Installation Guide

Daintree

®

 Wireless 

High Bay Sensor 

(WHS100)

6

10

13

Joining the ZigBee Lighting Control Network

11

Default Functionality

12

PIR Sensitivity Adjustment

Redusing noise on low voltage 

(0-10V) wiring

After successfully completing the Installation Test the WHS100 is 

ready to communicate with the Daintree Wireless Area Controller 

(WAC) and the Daintree Controls Software (DCS) web-based 

building controls management user interface.
A network join can be retriggered manually at any time by 

resetting the WHS100:
•  Reset to factory defaults: Press and hold the Utility button for 

  5 seconds. Release the button when the LEDs begin to flash    

  rapidly. This causes the device to leave any network to which it  

  is currently joined. Following the reset, the device attempts to   

  join a network. For more information about configuring 

  the lighting control network, see the instructions and on-line    

  help provided with the Daintree Controls Software application.
For more information about configuring the lighting control 

network, see the instructions and on-line help provided with 

the Daintree Controls Software web application.

The 

WHS100

 is designed to be part of the Daintree Networked.

 It should not be left to operate outside of the network indefinitely. 

The Daintree Controls Software web application provides many 

control efficiencies not otherwise available, including changing 

operational parameters. 

As shipped from the factory, before it is joined to the DCS network, 

and after it joins the network but before it is configured into a zone, 

the WHS100 controls the connected light as follows:
•  During occupancy light is ON at 100%

•  During vacancy an on/off light turns OFF, a dimming

  light is reduced to 10%.

•  Vacancy delay (Off Delay) is 10 minutes.

Functionality after Configured into a Zone

After the WHS100 is configured into a zone, it follows the control 

strategy for the zone, including delay time, light levels, and other 

features. The delay time is whatever the strategy dictates plus 20 

seconds. For example, if the strategy is set for 8 minutes, the 

vacancy delay is 8 minutes and 20 seconds.

There are no senstivity adjustments on the WHS100. 

Contact Daintree support for information on how to change 

the sensor sensitivity.

• Keep wiring as short as practical.
• Keep the signal lines separate from the mains voltage lines.
• Reduce the area created by the signal lines and the

  GND return (i.e., keep them close together).
• If possible twist the signal line with the GND return.

14

IEEE Address Labels

A small plastic bag containing two small labels and the lens mask 

is included with every sensor. The larger label with the WHS100’s 

full IEEE address is the Fixture label. Affix this label to the outside 

of the fixture or sensor in a standard location where it can be seen 

after installation and mounting.

Record IEEE Addresses

A marked-up copy of the facility floor plan showing the identity

 and location of each wireless adapter (including associated fixtures 

and sensors) should be available after installation. This will 

simplify and expedite the commissioning process.
Be sure that each sensor’s IEEE address (last 5 digits) is 

recorded on the facility floor plan. Use the Plan label supplied 

with the adapter or write the last 5 digits on the floor plan. This 

information will be used during thecommissioning process.

For factory installation by fixture manufacturers:

• Remove the

 Fixture

 label from its plastic bag, and affix to the 

  outside of the fixture or sensor in a consistent location where it 

  can be seen after installation and mounting.

• Leave the 

Plan

 label (smaller label) in its plastic bag. Tape the bag 

  to the Fixture label or next to it .

15

Troubleshooting

No LEDs turn on when I press the Utility button.

• Check line voltage wiring Light doesn’t operate as expected  

  in Installation Test Mode. 

• Make sure power is turned on to the fixture circuit .

• Check all wiring between the fixture and the sensor.

• Press the blue Utility button for 5 seconds to reset the unit.

Green motion detection LED does not activate when

walking through the coverage area.

• Check to see if the green LED turns on when you wave your 

  hand directly in front of the lens.

• If the LED turns on, check for objects or barriers obstructing 

  the sensor’s view of the coverage area.

Green LED flashes when the coverage area is vacant.

•  Check for sources of hot air flow in the coverage area.

•   See 

Placement Guidelines.

 Eliminate false trigger sources.

Light doesn’t turn Off after WHS100 joins the ZigBee network.

• Once the WHS100 is configured into a zone through DCS it 

  follows the Off Delay for the zone’s control strategy.

Light doesn’t turn Off after WHS100 is configured into a zone.

• Check the “Off delay” for the zone in the DCS.

• Check for other DCS scheduled events or manual

  overrides that may be keeping the lights On.

Содержание GE current WHS100

Страница 1: ...he sensor is mounted See IEEE Address Labels 3 Remove the tightening ring from the threaded nipple 4 Insert the sensor wires and threaded nipple through the knockout on the fixture 5 Thread the sensor...

Страница 2: ...the coverage area It may not detect a human body if it is blocked by the fixture housing furniture plants glass curtains etc Secure to a stable fixture to minimize sensor vibration 3 Mounting The dime...

Страница 3: ...ss of Regular power to the WHS100 disables dimming control causing the emergency fixture to operate at maximum output The Emergency Fixture is powered by Emergency power Loss of Regular power to the W...

Страница 4: ...ft Coverage radius 30 ft Use the mask to avoid occupancy triggers from activity outside the desired coverage area Insert the mask between the inside of the lens and the inner layer of the gasket not o...

Страница 5: ...uide Daintree Wireless High Bay Sensor WHS100 5 9 Coverage Patterns 8 foot lens LOW 20 foot radius 40 foot diameter 40 foot lens HIGH 30 foot radius 60 foot diameter 20 foot lens MED 30 foot radius 60...

Страница 6: ...from the mains voltage lines Reduce the area created by the signal lines and the GND return i e keep them close together If possible twist the signal line with the GND return 14 IEEE Address Labels A...

Страница 7: ...ircuit While Regular power is supplied to the LVS model RRU X UM the WHS100 provides switched On Off power to the fixture and controls dimming When the RRU X UM senses loss of Regular power the RRU X...

Страница 8: ...visory Control for Dimming ELV Fixtures WHS100 wiring to EcoSense Linear Dimming Control Module This advisory shows the wiring connections between the EcoSense LDCM PL and the WHS100 to provide dimmin...

Страница 9: ...in equipment nor to provide for every possible contingency to be met in connection with installation operation or maintenance Should further information be desired or should particular problems arise...

Отзывы: