background image

9 Relocation

Installation and operation manual

14

RWEYQ8~14T9Y1B

VRV IV water-cooled system air conditioner

4P452190-1D – 2020.10

9

Relocation

Contact  your  dealer  for  removing  and  reinstalling  the  total  unit.
Moving units requires technical expertise.

10

Disposal

This  unit  uses  hydrofluorocarbon.  Contact  your  dealer  when
discarding this unit.

NOTICE

Do  NOT  try  to  dismantle  the  system  yourself:  dismantling
of  the  system,  treatment  of  the  refrigerant,  oil  and  other
parts  MUST  comply  with  applicable  legislation.  Units
MUST  be  treated  at  a  specialised  treatment  facility  for
reuse, recycling and recovery.

For the installer

11

About the box

11.1

About 

  is  part  of  Daikin's  wider  commitment  to  reduce  our

environmental  footprint.  With 

  we  want  to  create  a  circular

economy  for  refrigerants.  One  of  the  actions  to  achieve  this,  is  the
reuse  of  reclaimed  refrigerant  in  VRV  units  produced  and  sold  in
Europe. For more information about the countries that are in scope,
visit: 

http://www.daikin.eu/loop-by-daikin

.

11.2

To remove the accessories from
the outdoor unit

Make sure that all accessories are available in the unit.

a

b

c

d

e

f

g

h

i

a

General safety precautions

b

Installation manual and operation manual

c

Additional refrigerant charge label

d

Installation information sticker

e

Fluorinated greenhouse gases label

f

Multilingual fluorinated greenhouse gases label

g

Piping accessory bag

h

Hose

i

Water filter

11.3

Accessory pipes: Diameters

Accessory pipes

(mm)

HP

Øa

Øb

Øc

Ød

Liquid pipe

▪ Front connection

(a)

Øa

Øb

▪ Top connection

Øc

Ød

8

12.7

12.7

12.7

9.5

10

12

12.7

14

Accessory pipes

(mm)

HP

Øa

Øb

Øc

Ød

Gas pipe

▪ Front connection

(a)

Øa

Øb

▪ Top connection

Øc

Ød

8

25.4

25.4

25.4

19.1

10

22.2

12

28.6

14

High pressure/Low
pressure gas pipe

▪ Front connection

(a)

Øa

Øb

▪ Top connection

Øc

Ød

8

25.4

25.4

25.4

15.9

10

19.1

12

14

22.2

(a)

Braze the straight accessory pipe onto the L-shaped
accessory pipe in order to get the correct diameter to
connect the field pipes (for front connection).

11.4

To remove the transportation stay

NOTICE

If the unit is operated with the transportation stay attached,
abnormal vibration or noise may be generated.

The compressor transportation stay must be removed. It is installed
under  the  compressor  leg  in  order  to  protect  the  unit  during
transport. Proceed as shown in the figure and procedure below.

1

Remove the bolt.

2

Lift the insulation to access the compressor mounting bolt.

3

Slightly loosen the mounting bolt.

4

Remove the transportation stay as shown in the figure below.

5

Tighten the mounting bolt to 12.3 N•m of torque.

Содержание VRV IV RWEYQ-T9

Страница 1: ...lation and operation manual VRV IV water cooled system air conditioner English Installation and operation manual VRV IV water cooled system air conditioner RWEYQ8T9Y1B RWEYQ10T9Y1B RWEYQ12T9Y1B RWEYQ1...

Страница 2: ...8 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direktiivid koos muudatustega Direktyvose su papildymais Direkt v s un to papildin jumos Smernice v platno...

Страница 3: ...S vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplot...

Страница 4: ...s not spin 13 8 2 15 Symptom The display shows 88 13 8 2 16 Symptom The compressor in the outdoor unit does not stop after a short heating operation 13 8 2 17 Symptom The inside of an outdoor unit is...

Страница 5: ...r reference guide Preparation of the installation reference data Detailed step by step instructions and background information for basic and advanced usage Format Digital files on http www daikineurop...

Страница 6: ...carrying wires are tautened before the earth wire is in case the power supply is pulled loose from the stress relief CAUTION Do NOT perform the test operation while working on the indoor units When pe...

Страница 7: ...ation CAUTION NEVER touch the internal parts of the controller Do NOT remove the front panel Some parts inside are dangerous to touch and appliance problems may happen For checking and adjusting the i...

Страница 8: ...ices ventilate the room and contact the dealer where you purchased the unit Do not use the system until a service person confirms that the portion where the refrigerant leaks is repaired 4 About the s...

Страница 9: ...ch 6 hours before operation 6 2 2 About cooling heating fan only and automatic operation Changeover cannot be made with a user interface whose display shows change over under centralised control refer...

Страница 10: ...humidity in your room with minimal temperature decrease minimal room cooling The micro computer automatically determines temperature and fan speed cannot be set by the user interface The system does...

Страница 11: ...ing for damage If damaged the unit may fall and result in injury NOTICE Do NOT wipe the controller operation panel with benzine thinner chemical dust cloth etc The panel may get discoloured or the coa...

Страница 12: ...unit manual Malfunction Measure The system operates but cooling or heating is insufficient Check if air inlet or outlet of outdoor or indoor unit is not blocked by obstacles Remove any obstacles and m...

