Operation manual
19
HXHD125A8V1B
VRV IV system indoor unit
4P404572-1 – 2015.04
5.13. Field settings table
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range
Step
Unit
Date
Value
Date
Value
0
Remote control setup
00
Installation related setting
(a)
2
2~3
1
—
01
Installation related setting
0
–5~5
0.5
°C
02
Not applicable. Do not change the default value.
1
—
—
—
03
Status: space heating schedule timer mode
Method 1=1 / Method 2=0
1 (ON)
0/1
—
—
04
Not applicable. Do not change the default value.
1
—
—
—
1
Automatic storage timing for domestic water heating
00
Status: night time storage
1 (ON)
0/1
—
—
01
Night time storage start time
1:00
0:00~23:00
1:00
hour
02
Status: day time storage
0 (OFF)
0/1
—
—
03
Day time storage start time
15:00
0:00~23:00
1:00
hour
2
Automatic setback function
00
Status: setback operation
1 (ON)
0/1
—
—
01
Setback operation start time
23:00
0:00~23:00
1:00
hour
02
Setback operation stop time
5:00
0:00~23:00
1:00
hour
3
Weather dependent set point
00
Low ambient temperature (Lo_A)
–10
–20~5
1
°C
01
High ambient temperature (Hi_A)
15
10~20
1
°C
02
Set point at low ambient temperature (Lo_Ti)
70
25~80
1
°C
03
Set point at high ambient temperature (Hi_Ti)
45
25~80
1
°C
4
Disinfection function
00
Status: disinfection operation
1 (ON)
0/1
—
—
01
Disinfection operation day selection
Fri
Mon~Sun
—
—
02
Disinfection operation start time
23:00
0:00~23:00
1:00
hour
5
Automatic setback and disinfection set point
00
Set point: disinfection operation temperature
70
60~75
5
°C
01
Disinfection operation time duration
10
5~60
5
min
02
Leaving water setback temperature
5
0~10
1
°C
03
Room setback temperature
18
17~23
1
°C
04
Not applicable. Do not change the default value.
0
—
—
—
6
Option setup
00
Installation related setting
0 (OFF)
0/1
—
—
01
Installation related setting
0 (OFF)
0/1
—
—
02
Not applicable. Do not change the default value.
0
—
—
—
03
Not applicable. Do not change the default value.
0
—
—
—
04
Installation related setting
0 0/2
1
—
7
Option setup
00
Not applicable. Do not change the default value.
0
—
—
—
01
Not applicable. Do not change the default value.
0
—
—
—
02
Installation related setting
0 (A)
0/1
—
—
03
Installation related setting
0 (OFF)
0/1
—
—
04
Installation related setting
0 (OFF)
0/1
—
—
8
Option setup
00
Installation related setting
1 (ON)
0/1
—
—
01
Not applicable. Do not change the default value.
1
—
—
—
02
Not applicable. Do not change the default value.
0
—
—
—
03
Status: low noise level
1
1~3
1
—
04
Installation related setting
0 0~2
1
—
Содержание VRV IV HXHD125A8V1B
Страница 1: ...OPERATION MANUAL HXHD125A8V1B system indoor unit...
Страница 23: ......
Страница 24: ...4P404572 1 2015 04 Copyright 2015 Daikin...