Installation Guide
9
Wired Dimming Connections (Optional)
Junction Box Cover Removal
• Using a #1 Phillips screwdriver, unscrew the 6
screws on the junction box cover.
• Remove the junction box cover from the junction
box enclosure.
NOTE: Be sure to hold on to the screws, junction box
cover, and gasket for future use.
Wall Dimming Wire Insertion
• Remove the sealed gland in the bottom of the
junction box enclosure, and install an appropriate
Listed ½” NPT fitting rated for the environment into
the open threaded open conduit connection.
• Bring the conductors for the building dimming
network into this fitting.
NOTE: Customer is responsible for the 1/2'' NPT- 14
thread per inch fitting.
Wire Dimming Electrical Connection
Connect the appropriate wiring to Dim + (0-10V) and
Dim - (0-10V) from driver. Insulate the black, pink &
blue wires. Follow dimming switch instructions for rest
of connection.
Junction Box Cover Replacement
• Ensure gasket is sitting in place on the inner edge of
the junction box cover.
• Fasten all 6 screws to ensure water tight seal.
NOTE: Be careful not to strip out the junction box
enclosure by over tightening the screws.
Driver
Dimming
Switch
Violet
Blue
Pink
Black
Gray
+ (0-10V)
- (0-10V)
Gasket in cover
1
3
2
4
Remove cover
Dimming In
To lightbar
AC input
Remove screws
WARNING / AVERTISSEMENT
RISK OF ELECTRIC SHOCK
• Turn power off before installation, inspection, cleaning or removal.
And follow appropriate lock out/tag out safety procedure.
• This product must be installed in accordance with the applicable
installation code by a person familiar with the construction and
operation of the product and the hazards involved.
RISQUE DE CHOC ELECTRIQUE
• Coupez l’alimentation avant l’inspection, l’installation ou la
désinstallation.
• Ce produit doit être installé selon le code d’installation pertinent, par
une personne qui connaît bien le produit et son fonctionnement ainsi
que les risques inhérents.