9
2.92
3.6
4.48
4.39
5.35
M
0.88
1.58
1.8
2.71
3.44
4.28
4.1
5.14
L
0.78
1.45
1.63
2.56
3.08
3.64
3.72
4.9
FCEER
e
Rating
17
25.2
27.1
24.7
23.5
30.6
27.7
25.4
Class
E
D
D
E
E
D
D
D
H
ea
ti
ng
Heating Capacity
e
H
kW
4.87
7.28
8.72
11.2
16.2
16.84
18.53
22.99
M
4.51
6.72
8
10.25
15.3
15.62
16.97
21.85
L
3.92
6.16
7.12
9.24
13.4
13.63
14.66
20.22
FCCOP
e
Rating
18.2
26.6
28.8
24.7
25.2
30.2
28.4
26.3
Class
E
D
D
E
D
D
D
D
So
u
nd
Sound Pressure Level (Outlet)
d(BA)
56/53/51
53/50/45
57/53/47
60/57/54
64/60/56
64/61/57
65/59/54
66/63/60
Sound Pressure Level
(Inlet + Radiated)
56/53/51
53/50/45
57/53/47
60/57/54
64/60/56
64/61/57
65/59/54
66/63/60
Sound Power Level (Outlet)
e
65/62/60
64/62/58
67/64/61
72/70/67
73/69/63
69/67/64
71/68/65
75/72/69
Sound Power Level
(Inlet + Radiated)
65/62/60
64/62/59
67/64/61
72/70/67
73/68/66
72/70/67
74/71/68
75/72/69
El
e
ctr
ic
al
Fan Motor Power
H
W
300
308
380
476
570
625
813
988
M
232
261
310
418
450
520
600
885
L
203
222
260
389
395
464
483
745
Fan Motor Running Current @ H
A
1.12
1.35
1.5
2.05
2.61
2.66
3.84
4.3
Fan Motor Starting Current @ H
3.35
4.04
4.51
6.14
7.84
7.97
11.53
12.89
H
ydr
aul
ic
Cooling Water Flow
Rate
H
L/h
735
1160
1400
1910
2175
2922
3022
3830
M
672
1093
1292
1749
2064
2694
2848
3634
L
581
990
1135
1542
1820
2354
2470
3381
Cooling Pressure Drop
e
H
kPa
13.3
13.8
18.9
43.1
43.8
36.3
12.9
22.6
M
11.7
12.1
16.3
37.7
34.8
31.7
10.9
20.67
L
9.3
10.3
13.2
31.2
27.9
24.6
8.6
18.28
Heating Water Flow
Rate
H
L/h
788
1227
1478
1917
2350
2887
3075
3942
M
722
1151
1365
1758
2225
2659
2909
3746
L
624
1041
1206
1546
1957
2317
2513
3466
Heating Pressure
Drop
e
H
kPa
14.6
13.6
18.8
38.6
41
31.7
11.9
15.91
M
12.7
11.8
16.1
33.2
32.6
27.6
10.1
14.59
L
10
10.2
13.1
27.3
26.2
21.9
7.9
12.78
Water Content
L
1.1
1.92
1.92
2.56
3.37
4.49
5.14
6.34
Construction
and Packing
Data
Water Connections
Type
Threaded Male
In
in
3/4
1
Out
Condensate Drainage Connection
3/4
Dimensions
L
mm
710
1110
1110
1110
1460
1460
1460
1760
W
630
630
630
630
650
650
750
750
H
300
300
300
300
380
380
430
430
Net Weight
kg
33
45
46
50
56
60
65
75
"e": Above specifications are based on declared Eurovent test data for the year of publication of this document. To confirm the most updated specifications,
please visit
www.eurovent-certification.com
Eurovent testing conditions:
a. Cooling mode:
b. Heating mode:
- Return air temperature: 27C DB/ 19C WB.
- Return air temperature: 20C.
- Inlet/ outlet water temperature: 7C/ 12C.