Daikin UDH Скачать руководство пользователя страница 8

IM 907 / Page 8 of 4

Installation

Piping

1. Branch piping to and from unit heater should be the

same size as unit connections and include swing

joints to allow for expansion and contraction of the

piping without placing a strain on the unit heater

element. On steam systems, the branch piping should

be taken off and returned above the center line of the

supply and return line.

2. Install pipe unions and shut-off valves in lines to

and from each unit heater to allow maintenance or

replacement of unit without shutting down and drain-

ing entire system. For hot water systems, include

a balancing valve in return line when possible for

water flow regulation. In areas subject to freezing,

a drain valve should be installed below each unit

heater to remove water from the heating coil.

3. In steam or hot water systems, rapid air removal is

required because entrained air is a cause of corro-

sion. Hot water systems should be equipped with

suitable air vent valves for rapid and complete

removal of air at the high points and ends of both

supply and return mains. Proper air venting for steam

systems can be achieved by use of a steam trap with

an internal air vent.

4. Traps must be located below the outlet of the unit.

Consult trap manufacturer for specific recommenda

-

tions. Each steam unit heater should be provided

with a trap of sufficient size and capacity to pass

a minimum of two times the normal condensate

released by the unit at the minimum differential

pressure in the system. Trap capacity is based on

the pressure differential between supply and return

mains. Steam systems should be equipped with a

float and thermostatic trap or an inverted bucket trap

with an air bypass.

5. It is advisable to use a pipe line strainer before each

steam trap draining a unit heater. This protection

will reduce the maintenance of the steam trap. When

strainers are used they could be installed between

the unit heater and the trap and be the same size as

the trap tapping. In order to catch dirt and scale, the

strainer should have a screen perforation size smaller

than the trap orifices.

6. On systems where the steam supply to the unit heater

is modulated or controlled by a motorized valve, a

vacuum breaker should be installed between the unit

outlet and the trap. If a vacuum breaker is used, it

should be in conjunction with a float and a

thermostatic trap.

7. Install a dirt pocket at the bottom of unit heater to

collect dirt and scale as shown in figures on page 7.

Pipe diameter must be the same size as unit

connections and about six inches long.

8. Provide adequate pipe hangers, supports, or anchors

to secure the piping system independently of the unit

heater.

Wiring Instructions

All wiring must be done in accordance with the National 

Electric Code and applicable local codes. In Canada, wir-

ing must conform to the Canadian Electric Code. Power 

supply to these unit heaters must be protected by a fused 

disconnect switch. It is recommended that all wiring be 

adequately grounded.

Electric wiring must be sized to carry the full load amp 

draw of the motor, starter, and any control that are used 

with the heater. All units with power codes B, I or L 

(polyphase motors) must be provided with suitable over-

current protection in circuit supplying heater at instal-

lation. Overcurrent protectors should be sized based on 

motor current rating shown on the unit serial plate, and 

applicable national electric code procedures.

All units are provided with an electrical junction box. 

Junction boxes are either integral to the motor or at-

tached to the unit casing. Units with explosion-proof 

motors have an explosion proof junction box attached to 

the motor. 

Any damage to or failure of units caused by incor-

rect wiring of the units is not covered by standard 

warranty. See page 22.

Location of room thermostat should be in the natural 

circulating path of room air. Mount thermostat about five 

feet above floor level where it will not be affected by 

heat from the unit or other sources of drafts that would 

prevent it from properly controlling room temperature. 

See instructions packed with the thermostat. Speed con-

trollers furnished with specified unit heater fan motors 

are packed separately and must be connected according 

to wiring diagram with each controller. Controllers are 

not interchangeable with different motor sizes or manu-

facturers and must be specifically wired to their respec

-

tive motors.

DANGER

Disconnect all electric power including remote 

disconnects before servicing. Failure to  

disconnect power before servicing can cause  

severe personal injury or death.

Содержание UDH

Страница 1: ...ance Data IM 907 Group Fan Coil Part Number 668709201 Date January 2008 Steam Hot Water Unit Heaters Installation Instructions for Horizontal Air Delivery Model UHH and Vertical Air Delivery Model UDH...

Страница 2: ...ice for standard horizontal and vertical air flow units Unit heaters should be installed following directions in this manual for proper performance and application to terms and conditions of manufactu...

Страница 3: ...sult in personal injury or WARNING The installer must determine and follow all applicable codes and regulations This equipment presents hazards of electricity rotating parts sharp edges heat and weigh...

Страница 4: ...uld generally be located in the central area of the space to be heated Place horizontal delivery units along the walls of the same building where heat loss is usually greatest See Figure 2 7 When only...

