1

3

• Split Sky Air • Outdoor Units

11

3

Electrical data

3D057296C

SYMBOLS

MCA

: Min. Circuit Amps (A)

TOCA

: Total Over Current Amps (A)

MFA

: Max. Fuse Amps (A) (See note 7)

MSC

: MSC means the max. current during the

starting of compressor. (A)

RLA

: Rated Load Amps (A)

OFM

: Outdoor Fan Motor (A)

IFM

: Indoor Fan Motor

FLA

: Full Load Amps

kW

: Fan Motor Rated Output (kW)

Max. 50Hz 264V

Min. 50Hz 198V

Max. 50Hz 264V

Min. 50Hz 198V

RZQS125-140C

Unit combination

Power supply

Comp.

OFM

IFM

Indoor unit

Outdoor unit

Hz-volts

Voltage range

MCA

TOCA

MFA

MSC

RLA

kW

FLA

kW

FLA

NOTES

1

RLA is based on the following conditions:
Power supply: 50Hz - 230V
Cooling
Indoor temperature 27°CDB/19°CWB
Outdoor temperature 35°CDB
Heating
Indoor temperature 20.0°CDB
Outdoor temperature 7.0°CDB/6.0°CWB

2

TOCA means the total value of each OC set

3

Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed operation range limits

4

Maximum allowable voltage unbalance between phases is 2%

5

MCA represents maximum input current., MFA represents capacity which may accept MCA
(next lower standard fuse rating, min.15A)

6

Select wire size based on the larger value of MCA or TOCA

7

MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)

Содержание RZQS71-140C7V1B

Страница 1: ...technical data Split Sky Air air conditioning systems RZQS71 140C7V1B EEDEN08 100...

Страница 2: ...the Eurovent Directory Daikin s unique position as a man ufacturer of air conditioning equip ment compressors and refrige rants has led to its close involve ment in environmental issues For several ye...

Страница 3: ...technical data Split Sky Air air conditioning systems RZQS71 140C7V1B EEDEN08 100...

Страница 4: ...cations 9 3 Electrical data 10 4 Options 12 5 Capacity tables 13 Combination table 13 Cooling capacity tables 15 Heating capacity tables 22 6 Dimensional drawing centre of gravity 27 Dimensional drawi...

Страница 5: ...rgy efficiency and very low sound level An inverter driven compressor allows the capacity to be adjusted precisely to match variations in room and outside temperatures During start up the room can be...

Страница 6: ...capacity Standard kW 7 1 10 0 12 5 13 4 Heating capacity Standard kW 8 0 11 2 14 0 15 5 Power Input Cooling Standard kW 2 52 3 83 4 4 4 97 Heating Standard kW 2 40 3 47 4 24 4 99 For combination indo...

Страница 7: ...8 10 10 Face Area m 0 641 0 641 0 98 0 98 Nr of Stages 34 34 52 52 Tube type Hi XSS 8 Fin Type WF fin Treatment Anti corrosion treatment PE Fan Type Propeller Discharge direction Horizontal Quantity 1...

Страница 8: ...ent m 40 70 70 70 Chargeless m 30 30 30 30 Additional Refrigerant Charge kg m see installation manual 4PW40416 1 see installation manual 4PW34874 1 Installation height difference Maximum m 15 30 30 0...

Страница 9: ...98 198 Maximum V 264 264 264 264 Current Rsce Sse kVA Equipment complying with EN 61000 3 12 Recomended fuses A 20 20 32 32 Wiring connections For Power Supply Remark see installation manual 4PW40416...

Страница 10: ...WB 2 TOCA means the total value of each OC set 3 Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed operation range li...

Страница 11: ...NOTES 1 RLA is based on the following conditions Power supply 50Hz 230V Cooling Indoor temperature 27 CDB 19 CWB Outdoor temperature 35 CDB Heating Indoor temperature 20 0 CDB Outdoor temperature 7 0...

Страница 12: ...1 140C7V1B 4 Options Available options for RZQS100 140C7V1B Name of option Kit name RZQS125C7V1B RZQS140C7V1B Central drain pan kit KKPJ5F180 Refrigerant branch piping Twin KHRQ22M20TA Triple KHRQ127H...

Страница 13: ...indoor units installed in same room 4 When different indoor models are used in combination designate the infrared remote controller that is equipped with the most functions as the main unit In table a...

Страница 14: ...dividual indoor capacities are not given because the combinations are for simultaneous operation indoor units installed in same room 3 When different indoor models are used in combination designate th...

Страница 15: ...mark Q show rated capacity and rated coefficient of power input However the max capacity is not guaranteed except at standard condition 3 On the tables Q show rated capacity and rated coefficient of...

Страница 16: ...except at standard condition 3 On the tables Q show rated capacity and rated coefficient of power input 4 SHC is based on each EWB and EDB SHC SHC correction for other dry bulb SHC 0 02 x AFR m 3 min...

Страница 17: ...SHC is based on each EWB and EDB SHC SHC correction for other dry bulb SHC 0 02 x AFR m 3 min x 1 BF x DB EDB Add SHC to SHC 5 Capacities are based on following conditions Outdoor air 85 RH however th...

Страница 18: ...n 3 On the tables Q show rated capacity and rated coefficient of power input 4 SHC is based on each EWB and EDB SHC SHC correction for other dry bulb SHC 0 02 x AFR m 3 min x 1 BF x DB EDB Add SHC to...

Страница 19: ...W NOTES 1 Ratings shown are net capacities which include a deduction for indoor fan motor heat 2 On the figure the mark j show the max at standard conditions On the figure the mark Q show rated capaci...

Страница 20: ...Units 20 Outdoor Units R 410A RZQS71 140C7V1B 5 Capacity tables 5 2 Cooling capacity tables 3TW29069 3 RZQS71 100C7V1B Capacity Field piping length m Cooling Heating Capacity in function of field pip...

Страница 21: ...S71 140C7V1B 1 5 Split Sky Air Outdoor Units 21 5 Capacity tables 5 2 Cooling capacity tables 3TW29069 3 RZQS125 140C Capacity Field piping length m Cooling Heating Capacity in function of field pipin...

Страница 22: ...of power input However the max capacity is not guaranteed except at standard condition 3 On the tables Q show rated capacity and rated coefficient of power input 4 SHC is based on each EWB and EDB SHC...

Страница 23: ...rated capacity and rated coefficient of power input 4 SHC is based on each EWB and EDB SHC SHC correction for other dry bulb SHC 0 02 x AFR m 3 min x 1 BF x DB EDB Add SHC to SHC 5 Capacities are bas...

Страница 24: ...r flow rate and BF are tabulated below Pair Model FCQH125C FCQ125C FBQ125 FHQ125 FAQ125 FVQ125 AFR BF 32 5 0 19 27 5 0 19 35 0 14 30 0 13 45 0 25 32 0 16 Twin Model FCQ60Cx2 FFQ60x2 FBQ60x2 FHQ60x2 AF...

Страница 25: ...which include a deduction for indoor fan motor heat 2 On the figure the mark j show the max at standard conditions On the figure the mark Q show rated capacity and rated coefficient of power input Ho...

Страница 26: ...point Heating capacity kW Coefficient of power input NOTES 1 Ratings shown are net capacities which include a deduction for indoor fan motor heat 2 On the figure the mark j show the max at standard c...

Страница 27: ...5 Refrigerant piping intake 6 Power supply wiring intake knock out hole J34 7 Control wiring intake Knock out hole J27 8 Drain outlet RZQS71 100C Hole for anchor bolt 4 M12 3TW26364 1 1 Gas pipe conne...

Страница 28: ...3 1 6 Split Sky Air Outdoor Units 28 Outdoor Units R 410A RZQS71 140C7V1B 6 Dimensional drawing centre of gravity 6 2 Centre of gravity 4TW30469 3 RZQS71 100C7V1B 4TW29169 4 RZQS125 140C...

Страница 29: ...ressure switch Filter Low pressure sensor 3TW29165 2 RZQS71 140C Twin Indoor unit Field piping J15 9 Field piping J9 5 Low pressure sensor Heat exchanger Filter Stop valve with service port 5 16 flare...

Страница 30: ...e branch and the indoor units should have the same size as the indoor connections 3TW29165 4 RZQS125 140C Double twin Indoor unit Field piping J15 9 Field piping J9 5 Low pressure sensor Heat exchange...

Страница 31: ...board Main A2P Printed circuit board Inverter BS1 BS4 Push button switch C1 C3 Capacitor DS1 Dip switch F1U Fuse T 6 3A 250V F6U Fuse T 3 15A 250V H1P 7P A2P Light emitting diode service monitor oran...

Страница 32: ...sure level A scale according to IEC 3 Reference acoustic pressure 0dB 20 Pa 4 Data is valid at nominal operation condition Measuring location discharge side 3TW30477 1 Sound pressure level dB Octave b...

Страница 33: ...peration condition 3 dB A A weighted sound pressure level A scale according to IEC 4 Reference acoustic pressure 0dB 20 Pa Measuring location discharge side 3TW29177 1 Sound pressure level dB Octave b...

Страница 34: ...ZQS100C7V1B NOTES 1 dB A A weighted sound power level A scale according to IEC 2 Reference acoustic intensity 0dB 10E 6 W m_ 3 Measured according ISO3744 3TW29167 3 Sound power level dB Octave band ce...

Страница 35: ...er row RZQS71 140C A Non stacked installation 2 Obstacles exist in front of the air inlet B Stacked installation Legend C Multiple row installation Relation of dimensions of H A and L are shown in the...

Страница 36: ...e icing To reduce the freeze up operation indoor de icing frequency it is recommended to install the outdoor unit in a location not exposed to wind 3TW29063 1A RZQS125 140C Model name RZQS125C7V1B RZQ...

Отзывы: