OMM 1130
-
2
73
Table continued
Type
Index
I/O
Description
LONworks
BACnet
Modbus
I
11
O
Active alarms 11
x
x
x
I
12
O
Active alarms 12
x
x
x
I
13
O
Active alarms 13
x
x
x
I
14
O
Active alarms 14
x
x
x
I
15
O
Active alarms 15
x
x
x
I
16
O
Active alarms 16
x
x
x
I
17
I
Network chiller mode set point
x
x
x
I
18
O
LON Chiller run mode
x
x
I
19
O
Active chiller mode
x
x
x
I
20
I
Network demand limit default set point
x
I
21
I
Network chiller mode default set point
x
I
22
O
Sequence Status
Bit 1 – Unit Full Load Flag
Bit 2 – Circuit One Available Flag
Bit 3 – Circuit Two Available Flag
x
x
x
I
28
O
Unit model type, refrigerant
x
x
x
I
29
O
Unit language
x
x
x
I
30
O
Unit software version
x
x
x
I
32
I
Compressor select
x
x
x
I
35
I/O
Clock year
x
x
I
36
I/O
Clock month
x
x
I
37
I/O
Clock day of month
x
x
I
38
I/O
Clock day of week
x
x
I
39
I/O
Clock hours
x
x
I
40
I/O
Clock minutes
x
x
I
45
O
Compressor starts
x
x
I
46
O
Compressor run hours
x
x
D
1
I/O
Network chiller enable set point
x
x
x
D
2
O
Chiller enable status
x
x
x
D
3
O
Active alarm indicator
x
x
x
D
4
O
Chiller run enabled
x
x
x
D
5
O
Chiller local control
x
x
x
D
6
O
Chiller capacity limited
x
x
x
D
7
O
Evap flow
x
x
x
D
8
O
Cond flow
x
x
x
D
9
I
Network chiller enable default set point
x
D
10
I
Ignore network defaults
x
D
24
I
Network clear alarm signal
x
x
x
Parameter Details
Units of Measure
Parameters will be expressed in different units dependant on the protocol selected.
Parameter
Type
Modbus
Units
BACnet
Units
LONworksU
nits
Temperature
o
F X 10
o
F X 10
o
C X 100
Pressure
PSI X 10
PSI X 10
KPa X 10
Percentage
% X 10
% X 10
% X 200