• Outdoor Unit • Outdoor units optimized for seasonal efficiency • RZQSG-LY1
1
2
• Split - Sky Air • Outdoor Unit
6
2
Specifications
Notes
(1) PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC
(2) See separate drawing for electrical data
(3) Equipment complying with EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-
voltage system with input current \> 16A and
≤
75A per phase
(4) Short-circuit power
(5) See separate drawings for electrical data
(6) European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current larger than 16A
and
≤
75A per phase.
(7) Related to 3D076918
Refrigerant oil
Type
FVC50K
Charged volume
l
0.9
1.35
Piping connections
Liquid
Quantity
1
Type
Flare connection
OD
mm
9.52
Gas
Quantity
1
Type
Flare connection
OD
mm
15.9
Drain
Quantity
5
Type
Hole
ID
mm
-
OD
mm
26
Piping length
OU - IU Min.
m
5
Max.
m
50
System Equiva-
lent
m
70
Charge-
less
m
30
Additional refrigerant charge
kg/m
See installation manual 4P302555-1
Level difference
IU - OU Max.
m
30.0
IU - IU
Max.
m
0.5
Heat insulation
Both liquid and gas pipes
Defrost method
Pressure equalising
Defrost control
Sensor for outdoor heat exchanger temperature
Safety devices
Item
01
High pressure switch
02
Fan motor thermal protection
03
Fuse
2-3 Electrical Specifications
RZQSG100LY1
RZQSG125LY1
RZQSG140LY1
Power supply
Name
Y1
Phase
3N~
Frequency
Hz
50
Voltage
V
380-415
Voltage range
Min.
%
10
Max.
%
10
Current
Zmax
List
Complies to EN61000-3-11
Recommended fuses
A
20
25
Wiring connections
For power supply
Remark
See installation manual 4P302555-1
For connection with
indoor
Remark
See installation manual 4P302555-1
Power supply intake
Outdoor unit only
2-2 Technical Specifications
RZQSG100LY1
RZQSG125LY1
RZQSG140LY1