Страница 13: ...stop Operation automatically restarts when the noise ceases 8 2 9 Symptom Noise of air conditioners Indoor unit A zeen sound is heard immediately after the power supply is turned on The electronic ex...

Страница 14: ...b Installation manual and operation manual c Additional refrigerant charge label d Installation information sticker e Fluorinated greenhouse gases label f Multilingual fluorinated greenhouse gases la...

Страница 15: ...ratures from 21 C DB to 32 C DB or 14 C WB to 25 C WB The ambient temperature around the unit should be above 0 C DB and below 40 C DB Relative humidity around the unit should be below 80 The water te...

Страница 16: ...l the water piping and field wiring front plate B has to be removed 13 2 2 To open the electrical component box of the outdoor unit NOTICE Do NOT apply excessive force when opening the electronic comp...

Страница 17: ...ery Determine the proper size using the following tables and reference figure only for indication In case of heat pump system A B B B C D F G E x y b a 3 1 2 4 5 1 2 VRV DX indoor unit 3 Branch select...

Страница 18: ...ed on the total capacity of the connected indoor units only in case RA DX indoor units are connected Total capacity index of connected indoor units Piping outer diameter size mm Gas pipe Liquid pipe 2...

Страница 19: ...ll the following restriction conditions A B C a c b A B C a To indoor units b Outdoor unit multi connecting piping kit first branch c Outdoor unit multi connecting piping kit second branch 14 2 Prepar...

Страница 20: ...on the piping between this shut off valve and the outdoor unit for cleaning by chemicals For cleaning and water draining of the outdoor unit long period of non use or during non use in winter install...

Страница 21: ...the design flow rate calculated by the hydronic engineer when designing the building system Correct valve selection is done when following conditions are met B C AND E A D For further selection requir...

Страница 22: ...ay enter the machine 14 3 6 Using the stop valve and service port To handle the stop valve Take the following guidelines into account Make sure to keep the appropriate stop valves open during operatio...

Страница 23: ...nect the vacuuming recovery unit through a manifold to the service port of all stop valves p p R410A N2 b c e a f g h d A C 1 D B a Pressure reducing valve b Nitrogen c Weighing scales d Refrigerant R...

Страница 24: ...ant piping for example water may have entered the piping first carry out the vacuum drying procedure below until all moisture has been removed All piping inside the unit has been factory tested for le...

Страница 25: ...for 1 hour the system may contain too much moisture In that case break the vacuum by pressurising with nitrogen gas to a gauge pressure of 0 05 MPa 0 5 bar and repeat steps 1 to 3 until all moisture h...

Страница 26: ...additional 0 5 kg of refrigerant per outdoor unit In case of heat recovery system Formula R X1 22 2 0 37 X2 19 1 0 26 X3 15 9 0 18 X4 12 7 0 12 X5 9 5 0 059 X6 6 4 0 022 1 04 A C R Additional refriger...

Страница 27: ...ks to each outdoor unit NOTICE The refrigerant charging port is connected to the piping inside the unit The unit s internal piping is already factory charged with refrigerant so be careful when connec...

Страница 28: ...flow rate is correct If not stop the pump immediately and carry out troubleshooting 14 6 4 To insulate the water piping The outdoor water piping MUST be insulated to prevent condensation during heatin...

Страница 29: ...g In case of heat recovery system B i a b f c f e g d c h j j i a Field power supply with earth leakage protector b Main switch c Earth connection d Outdoor unit e Indoor unit f User interface g BS un...

Страница 30: ...es using finishing tape as shown in figure below b a f c d f e f a Liquid pipe b Gas pipe c Finishing tape d High pressure low pressure gas pipe e Transmission wiring F1 F2 f Insulator 15 6 To route a...

Страница 31: ...e closed valve Select a flow switch contact of at least 15 V DC 1 mA Connect the flow switch to X2M terminals 5 and 6 In case of a multi outdoor unit system install one or more flow switches depending...

Страница 32: ...ng the current field setting value is possible In general normal operation can be resumed without special intervention after changing field settings Some field settings are used for special operation...

Страница 33: ...atus of the unit What How Changing and accessing the setting in mode 1 Once mode 1 is selected push BS1 one time you can select the wanted setting It is done by pushing BS2 Accessing the selected sett...

Страница 34: ...m 3 Each unit has a pump valve pump is OFF when slave unit does not operate Minimum water flow rate limit control To change the minimum water flow rate limit of the variable flow system change the set...

Страница 35: ...tion Check that the unit is properly installed to avoid abnormal noises and vibrations when starting up the unit Field wiring Be sure that the field wiring has been carried out according to the instru...

Страница 36: ...s 17 4 To perform a test run 1 Close all front panels in order to not let it be the cause of misjudgement except the electrical component box inspection opening service cover 2 Make sure all field set...

Страница 37: ...site publicly accessible The full set of latest technical data is available on the Daikin Business Portal authentication required 19 1 Service space Outdoor unit Make sure the space around the unit is...

Страница 38: ...pressor Double tube heat exchanger Liquid receiver Thermistor 20 Disposal NOTICE Do NOT try to dismantle the system yourself dismantling of the system treatment of the refrigerant oil and other parts...

Страница 39: ......

Страница 40: ...4P452190 1D 2020 10 Copyright 2017 Daikin 4P452190 1 D 0000000 Verantwortung f r Energie und Umwelt...

Отзывы: