![Daikin VRV IV RXMLQ8T7Y1B Series Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/daikin/vrv-iv-rxmlq8t7y1b-series/vrv-iv-rxmlq8t7y1b-series_installation-and-operation-manual_4705120012.webp)
5 Installation
Installation and operation manual
12
RXYLQ10~14T7Y1B*
VRV IV system air conditioner
4P543426-1 – 2018.07
>120 mm
>500 mm
5.3.4
Multiple outdoor units: Knockout holes
Connection
Description
Front connection
Remove the front plate knockout holes to
connect.
Bottom connection
Remove the knockout holes on the bottom
frame and route the piping under the bottom.
5.3.5
To protect against contamination
Seal the piping and wiring intake holes using sealing material (field
supply), otherwise the capacity of the unit will drop and small
animals may enter the machine.
5.3.6
Using the stop valve and service port
To handle the stop valve
▪ Make sure to keep all stop valves open during operation.
▪ The stop valves are factory closed.
To open the stop valve
1
Remove the stop valve cover.
2
Insert a hexagon wrench into the stop valve and turn the stop
valve counterclockwise.
3
When the stop valve cannot be turned any further, stop turning.
4
Install the stop valve cover.
Result:
The valve is now open.
To fully open the Ø19.1 mm~Ø25.4 mm stop valve, turn the
hexagonal wrench until a torque between 27 and 33 N•m is
achieved.
Inadequate torque may cause leakage of refrigerant and breakage of
the stop valve cap.
NOTICE
Pay attention that mentioned torque range is applicable for
opening Ø19.1~Ø25.4 mm stop valves only.
To close the stop valve
1
Remove the stop valve cover.
2
Insert a hexagon wrench into the stop valve and turn the stop
valve clockwise.
3
When the stop valve cannot be turned any further, stop turning.
4
Install the stop valve cover.
Result:
The valve is now closed.
To handle the stop valve cover
▪ The stop valve cover is sealed where indicated by the arrow. Do
NOT damage it.
▪ After handling the stop valve, tighten the stop valve cover
securely, and check for refrigerant leaks. For the tightening
torque, refer to the table below.
To handle the service port
▪ Always use a charge hose equipped with a valve depressor pin,
since the service port is a Schrader type valve.
▪ After handling the service port, make sure to tighten the service
port cover securely. For the tightening torque, refer to the table
below.
▪ Check for refrigerant leaks after tightening the service port cover.
Tightening torques
Stop valve
size (mm)
Tightening torque N•m (turn clockwise to close)
Shaft
Valve body Hexagonal
wrench
Cap (valve
lid)
Service
port
Ø9.5
5.4~6.6
4 mm
13.5~16.5
11.5~13.9
Ø12.7
8.1~9.9
18.0~22.0
Ø15.9
13.5~16.5
6 mm
23.0~27.0
Ø19.1
27.0~33.0
8 mm
22.5~27.5
Ø25.4
Содержание VRV IV RXMLQ8T7Y1B Series
Страница 37: ......
Страница 38: ......
Страница 39: ......
Страница 40: ...4P543426 1 2018 07 Copyright 2018 Daikin 4P543426 1 0000000M...