The direction this product directs air can be selected. However, a separately sold sealing material
kit is needed in order to make the unit direct air in two, three, or four (corner shut-off) directions.
(1) Select an installation location with the customer’s approval which matches the following
conditions:
• Cool (or warm) air reaches.
•
No objects block the air passage.
•
Drainage can be done with no problem.
•
Sturdy enough to support the weight of the indoor unit.
• The wall is not significantly tilted.
•
Enough room for installation and service work.
• No risk of flammable gas leaking.
• The length of the indoor-outdoor piping is no longer than the tolerated length (see the installation
manual that came with the outdoor unit for details).
[Space required for installation] (in.)
60
100
>
60
>
*
60
>
*
>
Air
outlet
Air
outlet
Air
inlet
F
or installation in
high places
H
60
>
*
60
>
*
60
>
*
60
>
*
Fig. 1
Fig. 2
NOTE
•
Leave 8 in. or more space where marked with the *, on sides where the air outlet is closed.
Model
H
FXZQ07·09·12·15·18MVJU9
11-1/4(Confirm the space of 11-5/8 or more)
CAUTION
•
The indoor and outdoor units and the power supply wiring and remote controller wiring must be
installed at least 40 in. away from any televisions or radios. This is to prevent interference with picture
and sound reception. (Interference may occur even at 40 in. away depending on the reception quality.)
•
If installing the wireless kit, the distance of the signal sent from the remote controller might be shorter if
there are fluorescent lights which are electrically started (such as with inverters, rapid starters, etc.) in
the room. The indoor unit should be installed as far away from fluorescent lights as possible.
(2) Ceiling height
•
Install this unit where the height of bottom panel is more than 100 in. so that the user cannot easily
touch it.
(3) Air direction
The air direction shown is an example.
Select the appropriate number of directions according to the shape of the room and the location of
the unit. Field settings have to be made using the remote controller and the outlet vents have to be
shut off if two, three, or four (corner shut-off) directions are selected. See the sealing materials (sold
separately) installation manual for details.