• VRV
®
Systems • Outdoor Unit
3
• Outdoor Unit • VRV
®
III heat recovery, with connection to heating only hydrobox • REYAQ-P
1
Specifications
Standard Accessories : Installation manual; Quantity : 1
Piping
connections
Liquid
Type
Braze connection
OD
mm
9.52
12.7
Gas
Type
Braze connection
OD
mm
22.2
28.6
Discharge
gas
Type
Braze connection
OD
mm
19.1
22.2
Piping length OU - IU
Max.
m
100
After branch
Max.
m
40
Total piping
length
System
Actual
m
300
Level
difference
OU - IU
Outdoor unit in
highest position
m
40
Indoor unit in
highest position
m
40
IU - IU
Max.
m
15
Additional refrigerant charge
kg/m
See installation manual
High pressure
side
Design pressure
bar
40
Defrost method
Deicer
Safety devices Item
01
HPS
02
Fan motor driver overload protector
03
Inverter overload protector
04
Overcurrent relay
PED
Category
Category II
1-1 Technical Specifications
REYAQ10P
REYAQ12P
REYAQ14P
REYAQ16P