8 Commissioning

Installer and user reference guide

45

SERHQ020~0 SEHVX20~64BAW
Split packaged air-cooled water chiller
4P508020-1A – 2018.01

Pump rotation direction

If  the  3-phase  power  input  to  the  indoor  unit  is  not
correctly  wired  (X1M),  the  pump  may  rotate  in  the  wrong
direction.  When  this  happens,  the  pump  may  slowly
overheat  due  to  reduced  air  flow,  fan  ventilation  may  be
reduced  and  the  motor  may  consume  more  power.  The
indicator  on  the  pump  motor  fan  cover  indicates  the
direction  of  rotation  of  the  pump.  Check  operation  of  this
indicator before starting the unit for the first time or when
the position of the indicator has changed. If the indicator is
in  the  white/reflecting  field,  switch  off  the  power  supply
and switch any two of the incoming supply wires at X1M.
The  correct  direction  of  rotation  is  also  shown  by  arrows
on the pump motor fan cover.

a

a

 = pump rotation direction indicator

Pipe size and pipe insulation

Be  sure  that  correct  pipe  sizes  are  installed  and  that  the
insulation work is properly executed.

The 

air purge

 valve is open (at least 2 turns).

Shut-off valves

Be sure that the shut-off valves are correctly installed and
fully open.

Filter

Make sure that the filter is installed correctly.

Damaged equipment

Check  the  inside  of  the  unit  on  damaged  components  or
squeezed pipes.

Brazing

Take  care  not  to  damage  the  piping  insulation  when
brazing field piping.

Water leak

Check the inside of the unit for water leakage. If there is a
water  leak,  try  to  repair  the  leak.  If  the  repair  is
unsuccessful,  close  the  water  inlet  and  outlet  shut-off
valves and call your local dealer.

Installation date and field setting

Be  sure  to  keep  record  of  the  installation  date  on  the
sticker  on  the  rear  of  the  upper  front  panel  according  to
EN60335‑2‑40 and keep record of the contents of the field
setting(s).

Schedule timer form

Fill  out  the  form  at  the  very  end  of  this  document.  When
programming  the  schedule  timer,  this  form  can  help  you
define the required actions for each day.

NOTICE

Operating  the  system  with  closed  valves  will  damage  the
pump.

Once all checks are fulfilled, the unit must be closed, only then can
the unit be powered up. When the power supply to the unit is turned
on,  "

"  is  displayed  on  the  user  interface  during  its  initialization,

which  may  take  up  to  30  seconds.  During  this  process,  the  user
interface cannot be operated.

8.5

Final check

Before switching on the unit, read the following recommendations:

▪ When  the  complete  installation  and  all  necessary  settings  have

been carried out, be sure that all panels of the unit are closed. If
this  is  not  the  case,  inserting  your  hand  through  the  remaining
openings  can  cause  serious  injury  due  to  electrical  and  hot  parts
inside the unit.

▪ The  service  panel  of  the  electrical  component  box  may  only  be

opened by a licensed electrician for maintenance purposes.

DANGER: RISK OF ELECTROCUTION

Do NOT leave the unit unattended when the service cover
is removed.

INFORMATION

During  the  first  running  period  of  the  unit,  the  required
power may be higher than stated on the nameplate of the
unit.  This  phenomenon  is  caused  by  the  compressor,  that
needs  a  continuous  run  time  of  48  hours  before  reaching
smooth operation and stable power consumption.

8.6

To perform a test run of the
outdoor unit

CAUTION

Do  NOT  insert  fingers,  rods  or  other  objects  into  the  air
inlet or outlet. When the fan is rotating at high speed, it will
cause injury.

CAUTION

Do  NOT  perform  the  test  operation  while  working  on
the indoor units.

When performing the test operation, NOT only the outdoor
unit,  but  the  connected  indoor  unit  will  operate  as  well.
Working on an indoor unit while performing a test operation
is dangerous.

