17
REYQ-TAYCA EDUS371706C-D
8. Capacity Range
8.1 Connection Ratio
Connection ratio =
Total capacity index of the indoor units
Capacity index of the outdoor units
Type
Min.
connection
ratio
Max. connection ratio
Types of connected indoor units
Type of connected air treatment equipment
When using only
FXDQ, FXMQ-PB,
FXAQ, FXSQ07-54T
When using at least
one FXFQ07/09,
FXZQ05T
FXSQ05T
Other indoor unit
models
FXMQ-MF
When FXMQ-MF is
only connected
When FXMQ-MF
and indoor units are
connected
Single outdoor units
50% *1
200% *2
130%
200% *2
100%
100% *3 *4
Double outdoor units
160% *2
Triple outdoor units
130%
Note:
*1. 70%: REYQ72T type
*
2. If the operational capacity of indoor units is more than 130%, low airflow operation is enforced in all the indoor units. Field setting now exists to
configure this situation. For cooling and heating mode – see below.
*3. When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total connection capacity of the outdoor-air
processing units (FXMQ-MF) must not exceed 30% of the capacity index of the outdoor units. And the connection ratio must not exceed 100%.
*4. It is permitted to use a maximum connection ratio of 130% in some circumstances – please contact your local Daikin representative for further
details.
*5. For indoor units used for cooling only (do not connect to Branch Selector unit when using for heat recovery), total capacity index must be 50%
or less than the capacity index of the outdoor units.
Indoor unit fan tap setting
Indoor units fan speed limitation related to connection capacity and outdoor air temperature for energy saving.
Default value = 0
Value
Indoor unit fan tap setting
0
Fan speed is limited to L tap when indoor units capacity ≥ 130%.
1
In heating mode, fan speed is limited to L tap when indoor units capacity ≥ 130%.
2
Fan speed follows the setting of the remote controllers (not limited by indoor units connection capacity).
3
Fan speed is limited to L tap when outdoor air temperature goes down to below 85.1°F (29.5°C) and indoor air
temperature is in condition A (*1). It returns to remote controller setting when outdoor air temperature goes up to over
90.5 °F (32.5°C) or indoor air temperature is in condition B (*2).
4
Fan speed is limited to L tap when outdoor air temperature goes down to below 74.3°F (23.5°C) and indoor air
temperature is in condition A (*1). It returns to remote controller setting when outdoor air temperature goes up to over
79.7°F (26.5°C) or indoor air temperature is in condition B (*2).
5
Fan speed is limited to L tap when outdoor air temperature goes down to below 66.7°F (19.3°C) and indoor air
temperature is in condition A (*1). It returns to remote controller setting when outdoor air temperature goes up to over
72.1°F (22.3°C) or indoor air temperature is in condition B (*2).
6
Fan speed is limited to L tap when outdoor air temperature goes down to below 85.1°F (29.5°C). It returns to remote
controller setting when outdoor air temperature goes up to over 90.5°F (32.5°C).
7
Fan speed is limited to L tap when outdoor air temperature goes down to below 74.3°F (23.5°C). It returns to remote
controller setting when outdoor air temperature goes up to over 79.7°F (26.5°C).
8
Fan speed is limited to L tap when outdoor air temperature goes down to below 66.7°F (19.3°C). It returns to remote
controller setting when outdoor air temperature goes up to over 72.1°F (22.3°C).
*
1. Indoor condition A: Temperature difference (indoor air temperature – set temperature) is more than –2.7°F (–1.5°C) and less than 5.4°F (3°C).
*
2. Indoor condition B: Temperature difference (indoor air temperature – set temperature) is –2.7°F (–1.5°C) or less, or 5.4°F (3°C) or more.
Содержание VRV IV REYQ-TAYCA
Страница 1: ...EDUS371706C D 202002 Engineering Data Heat Recovery 60 Hz Design Manual REYQ TAYCA 575 V ...
Страница 2: ......
Страница 27: ...25 REYQ TAYCA EDUS371706C D 10 Dimensions REYQ72 168TAYCA C 3D107340A ...
Страница 32: ...30 REYQ TAYCA EDUS371706C D 12 Center of Gravity REYQ72 120TAYCA 4D107384 ...
Страница 33: ...31 REYQ TAYCA EDUS371706C D REYQ144 168TAYCA 4D107385 ...
Страница 35: ...33 REYQ TAYCA EDUS371706C D 14 Piping Diagrams REYQ72 120TAYCA 3D107166 ...
Страница 36: ...34 REYQ TAYCA EDUS371706C D REYQ144 168TAYCA 3D107167 ...
Страница 43: ...41 REYQ TAYCA EDUS371706C D 18 Operation Limits REYQ72 384TAYCA 3D107375 ...
Страница 45: ...43 REYQ TAYCA EDUS371706C D 20 Sound Levels Reference Data REYQ72TAYCA 4D107379B ...
Страница 46: ...44 REYQ TAYCA EDUS371706C D REYQ96TAYCA 4D107380A ...
Страница 47: ...45 REYQ TAYCA EDUS371706C D REYQ120TAYCA 4D107381A ...
Страница 48: ...46 REYQ TAYCA EDUS371706C D REYQ144TAYCA 4D107382A ...
Страница 49: ...47 REYQ TAYCA EDUS371706C D REYQ168TAYCA 4D107383A ...
Страница 57: ...55 REYQ TAYCA EDUS371706C D 23 Caution Label 23 1 REYQ72 168TAYCA Operation Name Plate 3P558142 1B ...
Страница 58: ...56 REYQ TAYCA EDUS371706C D 3P558142 1B ...
Страница 59: ...57 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Страница 60: ...58 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Страница 61: ...59 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Страница 62: ...60 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Страница 63: ...61 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Страница 64: ...62 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Страница 65: ...63 REYQ TAYCA EDUS371706C D Collective Indications Label 3P385987 1A ...
Страница 66: ...64 REYQ TAYCA EDUS371706C D 3P385987 1A ...
Страница 77: ......
Страница 78: ......
Страница 79: ......