Troubleshooting
SiENBE07-618_C
88
Service Diagnosis
4.22 Output Overcurrent Detection
Remote Control
Display
L5
Method of
Malfunction
Detection
An output overcurrent is detected by checking the current that flows in the inverter DC section.
Malfunction
Decision
Conditions
A position signal error occurs while the compressor is running.
A speed error occurs while the compressor is running.
An output overcurrent signal is fed from the output overcurrent detection circuit to the
microcomputer.
If the error repeats 16 times, the system is shut down.
Reset condition: Continuous run for about 5 minutes without any other error
Supposed
Causes
Poor installation condition
Closed stop valve
Defective power module
Wrong internal wiring
Abnormal supply voltage
Defective outdoor unit PCB
Defective compressor