16
|
Unit installation
Installer and user reference guide
40
FXMQ-A
VRV system air conditioner
4P701548-1 – 2022.07
16 Unit installation
In this chapter
16.1 Preparing the installation site
Choose an installation location with sufficient space to transport the unit in and
out of the site.
Do NOT install the unit in places often used as work place. In case of construction
works (e.g. grinding works) where a lot of dust is created, the unit MUST be
covered.
16.1.1 Installation site requirements of the indoor unit
INFORMATION
Also read the general installation site requirements. See the
INFORMATION
The sound pressure level is less than 70 dBA.
INFORMATION
Equipment meets the requirement for commercial and light-industrial location when
professionally installed and maintained.
NOTICE
If the equipment is installed closer than 30 m to a residential location, the
professional installer MUST evaluate the EMC situation before installation.
CAUTION
This equipment is NOT intended for use in residential locations and will NOT
guarantee to provide adequate protection to radio reception in such locations.
CAUTION
Appliance NOT accessible to the general public, install it in a secured area, protected
from easy access.
This unit, both indoor and outdoor, is suitable for installation in a commercial and
light industrial environment.