21
3P184443-12N
English
CAUTION
• When clamping wiring, use the included clamping material to prevent outside pressure being exerted
on the wiring connections and clamp firmly. When doing the wiring, make sure the wiring is neat and
does not cause the control box cover to stick up, then close the cover firmly.
• When attaching the control box cover, make sure you do not pinch any wires.
• After all the wiring connections are done, fill in any gaps in the through holes with putty or insulation
(procured locally) to prevent small animals and insects from entering the unit from outside, as they
could cause short circuits in the control box.
• Outside the unit, separate the low voltage wiring (remote controller wiring and wiring between units)
and high voltage wiring (ground and other power wiring) at least 2 in. so that they do not pass through
the same place together. Proximity may cause electrical interference, malfunctions, and breakage.
9-2 WIRING EXAMPLE
•
Fit the power supply wiring of each unit with a switch and breaker/fuse as shown in the drawing.
COMPLETE SYSTEM EXAMPLE
Power supply
Indoor unit
Remote controller
BS unit
(Only for Heat
recovery system)
Main
switch
Switch
Breaker/Fuse
Power supply wiring
Transmission and remote controller wiring
Outdoor unit
Fig. 28
1. When using 1 remote controller for 1 indoor unit. (Normal operation)
L1 L2
P
1
P
2
L
1
L
2
P
1
P
2
F
1
F
2
T
1
T
2
P
1
P
2
F
1
F
2
T
1
T
2
P
1
P
2
P
1
P
2
P
1
P
2
P
1
P
2
F
1
F
2
T
1
T
2
P
1
P
2
F
1
F
2
T
1
T
2
L1 L2
L1 L2
L1 L2
L
1
L
2
L
1
L
2
L
1
L
2
F1 F2 F1 F2
IN/D OUT/D
Power supply
208/230V
1 ~ 60Hz
Power supply
208/230V
1 ~ 60Hz
No. 1
System
Indoor
unit A
Indoor
unit B
Indoor
unit C
Most
downstream
Indoor unit
Power supply
208/230V
1 ~ 60Hz
Power supply
208/230V
1 ~ 60Hz
Outdoor unit
Control box
Fig. 29
Содержание VRV FXZQ07MVJU9