Field Setting from Outdoor Unit
SiUS342303E
185
Part 5 Field Settings and Test Operation
2.3 Operating the BS Buttons and DIP Switches on the PCB
Operating the BS
buttons
By operating the BS buttons it is possible to:
Perform special actions (test operation, etc.).
Perform field settings (demand operation, low noise, etc.).
Below procedure explains how to operate the BS buttons to reach the required mode in the menu,
select the correct setting and modify the value of the setting. This procedure can be used any time
special settings and regular field setting are discussed in this manual.
Setting definition: [A-B]
C
A: mode
B: setting
C: setting value
A, B and C are numerical values for field settings. Parameter C has to be defined. It can be a
chosen from a set (0, 1, 2, 3, 4, 5,…) or regarded as an ON/OFF (1 or 0) depending on the
contents. This is informed when the field setting is explained.
Initialization:
Default Situation
Turn ON the power supply of the outdoor unit and all indoor units.
When the communication between indoor units and outdoor unit(s) is established and normal, the
segment indication state will be as below (default situation when shipped from factory).
When turning ON the power supply, the display blinks ON and OFF. First checks of the power
supply are executed (1 - 2 minutes).
When no trouble occurs: lighted as indicated (8~10 minutes).
Ready for operation: blank display indication as indicated.
When above situation cannot be confirmed after 12 minutes, the error code can be checked on the
indoor unit user interface and the outdoor unit segment display. Solve the error code accordingly.
The communication wiring should be checked at first.
INFORMATION During special operation (e.g., test operation, etc.) or when an error
happened, information will contain letters and numerical values.
INFORMATION Be sure to turn the power on at least 6 hours before operation in
order to have power running to the crankcase heater.
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...