Penyelesaian Masalah Menggunakan Remote Kontrol
Si341213
Diagnosis Servis
132
Penyelesaian Masalah
Perhatian
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Normal
After fixing the incorrect
wiring, press and hold the
RESET button on the
master
unit outdoor PCB for 5
seconds.
The unit will not run for up to
12 minutes.
Normal
Install the DIII-NET extension
adaptor.
Replace the indoor unit PCB.
Replace the unit outdoor PCB.
Catatan:
1. Check the correct wiring “indoor-outdoor” and “outdoor-outdoor” by Installation Manual.
What is Auto Alamat?
This is the Alamat automatically assigned to Unit Indoor and Unit Outdoor after initial power
supply upon installation, or after executing rewiring (Keep pressing the
more than 4 seconds).
RESET button for
Is electricity being
introduce for the first time
after installation or after an
indoor or unit outdoor
PCB has been
replaced?
YES
Does
an error
occur even after
12 minutes elapses
from the time when
electricity is introduced
to indoor and
unit
outdoor
s?
YES
NO
NO
Is
indoor - outdoor
and outdoor - outdoor
unit transmission
wiring normal?
(
1)
YES
Press and hold the RESET
button on the unit outdoor
PCB for 5 seconds.
NO
Does an error reoccur?
NO
YES
Disconnect
the outdoor-
unit outdoor
transmission wiring to
create the one-system
status, and then check
whether or not the
system is
normal.
YES
NO
Does a
“
UH
” error occur for
all indoor units in the
system?
YES
NO