Dimensions and Weights - Packaged Units
www.DaikinApplied.com 21
IOM 1322-1 • WATER-COOLED SCROLL COMPRESSOR
Figure 16: Lifting Locations, WGZ150-200D Packaged
Table 7: Lifting Weights, WGZ150-200D Packaged
NOTE:
Refer to
for details on transferring/lifting the unit. Do not lift unit by mounting holes in
feet.
Isolator Information
It is recommended that isolators be used on all upper level
installations or in areas where vibration transmission is a
consideration. Transfer the unit as indicated under
“ In all cases, set the unit in place and level. When spring-
type isolators are required, install springs running under the
main unit supports.
The unit should be set initially on shims or blocks at the listed
spring free height. When all piping, wiring, flushing, charging,
etc., is completed, the springs are adjusted upward to loosen
the blocks or shims that are then removed.
A rubber anti-skid pad should be used under isolators if
holddown bolts are not used.
Installation of spring isolators requires flexible piping
connections and at least three feet of flexible electrical conduit
to avoid straining piping and transmitting vibration and noise.
Refer to unit dimension drawing for mounting locations.
Figure 17: Isolator Locations
Table 8: WGZ-DW Isolator Kit Part Numbers
Model Number
030-060
070-080
90
100-130
150-200
Spring-Flex
332320501
332320502
332320503
332320504
332320505
R -I-S
332325501
332325502
332325502
332325503
332325503
Содержание WGZ030DW
Страница 4: ......
Страница 57: ...Unit Controller Operation www DaikinApplied com 57 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Страница 71: ...Unit Maintenance www DaikinApplied com 71 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Страница 72: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 72 www DaikinApplied com Troubleshooting Chart Troubleshooting Chart...
Страница 74: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 74 www DaikinApplied com Troubleshooting Chart...
Страница 75: ...Troubleshooting Chart www DaikinApplied com 75 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Страница 76: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 76 www DaikinApplied com Troubleshooting Chart...
Страница 77: ...Troubleshooting Chart www DaikinApplied com 77 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Страница 78: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 78 www DaikinApplied com Troubleshooting Chart...