Страница 5: ...4 46 UHH 108 UHH 121 UHH 165 UHH 193 UHH 258 UHH 290 UHH 340 Height Ft Spread Ft Model Size To determine how non standard steam pressures other than 2 lb affect mounting height Maximum Mounting Height...

Страница 6: ...k dimensions Horizontal Delivery Units Model UHH Series All horizontal delivery units have two tapped holes 3 8 16 in the top for unit suspension Piping support hangers or clamps are recommended and s...

Страница 7: ...Pressure Steam Steam Systems UHH 108 through 340 Horizontal Unit Heater Top Bottom Connection for High Pressure Steam Horizontal Unit Heater Top Bottom Connection for Low Pressure Steam Open Gravity...

Страница 8: ...e a vacuum breaker should be installed between the unit outlet and the trap If a vacuum breaker is used it should be in conjunction with a float and a thermostatic trap 7 Install a dirt pocket at the...

Страница 9: ...ttent Fan Operation Intermittent Hot Cold Coil To prevent a unit heater from deliver ing cold air when the thermostat is calling for heat an aquastat prevents fan operation when the heat supply to the...

Страница 10: ...for operations in areas containing flour starch or grain dust Class III motors are for operations in areas containing easily ignitable fibers and flyings N A N A N A N A 1 4 0 7 1 4 0 7 2 2 1 1 2 2 1...

Страница 11: ...AIR DELIVERY Model Type UHH 1550 1550 1550 1550 1550 1550 1075 1075 1075 1075 1075 1100 1100 Notes 1 Performance Data at Standard Conditions of 2 lb Steam and 60 F Entering Air Units with horizontal...

Страница 12: ...0 17 300 24 500 33 800 46 500 61 900 81 000 90 000 133 000 156 000 198 000 224 000 273 000 1 3 1 7 2 5 3 4 4 7 6 2 8 1 9 0 13 3 15 6 19 8 22 4 27 3 0 49 0 83 0 12 0 21 0 47 0 79 0 85 1 04 2 48 3 35 3...

Страница 13: ...data is for units without deflectors Please see Catalog 702 for additional outlet accessory performance data See Table 12 on page 14 for Sound Class definitions 11 15 16 17 19 21 24 25 27 31 30 33 40...

Страница 14: ...tores Tea Rooms Upper Floors at Department Stores II Bank Lobbies Cafeterias Drug Stores General Offices Grocery Stores Gymnasiums Main Floors at Department Stores Public Buildings III Post Offices Re...

Страница 15: ...HH 258 UHH 290 UHH 340 15 15 19 19 19 19 27 27 27 27 33 33 39 16 7 8 16 7 8 19 3 4 19 3 4 25 3 4 25 3 4 25 7 8 25 7 8 31 7 8 31 7 8 40 13 16 40 13 16 40 13 16 7 1 2 7 1 2 7 1 2 7 1 2 8 1 2 8 1 2 9 1 2...

Страница 16: ...75 23 75 26 875 32 875 41 8125 41 8125 Table 14 Dimensions Model UHX UNIT SIZE A B C D E F G H I 21 5 21 5 22 675 23 465 24 646 26 615 28 189 0 67 0 67 0 67 0 67 0 67 0 67 0 67 8 47 10 484 10 484 14 5...

Страница 17: ...4 Table 15 Dimensions Model UDH UNIT SIZE A B C D E F G MALE NPT CONNECTIONS FAN DIAMETER APPROX SHIPPING WT LB UDH 42 59 UDH 78 95 UDH 139 161 UDH 193 212 UDH 247 279 UDH 333 385 UDH 510 UDH 610 6 3...

Страница 18: ...l UDX UNIT SIZE A B C D E F G H 6 375 6 375 6 375 6 375 10 375 10 375 12 375 12 375 12 375 12 375 3 125 3 125 3 125 3 125 3 125 3 125 4 4 4 4 15 15 17 17 18 875 18 875 20 875 20 875 22 875 22 875 2 75...

Страница 19: ...umulation on fan blades 4 Fan hub or blade rivets loose 5 Motor shaft thrust bearing worn 6 Motor mounting bent fan not positioned properly in venturi 7 Unit mounted too rigidly transmits vibration no...

Страница 20: ...gh pressure air hose to loosen dirt by blowing from side where air leaves coil side adjacent to louvers on blow through units side adjacent to fan on draw through units For thorough cleaning of coil r...

Страница 21: ...______________________________ Serial Number ____________________________________________________________________________ Power Code ___________________________________________________________________...

Страница 22: ...on of parts or con trols not approved by the factory will be at customer s risk Note Daikin reserves the right to substitute parts of advanced design and to change specifications or prices without adv...

Страница 23: ......

Страница 24: ...our local Daikin Representative for warranty details Refer to Form 933 43285Y To find your local Daikin Representative go to www DaikinApplied com This document contains the most current product infor...

Отзывы: