• Outdoor Units • R-410A • RZQS71-140C7V1B
1
5
• Split Sky Air • Outdoor Units
19
5
Capacity tables
5 - 2
Cooling capacity tables
RZQS140C (Pair)
Cooling
Cooling capacity
Indoor
Outdoor temp. (°CDB)
EWB
EDB
25
30
35
40
(°C)
(°C)
TC
(kW)
SHC
(kW)
CPI
(-)
TC
(kW)
SHC
(kW)
CPI
(-)
TC
(kW)
SHC
(kW)
CPI
(-)
TC
(kW)
SHC
(kW)
CPI
(-)
16.0
22
12.3
8.29
0.76
12.2
8.37
0.89
12.5
8.73
0.99
12.1
8.46
1.09
18.0
25
14.0
9.09
0.83
13.6
8.91
0.91
13.1
8.70
1.00
12.6
8.44
1.10
19.0
27
14.4
9.06
0.84
13.9
8.89
0.91
13.4
8.68
1.00
12.8
8.42
1.10
19.5
27
14.5
9.05
0.84
14.1
8.87
0.91
13.5
8.66
1.00
13.0
8.41
1.10
22.0
30
15.2
8.93
0.85
14.7
8.77
0.92
14.3
8.57
1.01
13.7
8.32
1.11
24.0
32
15.8
8.81
0.85
15.3
8.64
0.93
14.8
8.45
1.02
14.3
8.22
1.12
3TW28149-1
SYMBOLS
AFR:
Air flow rate
(m
3
/min)
BF:
Bypass factor
EWB:
Entering wet bulb temp.
(°CWB)
EDB:
Entering dry bulb temp.
(°CDB)
TC:
Total cooling/heating capacity
(kW)
SHC:
Sensible heating capacity
(kW)
PI:
Power input
(kW)
(comp.+outdoor fan motor)
CPI:
Coefficient of power input.
(-)
Caution:
TC and SHC are shown by kW
NOTES
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark
j
show the max. at standard conditions.
On the figure the mark
Q
show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. On the tables
Q
show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m
3
/min.) x (1
−
BF) x (DB*
−
EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)
Corresponding refrigerant piping length
: 7.5 m
Level difference
: 0 m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.
(Pair)
FBQ140
AFR
(BF)
35
(0.14)
10. Rated power input of each model is tabulated below.
(Pair)
Outdoor
RZQS140C7
Indoor
FBQ140B8
Cooling
4.97kW
Heating
4.99kW
Capacity range
Rated point
Cooling capacity (kW)
Coefficient
of
power
input.
(-)