36
English
Type
Description
Actions
Field
setting
Shorted
between
Heating Thermo-on
Heating Thermo-off
Aux heater Indoor fan Aux heater Indoor fan
I
--
Heat-pump heating is always
locked out
2-16 = ON
--
ON
ON
(H/L)
OFF
LL
II
Mode 1
Lockout is controlled by ABC
terminals
2-37 =
Mode 1
A-C
ON
ON
(H/L)
OFF
LL
B-C
OFF
Mode 2
(for a heater which
doesn’t need airflow)
2-37 =
Mode 2
A-C
LL
LL
B-C
OFF
OFF
Mode 3
Lockout is controlled by the
outdoor ambient temperature and
setpoint which is configured by
the field setting 2-78 and 2-79
2-37 =
Mode 3
Same as 2-37 = Mode 1 & A-C shorted
Mode 4
2-37 =
Mode 4
Same as 2-37 = Mode 1 & B-C shorted
Mode 5
2-37 =
Mode 5
Same as 2-37 = Mode 2 & A-C shorted
Mode 6
2-37 =
Mode 6
Same as 2-37 = Mode 2 & B-C shorted
[2-78]= Heat pump lockout temp
Heat pump would be locked out when the outdoor ambient
temp is smaller than the Heat Pump Lockout Temp below –
this setting is only affective when heat pump lockout mode
has been set. Unit will switch to heat pump lock out.
Heat Pump
Lockout Temp
Fahrenheit
Celsius
0
− 15 (default)
− 26.1 (default)
1
− 10
− 23.3
2
− 5
− 20.5
3
0
− 17.7
4
5
− 15
5
10
− 12.2
6
15
− 9.4
7
20
− 6.6
8
25
− 3.8
9
30
− 1.1
10
35
1.6
11
40
4.4
12
45
7.2
13
50
10
14
Forced Heat pump Lock out
[2-79]= Heat pump lockout release differential
Heat pump would be resumed when the outdoor ambient
temp is recovered by differential (below) above the Heat
Pump Lockout Temp.
Heat Pump Lockout
Release differential
Fahrenheit
Celsius
0
5
2.8°C
1
10 (default)
5.6°C (default)
2
15
8.3°C
When HP lockout mode has been set the auto backup func-
tion will automatically be set. This will allow the auxiliary or
secondary heat source to be automatically energized in the
event of a system failure.
Error codes capable of auto backup are listed in the table below.
Please be aware that the error codes that are not listed do
not auto backup in order to protect the unit.
Error contents
Error code
(Auto backup
possible)
Actuation of high pressure switch
E3
Actuation of low pressure sensor
E4
Inv. compressor motor lock
E5
Compressor damage alarm
E6
Outdoor unit fan motor abnormality
E7
Electronic expansion valve coil abnormality
E9
Position signal abnormality of outdoor unit fan
motor
H3
H7
Outdoor air thermistor (R1T) abnormality
H9
Discharge pipe temperature abnormality
F3
Wet alarm
F4
Discharge pipe thermistor (R21T, R22T) and compres-
sor surface temperature thermistor (R14T) abnormality
J3
Accumulator inlet thermistor (R10T) abnormality
J5
Heat exchanging deicer thermistor (R11T) and heat
exchanger gas pipe thermistor (R8T,R9T) abnormality
J6
Receiver inlet thermistor (R3T) and sub cooling heat
exchanger liquid pipe thermistor (R7T) abnormality
J7
Heat exchanger liquid pipe thermistor (R15T, R4T,
R5T) abnormality
J8
Subcooling heat exchanger gas pipe thermistor (R6T)
and receiver gas purge thermistor (R13T) abnormality
J9
High pressure sensor abnormality
JA
Low pressure sensor abnormality
JC
Inverter PCB abnormality
L1
Reactor temperature rise abnormality
L3
Inverter radiation fin temperature rise abnormality
L4
Inv. compressor instantaneous overcurrent
L5
Inv. compressor overcurrent
L8
Inv. compressor startup abnormality
L9
Transmission error between inverter and control PCB
LC
01_EN_3P477778-3C.indb 36
2/8/2018 14:31:40