The lengths of remote controller wiring and transmission
wirings are as follows:
(1) Remote controller wiring
(indoor unit - remote controller) ..................... Max. 500 m
(2) Transmission wirings ............. Total wiring length 2000 m
• Outdoor unit - Indoor unit... .......................... Max. 1000 m
• Outdoor unit - BS unit .................................. Max. 1000 m
• BS unit - Indoor unit... .................................. Max. 1000 m
• Indoor unit - Indoor unit ............................... Max. 1000 m
9-3. Electrical characteristics
Model
Power supply
Model
Hz
Voltage
Voltage
range
FXKQ32AV16
FXKQ40AV16
max.264V
FXKQ50AV16 50 220-240 min. 198V
FXKQ63AV16
MCA: Minimum circuit current (A)
MFA: Maximum fuse current (A)
KW: Fan motor rated output power (kW)
FLA: Full-load current (A)
1 O. Wiring example
IFM
MCA MFA
KW
0.4 16.0 0.061
0.5 16.0 0.061
0.7 16.0 0.061
0.8 16.0 0.061
10-1.How
to connect power wiring, earth wires,
remote controller wiring and transmission
wiring
FLA
0.3
0.4
0.5
0.6
(As shown in the figure below, connect the wires after opening
the electrical component box cover.)
For the field connection, open the right size (Square
Shape) service cover only. All the connection (Field and
Panel) are in this.
(2)Connect the electric wires into the electrical component
box through the inlet port on one side.
10
Strong current inlet port
Power wiring (strong current)
Earth wire (strong current)
Weak current inlet port
Transmission wiring (weak current)
Remote controller wiring (weak current)
-.&,
Caution----------------
• Outside the air conditioner, don't route the remote controller
wiring and transmission wiring together with other electrical
wiring. Keep the remote controller wiring and transmission
wiring at least 50mm away from the power wiring and other
electrical wiring. Otherwise, being affected by the electrical
interference (external noise) may result in malfunction and
breakdown.
• For installation and wiring of the remote controller, refer to
the "Remote controller installation manual" included with it.
• When connecting the power supply of the air conditioner,
refer to the "Wiring diagram" simultaneously.
• Correctly connect the remote controller wiring and
transmission wiring to their corresponding terminals.
(3}Connect the wires in the electrical component box as
shown in the figure below.
Field Earth
Wire
L N
J__J.,
Power supply Single phase
~220-240V 50Hz
Power wiring (strong current)
Earth wire (strong current)
Transmission wiring (weak current)
Remote controller wiring (weak current)
Transmission wiring
(no polarity)
Remote controller wirin
(no polarity)
Connecting method of remote controller terminal
• When using streakline, do not weld its front
end for connection.
-.&,
Warning--------------
When connecting the wires, lay them regularly and fasten
the electrical component box cover securely.
The wire being clamped and the electrical component box
cover being protruded may result in electric shocks or fire
hazards.
Содержание VRV FXKQ32AV16
Страница 14: ...13...