manualshive.com logo in svg
background image

Installation Guide

Daintree

®

 Wireless 

High Bay Sensor 

(WHS100)

This equipment has been tested and found to comply with the  

limits for a Class B digital device, pursuant to Part 15 of the FCC 

Rules. These limits are designed to provide reasonable protection 

against harmful interference in a residential installation. This  

equipment generates, uses and radiates radio frequency energy 

and, if not installed and used in accordance with the instructions,  

may cause harmful interference to radio communications.  

However, there is no guarantee that interference will not occur  

in a particular installation. If this equipment does cause harmful 

interference to radio or television reception, which can be  

determined by turning the equipment off and on, the user is  

encourage to try to correct the interference by one

or more of the following measures:

•  

Reorient or relocate the receiving antenna;

•  

Increase the separation between the equipment and receiver;

•  

Connect the equipment into an outlet on a circuit different  

  from that to which the receiver is connected;

•  

Consult the dealer or an experienced radio/TV technician  

  for help.

Product complies with Part 15 of the FCC Rules. Operation is

subject to the following two conditions: (1) This device may not

cause harmful interference, and (2) This device must accept any 

interference received, including interference that may cause 

undesired operation.

This Class B digital apparatus complies with Canadian ICES-003.

Cet appareil numérique de la classe B est conforme à la

norme NMB-003 du Canada.

These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation, operation 

or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be 

referred to GE Current, a Daintree company.

Questions: 

Web:

 products.gecurrent.com

Phone: 

1-866-855-8629

www.gecurrent.com

© 2021 Current Lighting Solutions, LLC. All rights reserved. GE and the GE monogram are trademarks of the  

General Electric Company and are used under license. Information provided is subject to change without notice.  

All values are design or typical values when measured under laboratory conditions. 
DT109 (Rev. 03/29/2021

Input Power

  

120-277 VAC 50/60Hz

Load Rating 

 

5A @ 120-277VAC

Load Types 

 

General Use, Electronic Ballast

Ballast/Driver 

 

Control: On/Off, 0-10V Dimming

Dimming Output 

 

0-10V; 15mA (max sink)

Indicators 

 

Green LED (motion detection)  

   

Red LED (off for normal operation)

Motion Sensor 

 

PIR technology

Power Measurement 

 

2% accuracy (0.04~5A range)

Power Consumption 

 

0.32W @120VAC, 0.58W @277VAC

Dimensions (w/out 

 

3.54” L x 3.54” W x 1.78” H

mounting)

  

(90mm L x 90mm W x 45.4mm H)

Radio Properties 

 

2.4 GHz, +8dBm transmit power

Technology 

 

Wireless: ZigBee PRO (HA, BA)

Lenses Included 

 

360° lenses (8ft, 20ft, 40ft), Aisle    

   

Mask

Off-Delay Timer 

 

Configurable in CSM

Operating Environment

   -40°F to +158°F (-40°C to +70°C)    

   

5-95% RH, non-condensing,  

  

Indoor/Outdoor

Enclosure 

 

Watertight; IP66 rated*

Mounting 

 

Standard ½” knockout mount

Compliance 

 

FCC Part 15, FCC ID: Z6G-DT357 CAN

  

ICES-3 (B)/NMB-3(B), IC: 10478A-   

   

DT357 UL Listed

Specifications 

FCC Warning Message

Industry Canada (IC) Warning Message

CAUTION

RISK OF EXPOSURE IF BATTERY IS REPLACED BY AN 

INCORRECT TYPE. DISPOSAL OF USED BATTERIES ACCORDING 

TO THE INSTRUCTIONS

WHS100

18

19

Содержание GE current WHS100

Страница 1: ...he sensor is mounted See IEEE Address Labels 3 Remove the tightening ring from the threaded nipple 4 Insert the sensor wires and threaded nipple through the knockout on the fixture 5 Thread the sensor...

Страница 2: ...the coverage area It may not detect a human body if it is blocked by the fixture housing furniture plants glass curtains etc Secure to a stable fixture to minimize sensor vibration 3 Mounting The dime...

Страница 3: ...ss of Regular power to the WHS100 disables dimming control causing the emergency fixture to operate at maximum output The Emergency Fixture is powered by Emergency power Loss of Regular power to the W...

Страница 4: ...ft Coverage radius 30 ft Use the mask to avoid occupancy triggers from activity outside the desired coverage area Insert the mask between the inside of the lens and the inner layer of the gasket not o...

Страница 5: ...uide Daintree Wireless High Bay Sensor WHS100 5 9 Coverage Patterns 8 foot lens LOW 20 foot radius 40 foot diameter 40 foot lens HIGH 30 foot radius 60 foot diameter 20 foot lens MED 30 foot radius 60...

Страница 6: ...from the mains voltage lines Reduce the area created by the signal lines and the GND return i e keep them close together If possible twist the signal line with the GND return 14 IEEE Address Labels A...

Страница 7: ...ircuit While Regular power is supplied to the LVS model RRU X UM the WHS100 provides switched On Off power to the fixture and controls dimming When the RRU X UM senses loss of Regular power the RRU X...

Страница 8: ...visory Control for Dimming ELV Fixtures WHS100 wiring to EcoSense Linear Dimming Control Module This advisory shows the wiring connections between the EcoSense LDCM PL and the WHS100 to provide dimmin...

Страница 9: ...in equipment nor to provide for every possible contingency to be met in connection with installation operation or maintenance Should further information be desired or should particular problems arise...

Отзывы: