Proline® LEX Series Exit Sign 

Installation Guide

Maintenance

CAUTION: Always turn off AC power to the equipment before servicing. Servicing should be performed  

only by a qualified service technician. Use only MANUFACTURER supplied replacement parts.

BATTERY

The battery supplied with the EM model requires no maintenance. However, it should be tested periodically  

and replaced when it no longer operates the connected sign for the duration of a 30 second or 90 minute test.  

The battery supplies in this sign has a life expectancy of 5years when used in a normal ambient temperature  

of 72°F. 
NFPA 101 (Life Safety Code) requires that all emergency lighting equipment be functionally tested every 30 days  

for a minimum of 30 seconds and tested annually for a full 90 minute duration. Written records of the testing  

are to be kept for examination by the authority having jurisdiction. 