![Daikin UATN60CGXY1 Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/daikin/uatn60cgxy1/uatn60cgxy1_technical-manual_4705873016.webp)
12
Sound Data
Sound Power Level
Model
1/1 Octave Sound Power Level (dB) ref 1pW
Overall
(dBA)
125Hz
250Hz
500Hz
1kHz
2kHz
4kHz
8kHz
UATN60C
86
81
77
78
70
69
66
81
UATN90C
87
80
77
80
73
74
69
83
UATN120C
87
84
78
79
73
72
68
83
UATN150C
91
83
80
82
74
72
69
85
UATN180C
94
86
82
84
76
76
71
87
UATN210C
89
87
84
86
79
75
69
89
UATN240C
89
87
85
86
80
76
70
89
UATN300C
89
88
86
87
86
83
77
92
Measuring Location
Microphone position:
(1) Measurement at open field (Inlet + radiated).
(2) For microphone at position 1 until 4 and 9, the distance will be 1 meter from the centre of the unit’s
surface.
(3) For microphone at position 5 until 8, the distance will be 1 meter 1 meter at each x, y & z axis.
Standard: EN 12102
Содержание UATN60CGXY1
Страница 1: ...TECHNICAL MANUAL Package Air Conditioner Rooftop UATN C Series Cooling only 50Hz R410A TM 5RT C GA A1...
Страница 2: ......
Страница 4: ...Table of Contents ii...
Страница 48: ...44 Wiring Diagrams Wiring Diagrams Model UATN60 90C...
Страница 49: ...45 Wiring Diagrams Model UATN120 150 180C...
Страница 50: ...46 Wiring Diagrams Model UATN210 240 300C...
Страница 55: ......