This menu gives the status of digital inputs (D.I.), 1=ON, 0=OFF. Numbers are 1 through 18. See Table
5 on page 19 for number reference.
VIEW UNIT STATUS (6)
Analog Output
(volts x 100)
1 = 000.0 2 =
000.0
VIEW UNIT STATUS (7)
Analog Output
(volts x 100)
3 = 000.0 4 =
000.0
VIEW UNIT STATUS (8)
EXB1 Online
D.O. 1 2 3 4
0 0 0 0
View Unit Tempertures
Water Cooled = Y
TG Z i n Cool Mo de
Water Cooled = N
VIEW UNIT TEMP (1)
VIEW UNIT TEMP (1)
Evap LWT = XX.X
°
F
Evap LWT = XX.X
°
F
Cond EWT = XXX.X
°
F
OAT = XXX.X
°
F
LWT Target = XX.X
°
F
LWT Target = XX.X
°
F
TGZ Unit in Heat Mode (R134a)
VIEW UNIT TEMP (1)
Evap LWT = XX.X
°
F
Cond EWT = XXX.X
°
F
LWT Target = XX.X
°
F
The difference between the three screens above is that water-cooled units and the TGZ units will give the
entering condenser water temperature and air-cooled units will give the outside air temperature (OAT).
The outside-air temperature sensor is furnished with the unit, inside the control panel, wired to the correct
terminals. It must be installed outdoors in a location that will give the true outdoor temperature that the
condenser coils will see. Splicing of the sensor lead may be required. The unit will not operate without
the sensor installed.
WGZ unit
TGZ Unit (R134a)
VIEW UNIT TEMP (2)
VIEW UNIT TEMP (2)
LWT Pulldn= XX.X
°
F
LWT Pulldn= XX.X
°
F
Control Band= XX.X
°
F
Control Band= XX.X
°
F