Si34-601A
Field Setting
Test Operation
175
For setting items of (*1), refer to detailed information provided on page 174 onward.
Setting item
Content and objective of setting
Overview of setting procedure
Service setting
1
Indoor unit fan
forced H operation
Used to operate the indoor unit in the
stopped state in forced H operation mode.
Set No. 5 of "Setting mode 2" to indoor unit
forced fan H.
2
Indoor unit forced
operation
Used to operate the indoor unit in forced
operation mode.
Set No. 6 of "Setting mode 2" to indoor unit
forced operation mode.
3
Change of targeted
evaporating
temperature
(in cooling)
In cooling operation, used to change the
targeted evaporating temperature for
compressor capacity control.
Select high side or low side with No. 8 of
"Setting mode 2".
4
Change of targeted
condensing
temperature
(in heating)
In heating operation, used to change the
targeted condensing temperature for
compressor capacity control.
Select high side or low side with No. 9 of
"Setting mode 2".
5
Setting of defrost
selection
Used to change a temperature at which the
defrost operation is initiated, thus making
the initiation easy or hard.
Select fast side or slow side with No. 10 of
"Setting mode 2".
6
Setting of
sequential startup
Used to start units not in sequence but
simultaneously.
Set No. 11 of "Setting mode 2" to NONE.
7
Emergency
operation (*1)
If the compressor has a failure, used to
prohibit the operation of compressor(s)
concerned or outdoor unit(s) concerned
and to conduct emergency operation of the
system only with operable compressor(s)
or outdoor unit(s).
Make this setting while in "Setting mode 2".
For system with a single outdoor unit: Set
with No. 19 or 42.
For system with multiple outdoor units: Set
with No. 38, 39, or 40.
8
Additional
refrigerant
charging (*1)
If a necessary amount of refrigerant cannot
be charged due to the stop of outdoor unit,
operate the outdoor unit and then refill
refrigerant.
Set No. 20 of "Setting mode 2" to ON and
then charge refrigerant.
9
Refrigerant
recovery mode (*1)
Used to recover refrigerant on site.
With operations of indoor and outdoor units
prohibited, fully open the expansion valve
of the indoor and outdoor units.
Set No. 21 of "Setting mode 2" to ON.
10
Vacuuming mode
(*1)
Used to conduct vacuuming on site.
Fully open the expansion valves of the
indoor and outdoor units, and energize part
of solenoid valves. Use a vacuum pump to
conduct vacuuming.
Set No. 21 of "Setting mode 2" to ON.
11
ENECUT test
operation
Used to forcedly turn ON the ENECUT.
(Be noted this mode is not functional with
the indoor unit remote controller turned
ON.)
Set No. 24 of "Setting mode 2" to ON.
12
Power transistor
check mode
Used for the troubleshooting of DC
compressors.
Inverter waveform output makes it possible
to judge whether a malfunction results from
the compressor or the PC board.
Set No. 28 of "Setting mode 2" to ON.
13
Setting of model
with spare PC
board
In order to replace the PC board by a spare
one, be sure to make model setting.
For this setting, set the DS2-2, -3, and-4
switches on the PC board to the model
concerned.
Содержание VRV III RXYQ5-54PY1
Страница 1: ...RXYQ5 54PY1 R 410A Heat Pump 50Hz Si34 601A...
Страница 22: ...Si34 601A Specifications 11 Part 2 Specifications 1 Specifications 12 1 1 Outdoor Units 12 1 2 Indoor Units 33...
Страница 72: ...Si34 601A Refrigerant Circuit Refirgerant Circuit 61 RXYQ5P 3D050782 5 6 2 K T E D M N A P O W G J 4 3 1...
Страница 74: ...Si34 601A Refrigerant Circuit Refirgerant Circuit 63 RXYQ8P 3D050783 5 7 6 2 3 1 4 D N A P M O W T E F V G J...
Страница 101: ...Refrigerant Flow for Each Operation Mode Si34 601A 90 Refirgerant Circuit...
Страница 153: ...Outline of Control Indoor Unit Si34 601A 142 Function...
Страница 219: ...Troubleshooting by Remote Controller Si34 601A 208 Troubleshooting...
Страница 226: ...Si34 601A Troubleshooting by Remote Controller Troubleshooting 215...
Страница 325: ...Troubleshooting OP Unified ON OFF Controller Si34 601A 314 Troubleshooting...
Страница 327: ...Piping Diagrams Si34 601A 316 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ5PY1 3D050782...
Страница 328: ...Si34 601A Piping Diagrams Appendix 317 RXYQ8P 3D050783...
Страница 329: ...Piping Diagrams Si34 601A 318 Appendix RXYQ10P 12PY1 3D050784...
Страница 330: ...Si34 601A Piping Diagrams Appendix 319 RXYQ14P 16P 18PY1 3D050785...
Страница 334: ...Si34 601A Piping Diagrams Appendix 323 FXUQ BEVQ Indoor unit Connection Unit 4D037995F 4D034127B...
Страница 335: ...Wiring Diagrams for Reference Si34 601A 324 Appendix 2 Wiring Diagrams for Reference 2 1 Outdoor Unit RXYQ5PY1 3D050453G...
Страница 336: ...Si34 601A Wiring Diagrams for Reference Appendix 325 RXYQ8PY1 3D050454J...
Страница 337: ...Wiring Diagrams for Reference Si34 601A 326 Appendix RXYQ10PY1 3D050455H...
Страница 338: ...Si34 601A Wiring Diagrams for Reference Appendix 327 RXYQ12PY1 3D051890G...
Страница 339: ...Wiring Diagrams for Reference Si34 601A 328 Appendix RXYQ14P 16P 18PY1 3D050456H...
Страница 340: ...Si34 601A Wiring Diagrams for Reference Appendix 329 2 2 Field Wiring RXYQ5P 8P 10P 12P 14P 16P 18PY1 3D051452D...
Страница 341: ...Wiring Diagrams for Reference Si34 601A 330 Appendix RXYQ20P 22P 24P 26P 28P 30P 32PY1 3D052261B...
Страница 342: ...Si34 601A Wiring Diagrams for Reference Appendix 331 RXYQ34P 36P 38P 40P 42P 44P 46P 48P 50P 52P 54PY1 C 3D052262B...
Страница 343: ...Wiring Diagrams for Reference Si34 601A 332 Appendix 2 3 Indoor Unit FXCQ20M 25M 32M 63MVE 3D039556A...
Страница 344: ...Si34 601A Wiring Diagrams for Reference Appendix 333 FXCQ40M 50M 80M 125MVE 3D039557A...
Страница 345: ...Wiring Diagrams for Reference Si34 601A 334 Appendix FXFQ25M 32M 40M 50M 63M 80M 100M 125MVE 3D039600A...
Страница 346: ...Si34 601A Wiring Diagrams for Reference Appendix 335 FXZQ20M 25M 32M 40M 50M7V1B 3D038359...
Страница 347: ...Wiring Diagrams for Reference Si34 601A 336 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Страница 350: ...Si34 601A Wiring Diagrams for Reference Appendix 339 FXSQ20M 25M 32M 40M 50M 63M 80M 100M 125MVE 3D039561A...
Страница 351: ...Wiring Diagrams for Reference Si34 601A 340 Appendix FXMQ40MA 50MA 63MA 80MA 100MA 125MAVE 3D039620B...
Страница 352: ...Si34 601A Wiring Diagrams for Reference Appendix 341 FXMQ200MA 250MAVE 3D039621B...
Страница 353: ...Wiring Diagrams for Reference Si34 601A 342 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Страница 354: ...Si34 601A Wiring Diagrams for Reference Appendix 343 FXAQ20MA 25MA 32MAVE 40MA 50MA 63MAVE 3D034206C...
Страница 356: ...Si34 601A Wiring Diagrams for Reference Appendix 345 FXUQ71MA 100MA 125MAV1 3D044973A...
Страница 357: ...Wiring Diagrams for Reference Si34 601A 346 Appendix FXMQ125MF 200MF 250MFV1 3D044996C...
Страница 358: ...Si34 601A Wiring Diagrams for Reference Appendix 347 BEVQ71MA 100MA 125MAVE 3D044901B...
Страница 381: ...Method of Checking The Inverter s Power Transistors and Diode Modules Si34 601A 370 Appendix...
Страница 395: ...Si34 601A iv Index...