background image

www.gecurrent.com

© 2021 Current Lighting Solutions, LLC. All rights reserved. GE and the GE monogram are trademarks of the 

General Electric Company and are used under license. Information provided is subject to change without 

notice. All values are design or typical values when measured under laboratory conditions. 
CTRL044 (Rev 05/18/21)

Installation Guide

LightGrid Node 2.x Series 

Questions

• Email: [email protected]

• Leave a Voicemail: 1-877-843-5590

Troubleshooting

Symptom

Solution

The luminaire is not 

turning ON.

Check that the pole has power. The relay inside the Controller is Normally Closed, so the 

luminaire will always turn ON when the controller is first plugged in.

I did not see the 

dimming sequence in the 

first 60 seconds. 

Unplug the controller, and try plugging it in again. If you still do not see the sequence, check 

that the dimming wires of the fixture (Grey & Violet) are properly connected to the dimming 

wires of the ANSI socket. If you confirm the wiring is connected and the controller still does 

not dim the luminaire, try another new controller.

Отзывы: