Daikin UDH Скачать руководство пользователя страница 20

IM 907 / Page 0 of 4

Maintenance

Inspect Regularly

Under average conditions, it is recommended that unit 

heaters be inspected before every heating season - more 

often in locations where air is contaminated with cor-

rosive fumes, dust, soot or oil spray. Check for dirty, 

clogged coils, excessive vibration and loose connections.

Motors

A. Cleaning

Remove grease and dirt on motor during each

inspection or lubrication. Open frame motors should

be blown clean every heating season, or whenever

coils are cleaned, whichever is sooner.

B. Lubrication

1. Lubricate motor according to manufacturer’s

instructions located on the motor.

2. When no motor oiling instructions are on the

motor, oil the motor every two thousand hours

of operation with SAE20 motor oil for units in

normal applications. Adjust oiling according to

usage and atmosphere.

3. Some motors do not have oil fittings. These

motors are lubricated for long life and do not

require further lubrication.

C. Overload Protection

A change in line voltage higher or lower than motor

nameplate rating may cause overheating and serious

motor damage. Check plant voltage conditions. A

separate manual starter with thermal overload

protection device is recommended for those units

that do not have motors with built-in overload

protection.

Coils

A. Cleaning

Clean coil at least once a year; more often under

unfavorable conditions. Unless coil is kept reason-

ably free of dirt, lint and grease, its original heat-

ing capacity will be reduced - possibly to a serious

degree - and motor damage may result.

Two commonly used cleaning methods are:

1. Loosen dirt by brushing fins on side where air

enters coil and then turn on fan to blow dirt from

unit.

2. Use high pressure air hose to loosen dirt by

blowing from side where air leaves coil (side

adjacent to louvers on blow-through units; side

adjacent to fan on draw-through units).

For thorough cleaning of coil, remove motor and 

fan and spray a mild alkaline cleaning solution    

over the coil.

After a few minutes, follow by a hot water rinse.  

(A steam gun can be used for spraying cleaning    

solution and hot water.)

Coils subjected to corrosive fumes should be    

checked and cleaned frequently.

B. Internal Corrosion Safeguards

1. Provide controlled water treatment - don’t use

excess of boiler compounds. Contact your boiler

compound supplier for proper usage or the

services of a water treatment laboratory.

2. Periodic internal flushing of the coils is

recommended in areas where water supply is

suspected of causing scale. Use an alka-  

 

 

 

line-cleaning solution and introduce it at 

the main pump of the hydronic system. 

Flush thoroughly.

3. De-aerate boiler feed-water (particularly if large

amount of new water is used).

4. Insure rapid continuous and adequate condensate

drainage by properly sized and installed traps

and piping. Check traps for sticking.

Clean strainers ahead of traps. (When traps don’t

work, condensate accumulates in unit heater coil;

water hammer results.)

5. Adequately vent each unit.

6. Use low pressure steam when possible.

Casings

A. Cleaning

Periodic cleaning of casings is recommended to

remove dirt, grease and corrosive substances that

may injure finish. Rusted or corroded spots should be

cleaned and repainted.

B. General Inspection

Tighten fan guard and motor bracket. Check fan for

proper clearance, free rotation and firm connection to

shaft. When servicing is complete, tag unit to

indicate date of inspection, lubrication and cleaning.

WARNING

Using inorganic or mineral acids such as muriatic 

(hydrochloric) acid, even though inhibited, may lead to 

severe damage including corrosion and leakage

Содержание UDH

Страница 1: ...ance Data IM 907 Group Fan Coil Part Number 668709201 Date January 2008 Steam Hot Water Unit Heaters Installation Instructions for Horizontal Air Delivery Model UHH and Vertical Air Delivery Model UDH...

Страница 2: ...ice for standard horizontal and vertical air flow units Unit heaters should be installed following directions in this manual for proper performance and application to terms and conditions of manufactu...

Страница 3: ...sult in personal injury or WARNING The installer must determine and follow all applicable codes and regulations This equipment presents hazards of electricity rotating parts sharp edges heat and weigh...

Страница 4: ...uld generally be located in the central area of the space to be heated Place horizontal delivery units along the walls of the same building where heat loss is usually greatest See Figure 2 7 When only...

Страница 5: ...4 46 UHH 108 UHH 121 UHH 165 UHH 193 UHH 258 UHH 290 UHH 340 Height Ft Spread Ft Model Size To determine how non standard steam pressures other than 2 lb affect mounting height Maximum Mounting Height...

