3
2
• Split - Sky Air • RZQSG-L3/9V1
19
• Outdoor Unit • RZQSG-L3/9V1
2
Specifications
Standard Accessories : Tie-wraps; Quantity : 2;
Standard Accessories : Installation manual; Quantity : 1;
Operation range
Cooling
Ambien
t
Min.
°CDB
-15.0
Max.
°CDB
46
Heating
Ambien
t
Min.
°CWB
-15
Max.
°CWB
15.5
Refrigerant
Type
R-410A
Charge
kg
2.75
2.9
4.0
TCO
2
eq
5.7
6.1
8.4
Control
Expansion valve (electronic type)
GWP
2,087.5
Circuits
Quantity
1
Piping connections
Liquid
Quantity
1
Type
Flare connection
OD
mm
9.52
Gas
Quantity
1
Type
Flare connection
OD
mm
15.9
Drain
Quantity
3
5
Type
Hole
ID
mm
-
OD
mm
26
Piping length
OU - IU Min.
m
5
Max.
m
50
System Equival
ent
m
70
Chargel
ess
m
30
Additional refrigerant charge
kg/m
See installation manual
Level difference
IU - OU Max.
m
15
30.0
IU - IU
Max.
m
0.5
Heat insulation
Both liquid and gas pipes
Refrigerant oil
Type
FVC50K
Charged volume
l
0.75
0.9
1.35
Defrost method
Pressure equalising
Reversed cycle
Defrost control
Sensor for outdoor heat exchanger temperature
Safety devices
Item
01
High pressure switch
02
Fan motor thermal
protection
Low pressure switch
03
Fuse
Fan driver overload protector
04
-
Fuse
2-10 Electrical Specifications
RZQSG71L3V1
RZQSG100L9V1
RZQSG125L9V1
RZQSG140L9V1
Power supply
Name
V1
Phase
1~
Frequency
Hz
50
Voltage
V
220-240
Voltage range
Min.
%
-10
Max.
%
10
Current - 50Hz
Maximum fuse amps (MFA)
A
20
-
Current
Zmax
List
-
Complies to EN61000-3-11
Recommended fuses
A
25
40
Current - 60Hz
Maximum fuse amps (MFA)
A
-
Wiring connections
For power supply
Remark
See installation manual outdoor unit
For connection with
indoor
Remark
See installation manual outdoor unit
Power supply intake
Outdoor unit only
2-9 Technical Specifications
RZQSG71L3V1
RZQSG100L9V1
RZQSG125L9V1
RZQSG140L9V1
Содержание RZQSG-L3/9V1
Страница 1: ...Air Conditioning Technical Data RZQSG L3 9V1...
Страница 2: ......
Страница 23: ...3 3 Split Sky Air RZQSG L3 9V1 21 Outdoor Unit RZQSG L3 9V1 3 Electrical data 3 1 Electrical Data...
Страница 24: ...Outdoor Unit RZQSG L3 9V1 3 Split Sky Air RZQSG L3 9V1 22 3 Electrical data 3 1 Electrical Data...
Страница 29: ...3 5 Split Sky Air RZQSG L3 9V1 27 Outdoor Unit RZQSG L3 9V1 5 Combination table 5 1 Combination Table...
Страница 30: ...Outdoor Unit RZQSG L3 9V1 6 Split Sky Air RZQSG L3 9V1 28 6 Capacity tables 6 1 Cooling Heating Capacity Tables...
Страница 34: ...Outdoor Unit RZQSG L3 9V1 7 Split Sky Air RZQSG L3 9V1 32 7 Dimensional drawings 7 1 Dimensional Drawings...
Страница 35: ...3 7 Split Sky Air RZQSG L3 9V1 33 Outdoor Unit RZQSG L3 9V1 7 Dimensional drawings 7 1 Dimensional Drawings...
Страница 36: ...Outdoor Unit RZQSG L3 9V1 8 Split Sky Air RZQSG L3 9V1 34 8 Centre of gravity 8 1 Centre of Gravity...
Страница 37: ...3 8 Split Sky Air RZQSG L3 9V1 35 Outdoor Unit RZQSG L3 9V1 8 Centre of gravity 8 1 Centre of Gravity...
Страница 38: ...Outdoor Unit RZQSG L3 9V1 8 Split Sky Air RZQSG L3 9V1 36 8 Centre of gravity 8 1 Centre of Gravity...
Страница 39: ...3 9 Split Sky Air RZQSG L3 9V1 37 Outdoor Unit RZQSG L3 9V1 9 Piping diagrams 9 1 Piping Diagrams...
Страница 40: ...Outdoor Unit RZQSG L3 9V1 9 Split Sky Air RZQSG L3 9V1 38 9 Piping diagrams 9 2 Piping Diagram Twin Application...
Страница 53: ...3 12 Split Sky Air RZQSG L3 9V1 51 Outdoor Unit RZQSG L3 9V1 12 Installation 12 1 Installation Method...
Страница 54: ...Outdoor Unit RZQSG L3 9V1 12 Split Sky Air RZQSG L3 9V1 52 12 Installation 12 1 Installation Method...
Страница 55: ...3 12 Split Sky Air RZQSG L3 9V1 53 Outdoor Unit RZQSG L3 9V1 12 Installation 12 1 Installation Method...
Страница 56: ...Outdoor Unit RZQSG L3 9V1 13 Split Sky Air RZQSG L3 9V1 54 13 Operation range 13 1 Operation Range...