PAGE 20
Compressor Minimum Off Minutes
(Setup Step 24)
This feature allows the user to set a minimum off time for the compressor.
Settings are 5 mins., 3 mins., or 0 mins.
Number of Compressor Stages
(Setup Step 26)
This feature is for heat pump applications only.
This feature allows the thermostat to control 1 or 2 compressor stages
when configured for heat pump.
Minimum Heat/Cool Setpoint Difference
(Setup Step 25)
This feature allows the user to set the minimum gap between Heat and
Cool setpoints in
AUTO
mode. Select from 0 to 6. If setup step 2 is not set
for
AUTO-CHANGEOVER
, this step will not appear.
Cycles Per Hour
(Setup Step 23)
The Cycles Per Hour setting may limit the number of times per hour your
HVAC unit may energize. For example, at a setting of 6 cycles per hour the
HVAC unit will only be allowed to energize once every 10 minutes. The
Cycles Per Hour limit may be overridden and reset by pressing the UP or
DOWN buttons on the thermostat. Settings are No Limit, 2, 3, 4, 5, or 6.
Installer Setup
This feature allows the user to choose if the wired sensor will be used
as an indoor or outdoor sensor.
Wired Sensor Use
(Setup step 38)
Control To Temp Source
(Setup Step 39)
This feature allows the user to specify which temperature sensor source
the thermostat will use to measure room temperature. The choices are:
Thermostat:
Uses the internal thermostat sensor only.
Remote Sensor:
Uses wireless or wired sensors only.
NOTE:
If a remote sensor is being used, the degree icon on the large room
temperature display will blink.