HXY48TAVJU
VRV System indoor unit
3P616151-1A – 2021.12
Installation and operation manual
23
Note: The user interface can display temperatures in Celsius only.
A
Option setup
00
Not applicable. Do not change the default value.
0
—
—
—
01
Not applicable. Do not change the default value.
0
—
—
—
02
Pump target ΔT (heating).
9 (5)
5.4~14.4
(3~8)
1.8 (1)
°F (°C)
03
Allowable overshoot on leaving water.
5.4 (3)
1.8~9
(1~5)
0.9 (0.5)
°F (°C)
04
Not applicable. Do not change the default value.
0
—
—
—
b
Settings are not applicable
00
Not applicable. Do not change the default value.
35
—
—
—
01
Not applicable. Do not change the default value.
45
—
—
—
02
Not applicable. Do not change the default value.
1
—
—
—
03
Not applicable. Do not change the default value.
70
—
—
—
04
Not applicable. Do not change the default value.
70
—
—
—
C
Leaving water temperature limits
00
Set point: heating leaving water maximum
temperature.
113 (45)
99~113
(37~45)
1.8 (1)
°F (°C)
01
Set point: heating leaving water minimum
temperature.
77 (25)
77~99
(25~37)
1.8 (1)
°F (°C)
02
Set point: cooling leaving water maximum
temperature.
68 (20)
64~72
(18~22)
1.8 (1)
°F (°C)
03
Set point: cooling leaving water minimum
temperature.
50 (10)
41~64
(5~18)
1.8 (1)
°F (°C)
04
Not applicable. Do not change the default value.
0
—
—
—
d
Settings are not applicable
E
Service mode
00
Not applicable. Do not change the default value.
0
—
—
—
01
Not applicable. Do not change the default value.
0
—
—
—
02
Not applicable. Do not change the default value.
0
—
—
—
03
Not applicable. Do not change the default value.
1
—
—
—
04
Pump only operation.
0
0~25
1
—
F
Settings are not applicable
00
Pump target ΔT (cooling).
9 (5)
5.4~14.4
(3~8)
1.8 (1)
°F (°C)
01
Not applicable. Do not change the default value.
0
—
—
—
02
Not applicable. Do not change the default value.
1
—
—
—
03
Not applicable. Do not change the default value.
10
—
—
—
04
Not applicable. Do not change the default value.
50
—
—
—
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range
Step
Unit
Date
Value
Date
Value
TEMPERATURE CONVERSION TABLE
°C
°F
°C
°F
°C
°F
5
41
19
66.2
33
91.4
6
42.8
20
68
34
93.2
7
44.6
21
69.8
35
95
8
46.4
22
71.6
36
96.8
9
48.2
23
73.4
37
98.6
10
50
24
75.2
38
100.4
11
51.8
25
77
39
102.2
12
53.6
26
78.8
40
104
13
55.4
27
80.6
41
105.8
14
57.2
28
82.4
42
107.6
15
59
29
84.2
43
109.4
16
60.8
30
86
44
111.2
17
62.6
31
87.8
45
113
18
64.4
32
89.6