8 Configuration
Installer and user reference guide
24
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1 – 2017.08
8.2
List of settings
Setting
mode
Setting
switch
no.
Setting
description
Setting position no.
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
17(27)
0
Filter cleaning
time setting
Approx.
2500
hours
±1250
hours
—
—
—
—
—
—
—
—
—
—
—
—
—
1
Nighttime free
cooling timer
(after stop)
Off
On after
2 hours
On after
4 hours
On after
6 hours
On after
8 hours
—
—
—
—
—
—
—
—
—
—
2
Pre-cool/pre-
heat
Off
On
—
—
—
—
—
—
—
—
—
—
—
—
—
3
Pre-cool/pre-
heat duration
30
minutes
45
minutes
60
minutes
—
—
—
—
—
—
—
—
—
—
—
—
4
Initial fan
speed
High
Ultra-
high
—
—
—
—
—
—
—
—
—
—
—
—
—
5
Yes/No setting
for duct
connection
with VRV
system
Without
duct
With duct
Without duct
With duct
—
—
—
—
—
—
—
—
—
Setting for cold
areas (fan
operation
when heater
thermostat is
off)
—
—
Stop
Low
Stop
Low
—
—
—
—
—
—
—
—
—
17(27)
6
Nighttime free
cooling (fan
settings)
High
Ultra-
high
—
—
—
—
—
—
—
—
—
—
—
—
—
7
Target
temperature
for
independent
nighttime free
cooling
18°C
19°C
20°C
21°C
22°C
23°C
24°C
25°C
26°C
27°C
28°C
29°C
30°C
—
—
8
Centralised
zone interlock
setting
No
Yes
—
—
—
—
—
—
—
—
—
—
—
—
—
9
Pre-heat time
extension
setting
0
minutes
30
minutes
60
minutes
90
minutes
—
—
—
—
—
—
—
—
—
—
—