Страница 6: ...k dimensions Horizontal Delivery Units Model UHH Series All horizontal delivery units have two tapped holes 3 8 16 in the top for unit suspension Piping support hangers or clamps are recommended and s...

Страница 7: ...Pressure Steam Steam Systems UHH 108 through 340 Horizontal Unit Heater Top Bottom Connection for High Pressure Steam Horizontal Unit Heater Top Bottom Connection for Low Pressure Steam Open Gravity...

Страница 8: ...e a vacuum breaker should be installed between the unit outlet and the trap If a vacuum breaker is used it should be in conjunction with a float and a thermostatic trap 7 Install a dirt pocket at the...

Страница 9: ...ttent Fan Operation Intermittent Hot Cold Coil To prevent a unit heater from deliver ing cold air when the thermostat is calling for heat an aquastat prevents fan operation when the heat supply to the...

Страница 10: ...for operations in areas containing flour starch or grain dust Class III motors are for operations in areas containing easily ignitable fibers and flyings N A N A N A N A 1 4 0 7 1 4 0 7 2 2 1 1 2 2 1...

Страница 11: ...AIR DELIVERY Model Type UHH 1550 1550 1550 1550 1550 1550 1075 1075 1075 1075 1075 1100 1100 Notes 1 Performance Data at Standard Conditions of 2 lb Steam and 60 F Entering Air Units with horizontal...

Страница 12: ...0 17 300 24 500 33 800 46 500 61 900 81 000 90 000 133 000 156 000 198 000 224 000 273 000 1 3 1 7 2 5 3 4 4 7 6 2 8 1 9 0 13 3 15 6 19 8 22 4 27 3 0 49 0 83 0 12 0 21 0 47 0 79 0 85 1 04 2 48 3 35 3...

Страница 13: ...data is for units without deflectors Please see Catalog 702 for additional outlet accessory performance data See Table 12 on page 14 for Sound Class definitions 11 15 16 17 19 21 24 25 27 31 30 33 40...

Страница 14: ...tores Tea Rooms Upper Floors at Department Stores II Bank Lobbies Cafeterias Drug Stores General Offices Grocery Stores Gymnasiums Main Floors at Department Stores Public Buildings III Post Offices Re...

Страница 15: ...HH 258 UHH 290 UHH 340 15 15 19 19 19 19 27 27 27 27 33 33 39 16 7 8 16 7 8 19 3 4 19 3 4 25 3 4 25 3 4 25 7 8 25 7 8 31 7 8 31 7 8 40 13 16 40 13 16 40 13 16 7 1 2 7 1 2 7 1 2 7 1 2 8 1 2 8 1 2 9 1 2...

Страница 16: ...75 23 75 26 875 32 875 41 8125 41 8125 Table 14 Dimensions Model UHX UNIT SIZE A B C D E F G H I 21 5 21 5 22 675 23 465 24 646 26 615 28 189 0 67 0 67 0 67 0 67 0 67 0 67 0 67 8 47 10 484 10 484 14 5...

Страница 17: ...4 Table 15 Dimensions Model UDH UNIT SIZE A B C D E F G MALE NPT CONNECTIONS FAN DIAMETER APPROX SHIPPING WT LB UDH 42 59 UDH 78 95 UDH 139 161 UDH 193 212 UDH 247 279 UDH 333 385 UDH 510 UDH 610 6 3...

Страница 18: ...l UDX UNIT SIZE A B C D E F G H 6 375 6 375 6 375 6 375 10 375 10 375 12 375 12 375 12 375 12 375 3 125 3 125 3 125 3 125 3 125 3 125 4 4 4 4 15 15 17 17 18 875 18 875 20 875 20 875 22 875 22 875 2 75...

Страница 19: ...umulation on fan blades 4 Fan hub or blade rivets loose 5 Motor shaft thrust bearing worn 6 Motor mounting bent fan not positioned properly in venturi 7 Unit mounted too rigidly transmits vibration no...

Страница 20: ...gh pressure air hose to loosen dirt by blowing from side where air leaves coil side adjacent to louvers on blow through units side adjacent to fan on draw through units For thorough cleaning of coil r...

Страница 21: ...______________________________ Serial Number ____________________________________________________________________________ Power Code ___________________________________________________________________...

Страница 22: ...on of parts or con trols not approved by the factory will be at customer s risk Note Daikin reserves the right to substitute parts of advanced design and to change specifications or prices without adv...

Страница 23: ......

Страница 24: ...our local Daikin Representative for warranty details Refer to Form 933 43285Y To find your local Daikin Representative go to www DaikinApplied com This document contains the most current product infor...

Отзывы: