SiUS372201EB
Capacity Range
Part 1 General Information
20
4.3 Limitation of Capacity Index for Heat Recovery
Single Branch Selector Unit
Model
BSQ36TVJ
BSQ36TAVJ
BSQ60TVJ
BSQ60TAVJ
BSQ96TVJ
BSQ96TAVJ
Maximum number of
connectable indoor units
4
8
8
Total capacity index of
connectable indoor units
36 or less
More than 36 and 60 or less
More than 60 and 96 or less
Multi Branch Selector Unit (Standard Series)
Model
BS4Q54TVJ
BS4Q54TAVJ
BS6Q54TVJ
BS8Q54TVJ
BS10Q54TVJ
BS10Q54TAVJ
BS12Q54TVJ
BS12Q54TAVJ
Maximum number of
connectable indoor units per
branch
5
5
5
5
5
Number of branches
4
6
8
10
12
Maximum capacity index of
connectable indoor units
144 or less
216 or less
290 or less
290 or less
290 or less
Maximum capacity index of
connectable indoor units per
branch
1
54 or less
54 or less
54 or less
54 or less
54 or less
Multi Branch Selector Unit (Flex Series)
Model
BSF4Q54TVJ
BSF6Q54TVJ
BSF8Q54TVJ
Maximum number of connectable indoor units per branch
5
5
5
Number of branches
4
6
8
Maximum capacity index of connectable indoor units per branch
1
54 or less
54 or less
54 or less
Series configuration
Maximum capacity index of connectable indoor
units per branch selector unit
144 or less
162 or less
162 or less
Maximum capacity index of connectable indoor
units with branch selector units connected in
series
230 or less
230 or less
230 or less
Parallel configuration
Maximum capacity index of connectable indoor
units
144 or less
216 or less
290 or less
Notes:
1. When the total capacity index of indoor units to be connected downstream is larger than 54 (Max. 96), use
a joint kit (KHRP26A250T, optional parts) to join 2 branches downstream from the Branch Selector unit.
Suction gas piping
Liquid piping
Indoor unit
(Heating)
Indoor unit
(Cooling)
Indoor unit
(Cooling only)
Heat Recovery operation!
Branch
Selector
unit
Branch
Selector
unit
Heat Recovery
Outdoor unit
High and low pressure
gas piping
For indoor units used for cooling only (do not connect to Branch Selector unit when using for Heat Recovery),
total capacity index must be 50% or less than the capacity index of the outdoor units.
Содержание VRV EMERION REYQ-AATJA
Страница 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA B 208 230 V REYQ AAYDA B 460 V SiUS372201EB...
Страница 458: ...Check SiUS372201EB 451 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 457 CHECK 8 Refer to page 458...
Страница 490: ...Wiring Diagrams SiUS372201EB 483 Part 7 Appendix 1 2 2 Multi Branch Selector Unit Standard Series BS4Q54TVJ 3D089123B...
Страница 492: ...Wiring Diagrams SiUS372201EB 485 Part 7 Appendix BS6 8Q54TVJ 2D089122B...
Страница 493: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 486 BS10 12Q54TVJ 2D089121B...
Страница 499: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 492 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 500: ...Wiring Diagrams SiUS372201EB 493 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 501: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 494 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 505: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 498 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 506: ...Wiring Diagrams SiUS372201EB 499 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 507: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 500 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 509: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 502 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 513: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 506 FXHQ12 24 36MVJU 3D048116C...
Страница 514: ...Wiring Diagrams SiUS372201EB 507 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 521: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 514 VAM1200GVJU 3D073270D...