10
Application Information
Model
Compressor
Maximum
Continuous
Current (A)
Compressor
Full Load
Current,
FLA (A)
Compressor
Locked Rotor
Current,
LRA (A)
Minimum
Circuit Amps,
MCA (A)
Maximum
Fuse Amps,
MFA (A)
UATN60C
15
8
64
13.7
20.0
UATN90C
20
11
101
19.2
32.0
UATN120C
15/15
8/8
64/64
25.0
32.0
UATN150C
19/19
10/10
100/100
32.2
40.0
UATN180C
20/20
11/11
101/101
35.7
50.0
UATN210C
23/23
13/13
128/128
38.9
63.0
UATN240C
25/25
15/15
139/139
43.9
63.0
UATN300C
35/35
19/19
140/140
53.6
80.0
WARNING
● Before working in this unit, isolate it from the power supply.
● Electrical wiring to this unit and the remote controller shall be installed in accordance with the appropriate requirement
of the local wiring code.
Observe the notes mentioned below when wiring to the terminal block.
Precautions to be taken for power supply wiring.
(Use a round crimp-style terminal for connection to the terminal block.
In case it cannot be used due to unavoidable reasons, be sure to
observe the following instruction.)
CAUTION
● When connecting the connection wires to the terminal block using a single core wire, be sure to perform curling.
Problems with the work may cause heat and fires.
Stripping wire at terminal block
Good
Wrong
Strip wire end
to this point.
Excessive strip length
may cause electrical
shock or leakage.
● Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop.
WARNING
● Transmission wire must be routed at least 50mm away from the power cable.
● Transmission wire should be a shielded wire.
Round crimp-style
terminal
Stranded wire
Содержание UATN60CGXY1
Страница 1: ...TECHNICAL MANUAL Package Air Conditioner Rooftop UATN C Series Cooling only 50Hz R410A TM 5RT C GA A1...
Страница 2: ......
Страница 4: ...Table of Contents ii...
Страница 48: ...44 Wiring Diagrams Wiring Diagrams Model UATN60 90C...
Страница 49: ...45 Wiring Diagrams Model UATN120 150 180C...
Страница 50: ...46 Wiring Diagrams Model UATN210 240 300C...
Страница 55: ......