1. Supplementary Explanation
1.1
Field Setting, Service Mode Operation
1.1.1
Field Setting
Initial setting (mode
Nos. 17, 27, 18, 28)
4
3
6
1, 7
5
2
Unit No.
Mode No.
Setting position No.
Field setting mode
Setting switch No.
(HL039)
Step 1
With equipment in normal mode, press the
button for more than 4 seconds to enter field
setting mode.
Step 2
Mode No.: UP
↔
Mode No.: DOWN
Use [MODE] and [AIR VOLUME] to select desired mode No.
Step 3
To setting heat reclaim ventilation units by group, press
button and select desired unit
No.
Step 4
Press
button to select desired setting switch No.
Step 5
Press
button to select desired setting position No.
Step 6
Press
button to enter settings.
Step 7
Press
button to return to normal mode.
Содержание VAM 500EJ
Страница 1: ...Heat Recovery Ventilation Applied Models VAM 500EJ VAM 800EJ VAM1000EJ VAM2000EJ SiE 93 Service Manual...
Страница 5: ...Si 93 iv Table of Contents...
Страница 7: ...Introduction Si 93 vi 1 1 1 Cautions in Repair Warning...
Страница 8: ...Si 93 Introduction vii...
Страница 10: ...Si 93 General Constructions 1 Part 1 General Constructions 1 General Constructions 3 1 1 Explanation 3...
Страница 11: ...Si 93 2 General Constructions...
Страница 15: ...Si 93 6 Operation...
Страница 21: ...Si 93 12 Maintenance...
Страница 27: ...Si 93 18 Control Functions...
Страница 35: ...Si 93 26 Circuit Operations...
Страница 39: ...Si 93 30 Troubleshooting...
Страница 59: ...Troubleshooting Si 93 50 Troubleshooting...
Страница 61: ...Si 93 52 Supplementary Explanation...
Страница 72: ...Si 93 Appendix 63 Part 8 Appendix 1 Appendix 65 1 1 Wiring Diagram 65...
Страница 73: ...Si 93 64 Appendix...
Страница 74: ...Si 93 Appendix Appendix 65 1 Appendix 1 1 Wiring Diagram VAM500EJVE VAM800EJVE VAM1000EJVE...
Страница 75: ...Appendix Si 93 66 Appendix VAM2000EJVE...
Страница 79: ...Si 93 iv Index...
Страница 81: ...Si 93 vi Drawings Flow Charts When no indication is displayed on remote controller 45 Wiring Diagram 65...