8.6.1

Refrigerant added using automatic
charging

The test run will first run the following checks:

▪ Are the stop valves open?

▪ Is the wiring correct?

▪ Piping length

▪ Initial refrigerant state

This  checking  operation  takes  ±3  hours  (±4  hours  in  low  outdoor
temperature) to complete.

The system cannot check the initial refrigerant state if the outdoor or
indoor  temperature  is  out  of  range  (outdoor  temperature:
0~43°C DB, indoor temperature: 20~32°C DB) or if the unit is forced
OFF  during  the  test  run.  In  this  case,  after  performing  the  check
operation,  normal  operation  is  possible  although  error  code 

  is

displayed  on  the  indoor  unit  user  interface  and  the  refrigerant  leak
detection  function  cannot  be  used.  Perform  the  check  operation
again and complete the judgement of initial refrigerant state.

Perform the test run procedure.

8.6.2

Refrigerant added using manual charging
(cooling mode)

The test run will first run the following checks:

▪ Are the stop valves open?

▪ Is the wiring correct?

Содержание SERHQ032BAW1

Страница 1: ...user reference guide Split packaged air cooled water chiller English Installer and user reference guide Split packaged air cooled water chiller SERHQ020BAW1 SERHQ032BAW1 SEHVX20BAW SEHVX32BAW SEHVX40B...

Страница 2: ...utdoor unit 17 6 2 5 To open the electrical component box of the indoor unit 18 6 3 Mounting the outdoor unit 18 6 3 1 About mounting the outdoor unit 18 6 3 2 Precautions when mounting the outdoor un...

Страница 3: ...ield settings on the outdoor unit 59 12 11 ESP curve Indoor unit 60 For the user 60 13 About the system 60 13 1 System layout 60 14 User interface 61 15 Before operation 61 16 Operation 62 16 1 Operat...

Страница 4: ...y ensuring waste batteries are disposed of correctly you will help to prevent potential negative consequences for the environment and human health 1 3 For the installer 1 3 1 General If you are NOT su...

Страница 5: ...r does NOT have to operate WARNING ALWAYS recover the refrigerant Do NOT release them directly into the environment Use a vacuum pump to evacuate the installation NOTICE After all the piping has been...

Страница 6: ...n earth leakage protector Failure to do so may cause electric shock or fire When installing the earth leakage protector make sure it is compatible with the inverter resistant to high frequency electri...

Страница 7: ...ation What to do and know to configure the system after it is installed Operation Operation of the units Commissioning What to do and know to commission the system after it is configured Hand over to...

Страница 8: ...klift arms with a cloth to prevent damaging the unit If the paint on the bottom frame peels off the anti corrosion effect may decrease 3 2 3 To remove the accessories from the outdoor unit Make sure t...

Страница 9: ...the split system with options Where the outdoor and indoor units fit in the system layout 4 2 Identification NOTICE When installing or servicing several units at the same time make sure NOT to switch...

Страница 10: ...n area Heating 0 35 25 5 15 5 EWC 20 25 35 50 LWC TA A B TA Ambient temperature C DB LWC Leaving water condenser temperature C EWC Entering water condenser temperature C A Pull up area B Standard wate...

Страница 11: ...ause water leakage NOTICE This is a class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures CAUTION Applian...

Страница 12: ...cause water leakage NOTICE This is a class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures CAUTION Appli...

Страница 13: ...ticles entering the pipe Use a decent thread sealant to seal connections Capacity class Minimum required flow rate 20 23 l min 32 36 l min 40 46 l min 64 72 l min Field supply components Water pressur...

Страница 14: ...152 64 220 INFORMATION In critical processes or in rooms with a high heat load extra water might be required INFORMATION The temperature step difference can be modified using settings A 02 and F 00 Th...

Страница 15: ...to account Only use dry nitrogen to set the expansion vessel pre pressure Inappropriate setting of the expansion vessel pre pressure will lead to malfunction of the system Changing the pre pressure of...

Страница 16: ...25 1639 SEHVX64BAW 0 22 1747 The local wiring power cord must comply with IEC60245 The wiring type in protected pipes must be H05VV H07RN F must be used in unprotected pipes 5 5 3 Cable requirements I...

Страница 17: ...e outdoor unit on page 17 For service purposes the pushbuttons on the main PCB need to be accessed To access these pushbuttons the electrical component box cover does not need to be opened See 7 2 3 T...

Страница 18: ...allowed O Allowed The height of the foundation must at least be 150 mm from the floor In heavy snowfall areas this height should be increased depending on the installation place and condition The pre...

Страница 19: ...the top plate b a a Attach one L shaped support to the left side of the top plate using 2 screws from the accessory bag b Attach the other L shaped support to the right side of the top plate using 1...

Страница 20: ...The following illustrations show each part required in handling the valve c d a b a Service port and service port cover b Stop valve c Field piping connection d Stop valve cover a b c d e a Service po...

Страница 21: ...refrigerant gas leaks ventilate the area immediately Possible risks Excessive refrigerant concentrations in a closed room can lead to oxygen deficiency Toxic gas may be produced if refrigerant gas co...

Страница 22: ...lowing remaining oil to drip out in case the recovery was not complete Wait until all oil has dripped out 8 Cut the pinched piping off with a pipe cutter just above the brazing point or just above the...

Страница 23: ...when checking the refrigerant piping INFORMATION Also read the precautions and requirements in the following chapters General safety precautions Preparation NOTICE Use a 2 stage vacuum pump with a no...

Страница 24: ...the refrigerant charging process it is in case of larger systems recommended to first pre charge a portion of refrigerant through the liquid line before proceeding with the actual automatic or manual...

Страница 25: ...through this port Step 6a To automatically charge refrigerant INFORMATION The automatic refrigerant charging has limits as described below Out of these limits the system cannot operate the automatic...

Страница 26: ...art the complete charging procedure 5 Press BS4 to perform the temperature range check Result If the temperature is outside the temperature range press BS1 once and complete refrigerant charging at an...

Страница 27: ...ect the malfunction as indicated on the user interface display and restart the complete charging procedure 5 Press BS1 once to complete charging 6 Record the amount that was added on the additional re...

Страница 28: ...nfirm Result LEDs will be blinking in function of the last entered setting factory setting 0 kg 5 Enter the weighed and already recorded amount of additional refrigerant charge not the total amount of...

Страница 29: ...ting valve must be installed in the water system The regulating valve is to be used to regulate the water flow in the system field supply 6 8 4 To fill the water circuit 1 Connect the water supply to...

Страница 30: ...nnected securely Make sure all covers are closed before starting up the unit NOTICE Do NOT operate the unit until the refrigerant piping is complete Running the unit before the piping is ready will br...

Страница 31: ...with the unit located at the inside of the switch box cover 6 9 4 About the electrical wiring NOTICE Be sure to keep the power line and transmission line apart from each other Transmission wiring and...

Страница 32: ...f must be as such that the current carrying wires are tautened before the earth wire is in case the power supply is pulled loose from the stress relief NOTICE When routing earth wires secure clearance...

Страница 33: ...inal block Otherwise the entire system may break down The wiring from the indoor units must be connected to the F1 F2 In Out terminals on the outdoor unit PCB NOTICE Take care of the polarity of the t...

Страница 34: ...ront part of the user interface 2 Fasten the user interface on a flat surface NOTICE Be careful NOT to distort the shape of the lower part of the user interface by overtightening the mounting screws 3...

Страница 35: ...d settings are used for special operation e g 1 time operation recovery vacuuming setting manual adding refrigerant setting etc In such a case it is required to abort the special operation before norm...

Страница 36: ...s B S 1 B S 1 B S 1 a c b a Default situation H1P OFF b Mode 1 H1P flashing c Mode 2 H1P ON BS1 Press BS1 BS1 5 s Press BS1 for at least 5 s INFORMATION If you get confused in the middle of the proces...

Страница 37: ...he BS2 button to make field settings to configure the system The LEDs give a binary representation of the setting value number Setting binary Value Description Fan high static pressure setting In orde...

Страница 38: ...ate field setting first code 3 Press to select the appropriate field setting second code 4 Press and to change the value of the selected field setting 5 Press to save the new value 6 Repeat the previo...

Страница 39: ...he last programmed command 16 00 overruled the previous programmed command 13 00 and will remain active until the next programmed command 19 00 occurs So in order to know the actual setting you should...

Страница 40: ...emperature setpoint B Room setback temperature 5 03 t Time T Temperature Setback configured for leaving water temperature control 2 01 2 02 B A T t 45 C 40 C 5 C 5 02 A Normal leaving water temperatur...

Страница 41: ...tat input 1 heating operation ON 1 OFF 0 External room thermostat input 2 cooling operation ON 1 OFF 0 2 External room thermostat input 1 operation ON 1 OFF 0 External room thermostat input 2 cooling...

Страница 42: ...0 This setting is not applicable E 01 This setting is not applicable E 02 This setting is not applicable E 03 This setting is not applicable E 04 Pump only operation air purge function When installing...

Страница 43: ...nt It is possible that the leaving water temperature becomes lower than the setpoint if the unit is controlled by room temperature 8 Commissioning 8 1 Overview Commissioning This chapter describes wha...

Страница 44: ...nt panel according to EN60335 2 40 and keep record of the contents of the field setting s Switches Make sure that switches are set according to your application needs before turning the power supply o...

Страница 45: ...the user interface during its initialization which may take up to 30 seconds During this process the user interface cannot be operated 8 5 Final check Before switching on the unit read the following...

Страница 46: ...ng sound or the magnetic sound of a solenoid valve may become loud and the LED display may change but these are not malfunctions It is not possible to stop operation using a user interface during the...

Страница 47: ...box are hot Make sure you do NOT touch a conductive section Do NOT rinse the unit This may cause electric shocks or fire 9 2 1 To prevent electrical hazards When performing service to inverter equipm...

Страница 48: ...f valve hose if present Water pressure relief valve Electrical component box Water pressure Water filter pH value Pressure relief valve hose Check whether the pressure relief valve hose is positioned...

Страница 49: ...de Solution recharge operation Close valve A immediately and press the TEST OPERATION button once The operation will restart from the charging mode judgement onwards charging aborted Close valve A imm...

Страница 50: ...bstacles the wall heights have no influence on any indicated service space dimensions b a c d A C B D a e b d e A C B D 2 1 c a c e b d f A C B D 3 a c e b b d A C B D 4 Layout A B C D A B Possibility...

Страница 51: ...ata Installer and user reference guide 51 SERHQ020 032BAW1 SEHVX20 64BAW Split packaged air cooled water chiller 4P508020 1A 2018 01 INFORMATION Further specifications can be found in the technical en...

Страница 52: ...h i a a j j k k m l l m m o n n d d d d p d d d 20 kW a b b c d f e g h i a a a l o l l k k m m m m d d n n n d d d d d j j j d p d 32 kW a Check valve b Electronic expansion valve c Pressure regulati...

Страница 53: ...A B h g k C D a Air purge valve b Temperature sensors R11T R12T R13T R14T c Expansion vessel 12 l d Shut off valve field installed e Water inlet connection f Water outlet connection g Drain port h Wa...

Страница 54: ...ic contactor M1C K2M K3M Magnetic contactor M2C M3C K1R K2R Magnetic relay K2M K3M K3R K5R Magnetic relay Y1S Y3S K6R K9R Magnetic relay E1HC E3HC L1R Reactor M1C M3C Motor compressor M1F M2F Motor fa...

Страница 55: ...circuit 2 K1P Pump contactor K1S Pump overcurrent relay K R A3P PCB relay M1P Pump Q1T Thermostat for expansion vessel heater PS A P Switching power supply Q1DI Earth leakage circuit breaker field su...

Страница 56: ...r reference guide 56 SERHQ020 032BAW1 SEHVX20 64BAW Split packaged air cooled water chiller 4P508020 1A 2018 01 12 8 Technical specifications Outdoor unit INFORMATION For technical and electrical deta...

Страница 57: ...e 70 01 Not applicable Do not change the default value 10 02 Leaving water setback temperature 5 0 10 1 C 03 Room setback temperature 18 17 23 1 C 04 Not applicable Do not change the default value 1 6...

Страница 58: ...cable Do not change the default value 40 E Service mode 00 Not applicable Do not change the default value 0 01 Not applicable Do not change the default value 0 02 Not applicable Do not change the defa...

Страница 59: ...and setting via external control adapter NO YES 18 High static pressure setting OFF ON 22 Automatic night time low noise setting OFF Level 1 outdoor fan with step 6 or lower Level 2 outdoor fan with s...

Страница 60: ...any quality deterioration do not use the unit for cooling precision instruments or works of art NOTICE For future modifications or expansions of your system A full overview of allowable combinations...

Страница 61: ...al electronic parts WARNING This unit contains electrical and hot parts WARNING Before operating the unit be sure the installation has been carried out correctly by an installer NOTICE Never inspect o...

Страница 62: ...ot place the user interface in a place exposed to direct sunlight The LCD display may get discoloured or fail to display the data NOTICE Do not place items which might be damaged by moisture under the...

Страница 63: ...he system 16 3 1 About the clock INFORMATION The clock must be set manually Adjust the setting when switching from summertime to wintertime and vice versa The clock cannot be adjusted if the controlle...

Страница 64: ...is then operated in the leaving water control mode and is not functioning as a room thermostat The remote controller ON OFF status always has priority over the external room thermostat INFORMATION Set...

Страница 65: ...ferent levels of quiet mode operation The desired quiet mode is set through a field setting 1 Press to activate quiet mode operation Result appears on the display If the controller is set to permissio...

Страница 66: ...C 1 OFF ON ON 6 30 0 30 B t 6 30 9 00 16 00 23 00 19 C 19 C 22 C 21 C 42 C 42 C 45 C 44 C 19 C 19 C 22 C 21 C 42 C 42 C 45 C 44 C 3 OFF ON ON 18 C 40 C 40 C 18 C 1 Schedule timer 2 Setback function 3...

Страница 67: ...inking 4 Consult the action s using and 5 Hold down for 5 seconds to program the detailed actions Result The first programmed action appears 6 Select the action number you would like to program or to...

Страница 68: ...ult If is pressed when action number 3 is displayed actions 1 2 and 3 are stored but action 4 is deleted You automatically return to step 6 Press several times to return to previous steps in this proc...

Страница 69: ...imultaneously for 5 seconds 6 After 5 seconds the display will show the next day e g if was selected first This indicates that the day has been copied 7 Press to return to step 2 To delete a mode 1 Pr...

Страница 70: ...ble Contact your dealer for more information When asking your dealer for an intervention always state The complete model name of the unit The manufacturing number stated on the nameplate of the unit T...

Страница 71: ...or indoor unit is not blocked by obstacles Remove any obstacles and make sure the air can flow freely Check if the user interface display shows time to clean the air filter Refer to 17 Maintenance and...

Страница 72: ...opean national and local directives laws regulations and or codes that are relevant and applicable for a certain product or domain Service company Qualified company which can perform or coordinate the...

Страница 73: ......

Страница 74: ......

Страница 75: ......

Страница 76: ...4P508020 1A 2018 01 Copyright 2018 Daikin...

Отзывы: