background image

Daintree® Wireless Controls

Wireless Scene Switch(WWD2-4SM)

Installation Guide

5

Product Operation

 

 

 

 

Button Functionality

LED Indicator

Rapid flash (12 times per second)
for up to 30 seconds

Solid ON for 10 seconds

Flashes once (100ms duration)

Flashes ON 2 seconds every
30 seconds

Device is trying to join a ZigBee network

Device successfully joined a ZigBee network

Device has been activated while in the network

Batteries need to be replaced

Device has entered dual zone personality mode

Device has entered four scene personality mode

Flashes twice (100ms duration)

Flashes four times (100ms duration)

Forth Button

            Short press

            Double short press

            Hold

First Button

          

Short press

            Double short press

            Hold

Second Button

         

 Short press

            Double short press

            Hold

Third Button

         

 Short press

            Double short press

            Hold

Dual Zone Personality

Four Scene Personality

Zone 1 lights ON at previous level
Zone 1 lights ON at 100% output
Turn Zone 1 ON and dim up

Zone 2 lights ON at previous level
Zone 2 lights ON at 100% output
Turn Zone 2 ON and dim up

Zone 1 lights OFF
Zone 1 lights ON at minimum dimming level
Turn Zone 1 ON and dim down or dim down 
if lights are already ON

Zone 2 lights OFF
Zone 2 lights ON at minimum dimming level
Turn Zone 2 ON and dim down or dim down 
if lights are already ON

SCENE 1 turns ON

SCENE 2 turns ON

SCENE 3 turns ON

SCENE 4 turns ON

Содержание WWD2-4SM

Страница 1: ...one dimming control or allow the user to select from four configured scenes The buttons on the WWD2 4SM can be changed to clearly indicate the operation mode of the device The communication with the Daintree system utilizes a secure and reliable wireless connection which helps minimize installation costs and complexity DT044 Prepare Electrical Wiring Electrical Requirements When replacing a line v...

Страница 2: ... the plastic insulation strip out of the battery compartment Install the faceplate onto the device Note Device supports the use of other standard faceplates on the market If you want to install on the junction box use the screw in the package and a cross screwdriver to lock the device on the junction box If you want to install the device on the wall use the 3M tape in the package to stick the devi...

Страница 3: ...to remove the button module from the device Press the replacement button module with the desired printing onto the device 3 Please contact if you would like to purchase customized buttons Hold the reset button and 2nd button for 5 seconds to change the personality to dual zone mode Hold the reset button and 4th button for 5 seconds to change the personality to scene mode ...

Страница 4: ...6 50 The device s LED flashing on for 2 seconds every 30 seconds indicates that the batteries need to be replaced Use a standard screwdriver to open the faceplate Install the faceplate onto the device Separate the battery cover from the device Replace the batteries with AAA batteries All batteries need to be replaced at the same time 15 00 15 30 ...

Страница 5: ...four times 100ms duration Forth Button Short press Double short press Hold First Button Short press Double short press Hold Second Button Short press Double short press Hold Third Button Short press Double short press Hold Dual Zone Personality Four Scene Personality Zone 1 lights ON at previous level Zone 1 lights ON at 100 output Turn Zone 1 ON and dim up Zone 2 lights ON at previous level Zone ...

Страница 6: ...S ARE CORROSIVE WHEN HANDLING LEAKING BATTERIES PROPER PERSONAL SAFETY EQUIPMENT SHOULD BE USED INCLUDING RUBBER GLOVES AND EYE PROTECTION If it is discovered that the batteries have leaked wearing rubber gloves and using eye protection remove all of the batteries from the battery compartment and seal them in a plastic bag The bag should be discarded in a manner in accordance with local laws and r...

Страница 7: ...roduire de brouillage 2 L appareil doit accepter tout brouillage radioélectrique subi même si le brouillage est susceptible d en compromettre le fonctionnement FCC RF Radiation Exposure Statement Specific Absorption Rate SAR is a measure of the rate of RF radiofrequency energy absorption by the body from the source being measured This equipment has been subject to the FCC RF Exposure SAR Evaluatio...

Отзывы: