background image

English

6

4.

Remove the knock hole on the bottom frame and route 
the piping under the bottom frame.

5.

Gas side shutoff valve

6.

Liquid side shutoff valve

7.

Refrigerant charge port

8.

Brazing

9.

Liquid side accessory pipe (1)

10.

Gas side accessory pipe (1)

11.

Gas side accessory pipe (2)

12.

Liquid side accessory pipe (2)

13.

Knockout hole

14.

Punch the knock hole

15.

Gas side piping (field supply)

16.

Liquid side piping (field supply)

Processing the Gas side accessory pipe (2)

Only in case of connecting at lateral side, cut the Gas side acces-
sory pipe (2) referring the figure below.

(mm)

<In case of multi system: RQYQ18~48PY1B>

(Refer to figure 15)

1.

If connected to the front

2.

When connected at lateral side (bottom)

3.

Remove the shutoff valve cover to connect.

4.

Remove the knock hole on the bottom frame and route 
the piping under the bottom frame.

5.

Gas side shutoff valve

6.

Liquid side shutoff valve

7.

Refrigerant charge port

8.

Brazing

9.

Liquid side accessory pipe (1)

10.

Gas side accessory pipe (1)

11.

Gas side accessory pipe (2)

12.

Liquid side accessory pipe (2)

13.

Knockout hole

14.

Punch the knock hole.

Note

<Connecting Refrigerant Piping>

When connecting the piping on site, be sure to use the accessory 
piping.

Make sure the onsite piping does not come into contact with other 
piping or the bottom frame or side panels of the unit.

<Multi Systems>

The Outdoor unit multi connection piping kit (sold separately) is 
needed when connecting piping between outdoor units.
Refer to the installation manual that comes with the kit when 
doing this piping work.

4.

Precautions when connecting piping between outdoor units (In 
case of multi system)
The Outdoor unit multi connection piping kit (sold separately) is 
needed to connect piping between outdoor units in multi system. 
Only proceed with piping work after considering the limitations on 
installation listed here and in “5. Branching the refrigerant piping”, 
always referring to the kit’s installation manual.

(1)

The piping between outdoor units must be installed level 
(Pattern 1) or with a rise (Pattern 2). Otherwise oil may pool 
in the pipes.

(2)

To avoid the risk of oil detention in the stopping unit, always 
connect the shutoff valve and the piping between outdoor 
units as shown in the figure A or figure B.

Model

A

B

C

D

Q8 type

156

17

188

247

Q10 type

156

23

192

247

Q12 type

150

29

192

247

Q14 · 16 type

150

29

192

251

C

A

A

B

25

90

150

D

Cutting 
location

Gas side 
accessory 
pipe (2)

Gas side accessory pipe (2)

Gas side piping
(field supply)

Base

Pattern 1

Pattern 2

Prohibited pattern

Change to pattern 1 or pattern 2

to indoor unit

to indoor unit

to indoor unit

to indoor unit

to indoor unit

to indoor unit

Piping between outdoor units

Piping between outdoor units

Downward inclination

Downward inclination

Oil remains in piping

Front connections

Side (bottom) connections

Front connections

Side (bottom) connections

Front connections

Side (bottom) connections

Level

Rise

Downward inclination

A

B

A

B

Front connections

Side (bottom) connections

01_EN_3P226891-13Q.fm  Page 6  Thursday, December 2, 2010  10:15 AM

Содержание VRVIII-Q Series

Страница 1: ...B RQYQ18PY1B RQYQ20PY1B RQYQ22PY1B RQYQ24PY1B RQYQ26PY1B RQYQ28PY1B RQYQ30PY1B RQYQ32PY1B RQYQ34PY1B RQYQ36PY1B RQYQ38PY1B RQYQ40PY1B RQYQ42PY1B RQYQ44PY1B RQYQ46PY1B RQYQ48PY1B English Deutsch Fran a...

Страница 2: ...00_CV_3P226891 13Q fm Page 2 Thursday December 2 2010 1 08 PM...

Страница 3: ...200 300 Pattern 3 2 1 1500 3 1 4 2 5 2 mm 1000 1 0 0 0 1000 1 5 0 0 1500 1500 figure 2 2 4 5 1 8 9 10 3 6 7 11 figure 6 1 2 4 3 figure 7 1 2 3 100 100 100 2 3 100 100 100 1 2 6 3 3 4 5 figure 14 figur...

Страница 4: ...6 7 8 ABC A F1 F2 F1 F2 Q1 Q2 B C 3 1 1 ABC I P A1P TOIN DUNIT TOOUT DUNIT TOMULTIUNIT F1 F2 F1 F2 F1 F2 1 2 3 4 5 6 A F1 F2 F1 F2 Q1 Q2 Q1 Q2 B C ABC I P A1P A1P TOIN DUNIT TOOUT DUNIT TOMULTIUNIT T...

Страница 5: ...of Q14 16 type 1 13 2 3 4 14 5 6 7 8 9 11 10 12 15 1 2 3 4 5 6 7 8 9 10 13 13 15 16 17 14 11 12 1 6 5 4 2 3 1 2 3 4 5 figure 28 1 2 3 1 5 6 7 3 4 1 2 3 4 11 12 13 14 9 15 10 10 5 6 7 8 9 figure 31 fi...

Страница 6: ...r qualified personnel to carry out installation work Do not attempt to install the air conditioner yourself Improper installation may result in water leakage electric shocks or fire Install the air co...

Страница 7: ...imum refrigerant charge of a VRVIII system must be below 100kg this to be in accordance with CE requirement EN60335 2 40 standard This means that in case the total maximum refrigerant charge of the sy...

Страница 8: ...l 3 Clamps 4 Accessory pipes Note Do not throw away any of the accessories until installation is com plete 2 3 Option accessory To install the outdoor units the following optional parts are also requi...

Страница 9: ...to prevent snow from accumu lating on the fins 3 If condensate may drip on downstairs or walkway depending on the floor condition take a measure such as the installation of central drain pan kit sold...

Страница 10: ...gen permutation or nitrogen blow when brazing Refer to figure 10 Brazing without performing nitrogen permutation or nitrogen blow into the piping will create large quantities of oxidized film on the i...

Страница 11: ...ing piping between outdoor units Refer to the installation manual that comes with the kit when doing this piping work 4 Precautions when connecting piping between outdoor units In case of multi system...

Страница 12: ...18 1 Do not install vertically Refer to figure 18 2 Maintain a straight portion of 500 mm or more until the split of the joint without wrapping any onsite piping around this area Over 500 mm of straig...

Страница 13: ...r unit 1 8 a a u r s t i i b b a a s t r u b c d e f g h i i c d e f g h j k REFNET Header REFNET Header 1 2 3 4 5 6 1 2 3 4 5 6 7 H2 b r s u t c d e f g h 1 2 3 4 5 6 7 8 8 c d e f g h 1 2 3 4 5 6 7...

Страница 14: ...920 x 15 9 19 1 22 2 28 6 34 9 41 3 19 1 25 4 28 6 34 9 54 1 9 5 12 7 15 9 19 1 12 7 15 9 19 1 22 2 Total capacity of indoor units gas pipe liquid pipe standard size max size standard size max size u...

Страница 15: ...r ing and earth terminal 7 1 Power circuit safety device and cable requirements A power circuit see the following table must be provided for con nection of the unit This circuit must be protected with...

Страница 16: ...be finished simul taneously with the local refrigerant piping and wound with tape field supply as shown in figure 25 Refer to figure 25 1 Liquid pipe 2 Gas pipe 3 Transmission wiring 4 Insulation mat...

Страница 17: ...ve A C in figure 28 should be open or closed as shown in the table below Refer to figure 28 1 Gauge manifold 2 Nitrogen 3 Measuring device 4 R410A tank with siphon 5 Vacuum pump 6 Charge hose 7 Liquid...

Страница 18: ...of a nut See 7 4 Transmission Wiring Connection Procedure 2 Make sure there is no faulty power wiring or loosing of a nut See 7 5 Power Wiring Connection Procedure 3 Has the insulation of the main pow...

Страница 19: ...3 9 12 7 8 1 9 9 18 0 22 0 15 9 13 5 16 5 Hexagonal wrench 6 mm 22 5 27 5 19 1 27 0 33 0 Hexagonal wrench 8 mm 25 4 LED display h OFF i ON j Blinking Uncertain LED display H1P H2P H3P H4P H5P H6P H7P...

Страница 20: ...med in recovery or other service modes About re charging of refrigerant When sizes and length of field pipings are certain figure out the re charging amount of refrigerant by calculation method of ref...

Страница 21: ...Perform the refrigerant charging operation according to check operation and charge the remaining refrigerant of the additional charging amount For performing the refrigerant charging opera tion the pu...

Страница 22: ...cate to open the valve of the refrigerant tank as on the right in approx 6 min after the re start Operation for re charging of refrigerant 1 60 min Contamination prevention is opearted at the same tim...

Страница 23: ...t according to the list on the installation manual 1 11 Test operate again after the repair To check operate again press the RETURN button BS3 to turn the LED back to normal indications as procedure 1...

Страница 24: ...it are reversed Exchange two of the three phases L1 L2 L3 and connect with the correct phase U3 Check operation has been completed normally Perform the check operation again U1 U4 LC Power is not bein...

Страница 25: ...hecks After Test Run Perform the following checks after the test run is complete Record the contents of field setting Record them on the accessory REQUEST FOR THE INDI CATION label And attach the labe...

Страница 26: ...results of the calcu lations in steps 1 and 2 above If the result of the above calculation exceeds the maximum con centration level then make similar calculations for the second then third smallest ro...

Страница 27: ...3P226891 13Q EM10A040 1012 HT 00_CV_3P226891 13Q fm Page 6 Thursday December 2 2010 1 08 PM...

Отзывы: