R REMQ10~16P8 + REMHQ12P8Y1B

VRVIII System air conditioner

4PW48463-1A

Installation manual

22

2

Normal system display

3

Remote controller malfunction code display

Remote controller heating mode malfunction codes

Remote controller cooling mode malfunction codes

11.6. Procedure for inputting the additional 

refrigerant charge weight into the PCB

Availability of the leak detection function feature requires input of the
additional refrigerant charge amount immediately after finishing the
automatic charging. The input must be executed before performing
the test operation.

Procedure

1

Close the electric box lid and all front panels except the one on
the side of the electric box.

2

Press and hold the 

 button for 5 seconds to enter into

setting mode 2. 

The H1P LED is on 

w

.

3

Press the 

 button 14 times.

The LED display must be as follows:

Press the 

 button once as confirmation of the

LEDs combination.
LEDs will be blinking in function of the last entered setting
(factory setting = 0 kg).

4

The weighed and already recorded amount of additional
refrigerant charge (not the total amount of refrigerant present in
the system) must be entered by selecting the corresponding
LED display.

Scroll through the possible LED combinations by pressing the

  button until the LED combination corresponds to the

weight of additional refrigerant charge you must input.
Select the required input by pressing the 

 button

and confirm the input into the PCB by pressing the

 button again.

LED 

display

(Default 

status

before 

delivery)

Micro-

computer
operation

monitor

Mode

Ready

/Error

Cooling/Heating 

changeover

Low 

noise

Demand

Multi

Indivi-

dual

Bulk 

(master)

Bulk 

(slave)

HAP

H1P

H2P

H3P

H4P

H5P

H6P

H7P

H8P

Single outdoor 

unit system

c

x

x

w

x

x

x

x

x

Multiple 
outdoor 

unit 

system

Master 

unit

(a)

(a) The state of the H8P (multi) LED in a multi-system shows which unit is the master 

unit (

w

), slave 1 unit (

c

) or slave 2 unit (

x

). 

Only the master unit is connected to the indoor units with interunit wiring.

c

x

x

w

x

x

x

x

w

Slave 

unit 
1

(a)

c

x

x

x

x

x

x

x

c

Slave 

unit 
2

(a)

c

x

x

x

x

x

x

x

x

Error code 

P8 

recharge 
operation

Close valve A immediately and press the TEST OPERATION 
button once.
The operation will restart from the charging mode judgement 
onwards.

P2

charge 
hold

Close valve A immediately. Check 
following items:
- Check if the gas side stop valve is 

opened correctly

- Check if the valve of the refrigerant 

cylinder is opened

- Check if the air inlet and outlet of the 

indoor unit are not obstructed

After correcting the 
abnormality, restart 
the automatic 
charging procedure 
again.

Error code 

PA

PH

PC

replace 
cylinder

Close valve A and replace the empty cylinder. When renewed, 
open valve A (the outdoor unit will not stop operating).
The code on the display shows the unit where a cylinder is to be 
renewed:

PA

 = master unit, 

PH

 = slave unit 1, 

PC

 = slave unit 2, flashing 

PA

PH

 and 

PC

 = all units

After recplacing the cylinder, open valve A again and continue the 
work.

In case of an outdoor multi system, replacing the 
refrigerant tank of the outdoor unit during the refrigerant 
charging operation when the display on the remote 
controller is not showing 

PA

PH

 or 

PC

, may cause an 

abnormal stop of the refrigerant charging operation.

P8 

recharge 
operation

Close valve A immediately.
Restart the automatic charging procedure again.

P2

charge 
hold

Close valve A immediately. Check 
following items:
- Check if the high pressure/low 

pressure gas pipe, suction gas pipe, 
liquid pipes and equalizer pipe stop 
valves are opened correctly

- Check if the valve of the refrigerant 

cylinder is opened

- Check if the air inlet and outlet of the 

indoor unit are not obstructed

After correcting the 
abnormality, restart 
the automatic 
charging procedure 
again.

*
abnormal 
stop

Close valve A immediately. Confirm the 
malfunction code by the remote controller 
and correct the abnormality by following 
the 

"Correcting after abnormal completion 

of the test operation" on page 26

.

If a wrong value is inputted for the additional charged
refrigerant weight, the accuracy of the leak detection
function will decrease.

H1P

H2P

H3P

H4P

H5P

H6P

H7P

w x

x w w w x

BS1  MODE

BS2  SET

BS3  RETURN

BS2  SET

BS3  RETURN

BS3  RETURN

Содержание VRV III

Страница 1: ...INSTALLATION MANUAL REMQ8P9Y1B REMQ10P8Y1B REM H Q12P8Y1B REMQ14P8Y1B REMQ16P8Y1B System air conditioner ...

Страница 2: ... mm d 500 mm a 50 mm b 100 mm c 50 mm d 500 mm a 200 mm b 300 mm a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm a 200 mm b 300 mm e 400 mm a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm f 600 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm f 500 mm a 10 mm b 300 mm c 10 mm d 300 mm e 20 mm f 500 mm a 50 mm b 100 mm c 50 mm d 100 mm e 100 mm f 500 mm 1500 500 11 2 1 6...

Страница 3: ...m 500 mm 1 1 1 A B 2 2 2 4 5 3 8 F1 F2 F1 F2 Q1 Q2 F1 F1 F2 F2 Q1Q2 7 TOIN DUNIT TOOUT DUNIT TOMULTIUNIT A1P Q1 Q2 A1P Q1 Q2 A1P 1 2 2 3 4 5 6 8 10 10 9 9 REMQ8 12 REMQ14 16 REMHQ12 1 2 3 4 1 5 6 7 8 F1 F2F1F2 F1 F2F1F2 TO IN D UNIT TO OUT D UNIT TO IN D UNIT TO OUT D UNIT F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 11 10 10 9 9 12 13 14 15 16 17 18 20 19 21 ...

Страница 4: ...entom ima uz uvjet da se oni koriste u skladu s našim uputama 16 megfelelnek az alábbi szabvány ok nak vagy egyéb irányadó dokumentum ok nak ha azokat előírás szerint használják 17 spełniają wymogi następujących norm i innych dokumentów normalizacyjnych pod warunkiem że używane są zgodnie z naszymi instrukcjami 18 sunt în conformitate cu următorul următoarele standard e sau alt e document e normat...

Страница 5: ...in matalapainepuolen lämpötila L C TSmax Suurinta sallittua painetta PS vastaava kyllästyslämpötila M C Kylmäaine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi 14 Maximální přípustný tlak PS K bar Minimální maximální přípustná teplota TS TSmin Minimální teplota na nízkotlaké straně L C TSmax Saturovaná teplota odpovídající maximálnímu přípustnému tlak...

Страница 6: ... 75 kW For changing the refrigerant flow to indoor units the REYQ P system can be combined with BS units of the types BSVQ100P BSVQ160P and BSVQ250P only Other BS unit types will cause malfunctions when combined with the REYQ P system The REM H Q P units can be combined with Daikin VRV indoor units for air conditioning purposes suitable for R410A The present installation manual describes the proce...

Страница 7: ... REYQ48 REMQ16 REMQ16 REMQ16 600 1560 Standard combinations of outdoor units Total capacity of indoor units REYHQ16 REMQ8 REMQ8 200 520 REYHQ20 REMQ8 REMHQ12 250 650 REYHQ22 REMQ10 REMHQ12 275 715 REYHQ24 REMHQ12 REMHQ12 300 780 NOTE When installing a multi outdoor system with 2 units BHFQ23P907 outdoor unit multi connection piping kit is required with 3 units BHFQ23P1357 outdoor unit multi connec...

Страница 8: ...lowable safety limits in the event of a refrigerant leak 11 To prevent dripping water to form a puddle underneath the unit install a drain pan available as option kit 12 The equipment is not intended for use in a potentially explosive atmosphere Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals Small animals making contact wi...

Страница 9: ...e The height of the foundation must at least be 150 mm from the floor The unit must be installed on a solid longitudinal foundation steelbeam frame or concrete and make sure the base under the unit is larger than the grey marked area as indicated in figure 3 Fasten the unit in place using four foundation bolts M12 It is best to screw in the foundation bolts until their length remains 20 mm above t...

Страница 10: ...iping must be installed by a licensed refrigeration technician and must comply with relevant local and national regulations Caution to be taken when brazing refrigerant piping Do not use flux when brazing copper to copper refrigerant piping Particularly for the HFC refrigerant piping Therefore use the phosphor copper brazing filler metal BCuP which does not require flux Flux has extremely harmful ...

Страница 11: ...alves are fully closed 2 Connect a charge hose to service ports of all stop valves 3 Recover gas and oil from the pinched piping by using a recovery unit 4 When all gas and oil is recovered from the pinched piping disconnect the charge hose and close the service ports 5 In case the pinched piping lower parts looks like detail A in figure 6 proceed with procedure step 8 In case the pinched piping l...

