Introduction and Installation
www.DaikinApplied.com
5
IOM 1322-1 • WATER-COOLED SCROLL COMPRESSOR
This manual provides installation, operation, and maintenance information for Daikin scroll chillers with the MicroTech
®
controller.
NOTE:
Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and
regulations, and experienced with this type of equipment.
DANGER
LOCKOUT/TAGOUT
all power sources prior to starting, pressurizing, de-pressuring, or powering down the Chiller. Failure to follow this warning exactly
can result in serious injury or death. Disconnect electrical power before servicing the equipment. More than one disconnect may be required to de-energize the
unit. Be sure to read and understand the installation, operation, and service instructions within this manual.
WARNING
Electric shock hazard. Improper handling of this equipment can cause personal injury or equipment damage. This equipment must be properly grounded.
Connections to and service of the MicroTech
®
control panel must be performed only by personnel that are knowledgeable in the operation of the equipment
being controlled. Disconnect electrical power before servicing the equipment.
CAUTION
Static sensitive components. A static discharge while handling electronic circuit boards can cause damage to the components. Discharge any static electrical
charge by touching the bare metal inside the control panel before performing any service work. Never unplug any cables, circuit board terminal blocks, or power
plugs while power is applied to the panel.
CAUTION
When moving refrigerant to/from the chiller from an auxiliary tank, a grounding strap must be used. An electrical charge builds when halo-carbon refrigerant
travels in a rubber hose. A grounding strap must be used between the auxiliary refrigerant tank and the chiller’s end sheet (earth ground), which will safely take
the charge to the ground. Damage to sensitive electronic components could occur if this procedure is not followed.
WARNING
This equipment generates, uses, and can radiate radio frequency energy. If not installed and used in accordance with this instruction manual, it may cause
interference with radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the owner will be
required to correct the interference at the owner’s own expense.
Daikin Applied disclaims any liability resulting from any interference or for the correction thereof.
WARNING
Polyolester Oil, commonly known as POE oil is a synthetic oil used in many refrigeration systems, and may be present in this Daikin product. POE oil, if ever
in contact with PVC/CPVC, will coat the inside wall of PVC/CPVC pipe causing environmental stress fractures. Although there is no PVC/CPVC piping in this
product, please keep this in mind when selecting piping materials for your application, as system failure and property damage could result. Refer to the pipe
manufacturer’s recommendations to determine suitable applications of the pipe.
HAZARD IDENTIFICATION INFORMATION
DANGER
Danger indicates a hazardous situation which will result in death or serious injury if not avoided.
WARNING
Warning indicates a potentially hazardous situations which can result in property damage, personal injury, or death if not avoided.
CAUTION
Caution indicates a potentially hazardous situations which can result in minor injury or equipment damage if not avoided.
NOTE:
Indicates important details or clarifying statements for information presented.
Introduction and Installation
Содержание WGZ030DW
Страница 4: ......
Страница 57: ...Unit Controller Operation www DaikinApplied com 57 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Страница 71: ...Unit Maintenance www DaikinApplied com 71 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Страница 72: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 72 www DaikinApplied com Troubleshooting Chart Troubleshooting Chart...
Страница 74: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 74 www DaikinApplied com Troubleshooting Chart...
Страница 75: ...Troubleshooting Chart www DaikinApplied com 75 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Страница 76: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 76 www DaikinApplied com Troubleshooting Chart...
Страница 77: ...Troubleshooting Chart www DaikinApplied com 77 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Страница 78: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 78 www DaikinApplied com Troubleshooting Chart...