Installation and operation manual
22
HXY48TAVJU
VRV System indoor unit
3P616151-1A – 2021.12
8.4.
Field setting list for Installation Manual
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range
Step
Unit
Date
Value
Date
Value
0
Remote control setup
00
User permission level.
2
2~3
1
—
01
Room temperature compensation value.
32 (0)
23~41 (–5~5)
0.9 (0.5)
°F (°C)
02
Not applicable. Do not change the default value.
1
—
—
—
03
Status: space heating schedule timer mode
Method 1=1 / Method 2=0.
1 (ON)
0/1
—
—
04
Status: space cooling schedule timer mode
Method 1=1 / Method 2=0.
1 (ON)
0/1
—
—
1
Settings are not applicable
00
Not applicable. Do not change the default value.
1
—
—
—
01
Not applicable. Do not change the default value.
1:00
—
—
—
02
Not applicable. Do not change the default value.
0
—
—
—
03
Not applicable. Do not change the default value.
15:00
—
—
—
2
Automatic setback function
00
Status: setback operation.
1 (ON)
0/1
—
—
01
Setback operation start time.
23:00
0:00~23:00
1:00
hour
02
Setback operation stop time.
5:00
0:00~23:00
1:00
hour
3
Weather dependent set point
00
Low ambient temperature (Lo_A).
14 (–10)
–4~41 (–20~5)
1.8 (1)
°F (°C)
01
High ambient temperature (Hi_A).
59 (15)
50~68 (10~20)
1.8 (1)
°F (°C)
02
Set point at low ambient temperature (Lo_Ti).
104 (40)
77~176 (25~80)
1.8 (1)
°F (°C)
03
Set point at high ambient temperature (Hi_Ti).
77 (25)
77~176 (25~80)
1.8 (1)
°F (°C)
4
Settings are not applicable
5
Automatic setback and disinfection set point
00
Not applicable. Do not change the default value.
70
—
—
—
01
Not applicable. Do not change the default value.
10
—
—
—
02
Leaving water setback temperature.
41 (5)
32~50 (0~10)
1.8 (1)
°F (°C)
03
Room setback temperature.
64 (18)
63~73 (17~23)
1.8 (1)
°F (°C)
04
Not applicable. Do not change the default value.
0
—
—
—
6
Option setup
01
External room thermostat installed.
0 (OFF)
0/2
—
—
02
Not applicable. Do not change the default value.
0
—
—
—
8
Option setup
00
User interface temperature control.
0 (OFF)
0/1
—
—
01
Not applicable. Do not change the default value.
1
—
—
—
02
Emergency operation.
0
0/1
—
—
03
Not applicable. Do not change the default value.
1
—
—
—
04
Status: freeze-up prevention.
0
0~2
1
—
9
Automatic temperature compensation
00
Leaving water temperature compensation value
(heating).
0
–3.6~3.6 (–2~2)
0.36 (0.2)
°F (°C)
01
Leaving water thermistor auto corrective function.
1 (ON)
0/1
1
—
02
Not applicable. Do not change the default value.
0
—
—
—
03
Leaving water temperature compensation value
(cooling).
0
–3.6~3.6 (–2~2)
0.36 (0.2)
°F (°C)
04
Not applicable. Do not change the default value.
0
—
—
—
01_EN_3P616151-1A.fm 22 ページ 2021年12月14日 火曜日 午後1時29分