Страница 12: ...ons The piping between the outdoor units must be routed level or slightly upward to avoid the risk of oil retention into the piping side Pattern 1 Pattern 2 Prohibited patterns change to pattern 1 or 2 To avoid the risk of oil retention to the outmost outdoor unit always connect the stop valve and the piping between outdoor units as shown in the 4 correct possibilities of the figure below NOTE All...

Страница 13: ...lation may lead to malfunction of the outdoor unit 5 Piping length restrictions Make sure to perform the piping installation within the range of the maximum allowable pipe length allowable level difference and allowable length after branching as indicated in 6 6 Example of connection on page 9 6 5 Protection against contamination when installing pipes Take measures to prevent foreign materials lik...

Страница 14: ... 40 m Outdoor unit multi connection piping kit and refrigerant branch kit selection How to select the refnet joint When using refnet joints at the first branch counted from the outdoor unit side choose from the following table in accordance with the capacity of the outdoor unit example refnet joint A How to select the refnet header Choose from the following table in accordance with the total capac...

Страница 15: ...cted outdoor unit Suction gas pipe Liquid pipe 20 25 32 40 50 12 7 6 4 Outdoor unit capacity type Hp Piping outer diameter size mm 63 80 100 125 15 9 9 5 Suction gas pipe HP LP gas pipe Liquid pipe 200 19 1 9 5 8 10 22 2 19 1 9 5 250 22 2 9 5 12 28 6 19 1 12 7 14 16 28 6 22 2 12 7 D Equalizer piping outdoor units only Piping outer diameter size mm 19 1 How to calculate the additional refrigerant t...

Страница 16: ...to 90 m Size up of the main suction gas pipe may affect a good oil return to the outdoor unit due to influence of the HP LP gas pipe indoor unit 8 b c d e f g p 90 m increase the pipe size of b c d e f g Increase the pipe size as follows For calculation of total extension length the actual length of above pipes must be doubled except length of main pipes and of pipes which do not have an increased...

Страница 17: ... fan PS Switching power supply A1P A3P Q1DI Earth leakage breaker field supply Q1RP Phase reversal detection circuit R1T Thermistor air A1P fin A3P R3T R9T Thermistor H E gas H E de icer sub cool H E gas sub cool H E liquid H E liquid suction liquid R10 Resistor current sensor A4P A8P R31T R33T Thermistor discharge M1C M3C R50 R59 Resistor R90 Resistor current sensor R95 Resistor current limiting ...

Страница 18: ... for connection wiring to indoor outdoor transmission F1 F2 outdoor outdoor transmission F1 F2 outdoor multi transmission Q1 Q2 and on how to use BS1 BS5 and DS1 DS2 switch Do not operate the unit by short circuiting protection device S1PH S3PH NOTE Use copper conductors only For connection wiring to the central remote controller refer to the installation manual of the central remote controller Us...

Страница 19: ...ans that an earth leakage breaker capable of handling high frequency electrical noise must be used in order to prevent malfunctioning of the earth leakage breaker itself Earth leakage breakers that are especially designed for protecting ground faults must be used in conjunction with main switch and fuse for use with wiring Never connect the power supply in reversed phase The unit can not operate n...

Страница 20: ...the back of the electric box lid 2 Power wiring and ground wiring between outdoor units inside conduit When the wiring is routed out through the lateral panel 3 Transmission wiring 4 Pipe opening 5 Conduit 6 Power wiring and ground wiring 7 Cut off the shaded zones before use 8 Through hole cover 1 Knockout hole 2 Burr 3 If there are any possibilities that small animals enter the system through th...

Страница 21: ...ansmission wiring between outdoor units 1 Liquid pipe 2 HP LP gas pipe 3 Finishing tape 4 Suction gas pipe 5 Transmission wiring 6 Insulation material 1 Power supply 380 415 V 3N 50 Hz 2 Earth leakage breaker 3 Fuse 4 Grounding wire 5 Power supply terminal block 6 Connect each power wire RED to L1 WHT to L2 BLK to L3 and BLU to N 7 Ground wire GRN YLW 8 Clamp the power wire to the plastic bracket ...

Страница 22: ...rigerant follow the procedure as described in this chapter 11 1 Important information regarding the refrigerant used This product contains fluorinated greenhouse gases covered by the Kyoto Protocol Do not vent gases into the atmosphere Refrigerant type R410A GWP 1 value 1975 1 GWP global warming potential Please fill in with indelible ink the factory refrigerant charge of the product the additiona...

Страница 23: ...at are active can be read from the LED display in the Monitor Mode procedure below NOTE National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate official national language on the unit Therefore an additional multilingual fluorinated greenhouse gases label is supplied with the unit Sticking instructions are illustrated on the backside o...

Страница 24: ... button to return to step 1 setting mode 1 H1P x OFF Adding refrigerant using the automatic refrigerant charging function is recommended When charging a system charging over the permissible quantity can cause liquid hammer Always use protective gloves and protect your eyes when charging refrigerant When the refrigerant charging procedure is done or when pausing close the valve of the refrigerant t...

Страница 25: ...o BS unit indoor unit 13 Stop valve 14 Service port 15 Field piping 16 Refrigerant flow when pre charging through the liquid stop valve service port refer to step 3 on page 19 17 Refrigerant flow when automatic charging through the charge port refer to step 5 on page 20 18 The refrigerant will be charged with 30 kg in 1 hour at an outdoor temperature of 30 C DB 12 kg at 0 C DB If you need to speed...

Страница 26: ... to confirm that charging is completed Record the amount that was added on the additional refrigerant charge label provided with the unit and attach it on the back side of the front panel Perform the procedure 11 6 Procedure for inputting the additional refrigerant charge weight into the PCB as described on page 22 10 In case leak detection function not required Press the button once and the charg...

Страница 27: ...g c x x w x x x x w Slave unit 1 a c x x x x x x x c Slave unit 2 a c x x x x x x x x Error code P8 recharge operation Close valve A immediately and press the TEST OPERATION button once The operation will restart from the charging mode judgement onwards P2 charge hold Close valve A immediately Check following items Check if the gas side stop valve is opened correctly Check if the valve of the refr...

Страница 28: ...procedure from step 2 onwards Make sure to open the stop valves after charging the refrigerant Operating with the stop valves closed will damage the compressor BS1 MODE BS1 MODE WARNING ELECTRIC SHOCK Caution when performing service to inverter equipment 1 Do not open the electric box cover for 10 minutes after the power supply is turned off 2 Measure the voltage between terminals on the terminal ...

Страница 29: ...itch which is located on the outdoor unit PCB A1P The figure shows state of the LED indications when the unit is shipped from the factory Check operation procedure 1 Turn the power on for the outdoor unit and the indoor unit Be sure to turn the power on at least 6 hours before operation in order to have power running to the crankcase heater 2 Make sure that transmission is normal by checking the L...

Страница 30: ...n state x normal w abnormal c under preparation or under test operation 2 Indication of low noise operation state x standard operation factory setting w operation 3 Indication of power consumption limitation setting x standard operation factory setting w operation NOTE If you get confused in the middle of the setting process push the button Then it returns to setting mode 1 H1P LED is off Possible...

Страница 31: ...tarts During the test operation the refrigerant running sound or the magnetic sound of a solenoid valve may become loud and the LED display may change but these are not mal functions During the test operation it is not possible to stop the unit operation from a remote controller To abort the operation press the button The unit will stop after 30 seconds 6 Close the front panel in order to let it n...

Страница 32: ...igerant charge hose to the refrigerant charging port for additionaly charging 4 When the unit is not operating push the button until the additional refrigerant charging operation function A in setting mode 2 can be defined refer to Setting the mode on page 25 the H1P LED is on w 5 The operation starts automatically The H2P LED will start flashing c and the messages Test operation and Under central...

Страница 33: ... heavier than air Procedure for checking maximum concentration Check the maximum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply 1 Calculate the amount of refrigerant kg charged to each system separately 2 Calculate the smallest room volume m3 In a case such as the following calculate the volume of A B as a single room or as the smallest ro...

Страница 34: ...6P8 REMHQ12P8Y1B VRVIII System air conditioner 4PW48463 1A 16 DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local and national legislation NOTES ...

Страница 35: ... 3 2 6 6 6 6 23 18 9 8 1 2 4 3 5 13 14 15 10 7 12 19 2 1 24 6 11 16 17 15 6 5 10 11 12 7 4 9 16 17 18 3 8 13 14 2 2 1 1 9 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 4 4 6 6 6 6 6 6 NOTES 22 23 24 ...

Страница 36: ...4PW48463 1A Copyright Daikin ...

Отзывы: